19 / 50
ctrlX CORE X7
Interface description
Bosch Rexroth AG
R911419122, Edition 01
No.
Name
Connection type
Connector type
(integrated)
Mating connector and cable
(From outside)
⑥
⑦
XF50
XF52
Ethernet
10/100/1000 MBit
Ethernet (configurable)
XF52 is TSN-capable (Time-Sensitive Networking)
RJ45 socket
8-pin
RJ45 plug
(twisted pair, 8-wire)
⑧
⑨
⑩
XF10
XF11
XF12
Ethernet
10/100/1000 MBit
HMI and engineering port
RJ45 socket
8-pin
RJ45 plug
(twisted pair, 8-wire)
⑪
PH02
Display port
Display port socket
Display port plug
NOTICE
Damage of the device by plug mounting under voltage!
−
Before mounting or dismounting components, disconnect the control -
including its components - from voltage.
−
Connect the voltage only after the control and its components have been
set up.
9.1.1
Local bus interface EtherCAT of ctrlX CORE
PLUS
X7
The local bus connected to the ctrlX CORE
PLUS
at the right is a 100 MBit/s LVDS EtherCAT bus
and the cycle time between 1
ms and 10
ms. The ctrlX CORE
PLUS
can be extended with up to 20
ctrlX I/O modules. The number of connectable modules depends on the total current consumption
of the ctrlX I/O modules. The ctrlX CORE
PLUS
can provide up to 3
A for the current supply of the
modules. The ctrlX CORE
PLUS
supplies the connected I/O modules with the logic voltage U
L
and the
periphery voltage U
P
. The voltages and currents fed in are measured internally and applied to the
process data. For U
L
, only the current consumption of the infeed terminal and the I/O modules. For
the integration into the parent system, the respective ESI files are available. For the ESI files, go to
http://www.boschrexroth.com/electrics
.
Synchronizing the application
The application is synchronized in the "SM synchronous" mode.
Int