Unexpected system start-up due to installing
energized components!
WARNING
●
Disconnect the complete station and the components before mounting or
demounting the components! Connect the voltage only after the entire station
has been set up.
●
All safety-related components of the system (wiring, connected sensors and
commanders, configuration, contactor monitoring) have to meet the
corresponding safety standard (e.g. DIN EN 62 061, DIN EN 60204 or DIN EN
ISO 13 849-1).
●
The voltage supply has to fulfill the regulations for extra-low voltages with
safe separation (SELV, PELV) in accordance with EN 60664 and EN 50178
(equipment of electrical power installation with electronic devices) .
●
The external voltage supply of the device has to be able to bridge brief mains
voltage failures of 20 ms as specified in EN60204-1. Otherwise, the SafeLogic
compact control can sporadically switch off in case of temporary voltage
drops.
●
To ensure electromagnetic compatibility (EMC), the DIN mounting rail must
be connected to functional earth (FE). Additionally, connect all network cable
shields directly at the control cabinet entrance to a common FE ground line.
Damages due to electrostatic discharges!
NOTICE
Ensure that suitable ESD protective measures are taken during mounting.
Otherwise the devices may be damaged.
Connecting Sercos cables:
1. Connect the Sercos cables to the XFE1 and XFE2 connections.
2. Fix the cables to avoid damage due to vibration.
3. Connect the cable shields of the Sercos cables directly at the control
cabinet input to the mutual functional earth (FE).
11 Commissioning
No system commissioning without approval by a qualified person!
Ensure that qualified staff checks, documents and releases the
system before the initial commissioning of the system in which the
SafeLogic compact system is used.
The SafeLogic compact system is configured using the configuration software
SafeLogic Designer either via the RS232 interface of the SLC-3-CPUx module or
via the Ethernet interface of a SafeLogic compact Ethernet Gateway. For a
detailed description of the configuration, refer to the operating instructions
Sercos Gateway
Bosch Rexroth AG
Commissioning
DOK-CONTRL-SLC*GW*GS3S-IT03-EN-P
19/31
Содержание R911172765
Страница 1: ...IndraControl SafeLogic compact Sercos Gateway Operating Instructions R911338431 Edition 03 ...
Страница 30: ...Bosch Rexroth AG Sercos Gateway 26 31 DOK CONTRL SLC GW GS3S IT03 EN P ...
Страница 33: ...Sercos Gateway Bosch Rexroth AG DOK CONTRL SLC GW GS3S IT03 EN P 29 31 ...
Страница 34: ...Bosch Rexroth AG Sercos Gateway 30 31 DOK CONTRL SLC GW GS3S IT03 EN P ...
Страница 35: ...Notes Sercos Gateway Bosch Rexroth AG ...