R911418827, Edition 01, 4 / 8
6
Object directory
6.1 CoE standard objects
The object directory of the module contains objects that can
be triggered via SDO services. These are defined in the ETG
standards:
Index
(hex)
Name
1000
Device type
1001
Error register
1008
Device name
1009
Hardware version
100A
Software version
1018
Identify
10F1
Error settings
10F3
Diagnosis history
10F8
Timestamp object
1Ann
PDO mapping TxPDO
1C00
Sync manager type
1C12
Sync manager 2 assignment
1C13
Sync manager 3 assignment
1C32
SM output parameter
1C33
SM input parameter
F000
Modular device profile
F100
Device state
F800
Device settings
6.2 Module-specific CoE objects
Objects with a module-specific design are described in the
following table.
Index
(hex)
Object
name
Data type Direc-
tion
Error,
warning,
informa-
tion
Diagnostic
number,
description
Unit
6000
6010
6020
6030
Channel 1, 2, 3, 4
60x0:01
Value
Int16
IN
‒
‒
μ
A
60x0:02
Underrange Bit
IN
W
0x2360
‒
60x0:03
Overrange Bit
IN
W
0x8910
‒
60x0:04
Limit 1
2Bit
IN
‒
Bit0: Value
≤ Limit 1
Bit1: Value
≥ Limit 1
‒
60x0:06
Limit 2
2Bit
IN
‒
Bit0: Value
≤ Limit 2
Bit1: Value
≥ Limit 2
‒
A000:0
Material
number
String(20) IN
‒
‒
‒
A010:0
Full serial
number
String(20) IN
‒
‒
‒
F100:01
Periphery
voltage ok
Bit
IN
I
0x3400
‒
F100:02
Error
Bit
IN
E
0x1000
‒
6.3 COE objects for parameterization
The module can be parameterized using these objects. Each
channel can be freely parameterized. The initial value for the
objects is "0" or "false".
The module does not remanently save the parameter values.
To automatically apply the settings required upon each bus
start, set the values in the start parameters of the engi-
neering.
Index
(hex)
Object name Data type
Access Unit
Description
8000
8010
8020
8030
Channel 1, 2, 3, 4 settings
80x0:01 User gain
Int32
RW
‒
‒
80x0:02 User offset
Int16
RW
‒
‒
80x0:03 Limit 1
Int16
RW
μ
A
‒
80x0:04 Limit 2
Int16
RW
μ
A
‒
80x0:05 User scale
enable
Bit
RW
‒
Enabling the User Scale
calculation
80x0:06 Limit 1
enable
Bit
RW
‒
Enabling of limit value
check "Limit 1"
80x0:07 Limit 2
enable
Bit
RW
‒
Enabling of limit value
check "Limit 2"
80xE:01 ADC Raw
value
Int16
RO
‒
‒
F800
Device Settings
F800:01 Oversam-
pling factor
3Bit
RW
‒
Oversampling Rate
(0, 2, 4, 8, 16, 32, 64)
7
Process data of the module
The module has data that is inserted into the cyclic process
data image. Depending on the setting "Standard" or "com-
pact", the module is represented as shown in the following
tables.
Diagnostic information can also be retrieved via acyclic serv-
ices using CoE. They are shown as indices 80x0 (hex) (see ).
The current values as well as the diagnostic data can be
shown and hidden in the Engineering. This allows to reduce
the amount of data in the application.
Process data consists of the value and the diagnostic data in
the standard representation: