Bosch Security Systems | 2005-04 | 9922 141 10364en
Plena Voice Alarm System
| Basic System Manual | Operation
en
| 39
5.6.7
Distribute the alarm message
Distributing the default alarm message is similar to
distributing the default alert message (see section 5.6.6).
Push the
Alarm message
button instead of the
Alert
message
button (see figure 5.19).
5.7 Fault
state
5.7.1
Introduction
If a supervised function fails, the voice alarm controller
enters the fault state and:
•
Starts a beeper. The beeper is switched off when the
fault is acknowledged (see section 5.7.2).
•
Closes the
Fault Status NO
output contact. This
status output contact is opened again when the fault
is reset (see section 5.7.3).
•
Lights a fault indicator on the front panel that
indicates the source of the fault (see section 5.7.4).
The indicator is switched off when the fault is reset
(see section 5.7.3).
5.7.2
Acknowledge the fault state
The beeper can be switched off by acknowledging the
fault state with the
Fault Ack
button (see figure 5.20).
The following buttons also acknowledge the fault state
and stop the beeper:
•
Alert
button
•
Alarm
button
•
PTT button of the emergency microphone
5.7.3
Reset the fault state
Reset the fault state by pushing the
Fault Reset
button
(see figure 5.21). In order to reset the fault state, it first
must be acknowledged (see section 5.7.2). When the
Fault Reset
button is pushed, the fault indicators are
switched off and the status of the system is checked.
•
If the fault is not resolved, the fault indicators are
switched on again. The beeper remains off. It is only
switched on if a new fault occurs or if the resolved
fault occurs again.
•
If the fault is resolved, the fault indicators remain off.
figure 5.19: Alarm message button
figure 5.20: Fault Ack button
Indicator test
EMG mic
All call
Alert message
Alarm message
Zone select
Zone1
Zone2
Fault
Reset
EMG
Ack
figure 5.21: Fault Reset button
Zone select
Zone1
Zone2
Fault
Reset
EMG
Ack