The power cord must be a three-conductor type (two
current carrying conductors; one ground conductor)
terminated on one end by an IEC 60320 appliance
coupler (for connection to the midspan), and on the
other end by a plug containing a ground (earthing)
contact.
–
The power cord must be rated for a minimum of 250
VAC RMS operation, with a minimum rated current
capacity of 5 Amps (or a minimum wire gauge of 18
AWG (0.75mm
2
).
–
Midspans installed in Australia require power cords
with a minimum wire gauge of 16 AWG (1.0 mm
2
).
–
A voltage mismatch can cause equipment damage and may
pose a fire hazard. If the voltage indicated on the label is
different from the power outlet voltage, do not connect the
midspan to this power outlet.
–
The AC wall socket-outlet must be near the midspan and
easily accessible. You can remove AC power from the
midspan by disconnecting the AC power cord from either
the wall socket-outlet or the midspan appliance coupler.
–
The PoE injector "Data In" and "Data & Power Out" ports
are shielded RJ45 data sockets. They cannot be used as
Plain Old Telephone Service (POTS) telephone sockets.
Only RJ45 data connectors can be connected to these
sockets.
–
The Data In and Data & Power Out interfaces are qualified
as SELV (Safety Extra-Low Voltage) circuits according to
IEC 60950-1. These interfaces can only be connected to
SELV interfaces on other equipment.