4.4.3.4
Enable/Disable Delayed Day Mode
The Delayed Day Mode is configured from Control Level 3. This mode causes the panel to respond to high sensor
signals by sounding the panel buzzer and displaying a warning message at the alphanumeric display. The panel delays
alarm activation for a programmed period. Configuration parameters allow variations in time of day and zones affected.
The Control Level 2 operator may enable or disable the Delayed Day Mode through the Enable or Disable Menu.
To enable the Delayed Day Mode, select 4) Day Modes, from the Enable Menu.
The display will prompt for the programmed number of days. To accept as prompted, press the [Yes] key.
To change from the prompted number of days, press the [Change] key, enter the desired number of days and press the
[Enter] key.
Enter 0 days to disable the Delayed Day Mode. Enter 200 days to permanently enable the Delayed Day Mode.
Note:
If the Delayed Day Mode has not been programmed into the panel, pressing 4) Day Modes from the Enable or Disable
Menu will return the alphanumeric display to the Main Menu.
4.4.3.5
Enable/Disable Relays
Select 5) Disable, from the Main Menu to disable relays during testing. The panel will then display the Disable Menu.
Select 5) Outputs. The display shows the following:
1) Sounders 2) Relays
ENABLED ENABLED
Figure 17: Outputs Menu
Note:
NAC devices such as bells, horns and strobes, all of which are sounders, cannot be enabled or disabled from Control
Level 2.
Select 2) Relays. The panel buzzer will sound, the System Trouble LED will light and the alphanumeric display message
indicates that the relays are disabled.
Press the [Trouble Silence] key to silence the buzzer. The Trouble Silenced LED will light.
Note:
Any disabled outputs must be enabled before the system can be reset.
To enable the outputs, press the [No] key to revert to the Main Menu.
[ACTIVE] 1) Commission 2) Test 3) Time [1]
4) Enable 5) Disable 6) Print 7) View
Figure 18: Main Menu
Enter the Enable Menu by selecting 4) Enable.
Select 5) Outputs.
Select 2) Relays. The system will reset and the Trouble Silenced LED will go out.
Press the [No] key to return to the Main Menu.
Control Level 2
National Security Systems (800)457-1999
http://www.nationalsecuritysystems.com