Maintenance
Type L 309
Power Supply Module
13
1070 078 131-104 (00.05) GB
6. Maintenance
The power supply module is maintenance-free. However, a faulty connection or
mains overvoltages can cause an activation of the protective fuses in the device. If
necessary, these can be replaced by the customer himself.
Any other defects should be remedied by the manufacturer.
WARNING!
- Danger of life through electrical voltage!
Disconnect the power supply module from the mains before locating faults or
replacing fuses!
CAUTION!
- Danger of personal injury or damage to property!
Only use the fuse types and ratings specified. Fuses must not be bridged!
The following fuses may be used:
F1: M 1.25 A
27 V A.C. output voltage (X1/1)
F2: M 2.5 A
24 V D.C. output voltage (X1/8)
F3: M
4
A
rectifier input (for generating the
24 V D.C. output voltage)
F4: FF 6.3 A 500 V 6.3 x 32 mm
mains transformer primary input (L2)
F5: FF 6.3 A 500 V 6.3 x 32 mm
mains transformer primary input and
measuring transformer primary input
(L1*)
F6: FF 6.3 A 500 V 6.3 x 32 mm
measuring transformer primary input (V)
F1
F2
F3
F4
F5
F6
!
!
Содержание L 309 Series
Страница 1: ...Power Supply Module Technical Information L 309 150 L 309 250 104 Edition ...
Страница 3: ......
Страница 5: ...Flexible Automation Type L 309 Power Supply Module 1070 078 131 104 00 05 GB ...
Страница 15: ...Flexible Automation Type L 309 Power Supply Module Structure 2 1070 078 131 104 00 05 GB ...
Страница 27: ...Maintenance Type L 309 Power Supply Module 14 1070 078 131 104 00 05 GB ...
Страница 31: ...Dimensioning instructions Type L 309 Power Supply Module 18 1070 078 131 104 00 05 GB ...
Страница 33: ...Fault messages Type L 309 Power Supply Module 20 1070 078 131 104 00 05 GB ...
Страница 36: ...A 1 1070 078 131 104 00 05 GB 1070 078 131 104 00 05 GB TI WS AT VWS Printed in Germany ...