PI
−
34.62c
Product Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 10 von 30
BDL
−
F.01U.002.709
A5.en / 29.12.2004
ST
−
FIR/ PRM1 / deh
6. Functional Description
Smoke and contamination are measured separately with the NOM 100/NOM K 100.
For
smoke measurement
, a light source sends 15 light flashes through the mea-
suring area one after the other at one second intervals.
For
contamination measurement
, an additional light source then sends a light
flash to the opposite interior wall.
In both cases, the light, which contacts a photo diode, provides information about
quiescent state, contamination or alarm.
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
14 15
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
4
5
Threshold
Alarm
Number of
Light flashes for smoke measurement
Light flashes for contamination measurement
Scattered light when there is smoke
Î
Reflection light if there is contamination
3
2
1
light flashes