9
Interface to SPC Panel/System
56
Bosch Security Systems
Seismic Detectors Application Guide
I-200153-1
04.2016
Automatic test is only available in the unrestricted mode of operation. See the SPC doc-
umentation for more information.
System status
Seismic
test
Result
Reporting & Display
Set
Yes
Pass
Successful test result posted to system log
Yes
Fail
A failure will be posted to the system log together
with the zone(s) of the failed detector(s).
When the system is unset, a seismic failure report
will be displayed on the keypad. The system cannot
be set until this fault is cleared
Unset
Yes
Pass
Successful test result posted to system log
Yes
Fail
A failure will be posted to the system log together
with the zone(s) of the failed detector(s).
A seismic failure report will be displayed on the key-
pad.
The system cannot be set until this fault is cleared
Table 9-2: Automatic seismic test
9.2.3
Automatic test when setting
In the configuration option page, there is an option to force a test on the seismic detectors each
time the system is set. The normal exit time of the system is delayed by the duration of the seismic
test.
Setting time
System arming time
Seismic test time
30 seconds
Exit time
45 seconds (default)
Total setting time
75 seconds
As per the automatic seismic test, the results are logged and displayed in a similar manner;
Automatic test
on set
Yes
Pass
Successful test result posted to system log
Yes
Fail
A failure will be posted to the system log together
with the zone(s) of the failed detector(s).
A seismic failure report will be displayed on the key-
pad.
The system cannot be set until this fault is cleared
For all test options, if a seismic detector is not served by a form of test transmitter, inter-
nal GMXS1 or external GMXS5 or if the test device is defective or out of range, then a
fail will be recorded for each test.
With the unrestricted mode selected in the SPC panel, system testing can be a combina-
tion of automatic test and automatic test when setting. In this case, all seismic detectors
are tested each time the system is set.