Heatronic boiler control settings
57
Greenstar – 6721822579 (2021/01)
Service function 1.b: Maximum DHW output
The hot water output can be adjusted between the minimum and
maximum DHW outputs to suit the heat transfer capacity of the DHW
tank coil.
▶ Select service function 1.b.
▶ Select the DHW output in MBH (kW) and determine the associated
setting in percent (%).
▶ Enter the setting (
▶ Save the setting (
▶ Record the set DHW output in the commissioning log (
page 78).
▶ Exit the service functions.
The display returns to the supply temperature.
The
factory setting
is the maximum nominal output:
100
(100 %).
Service function 1.E: Pump mode for space heating operation
If an outdoor temperature sensor for an outdoor reset control is
connected, pump control mode 04 is automatically set.
•
Pump control mode 00 (automatic mode)
: The BUS control
controls the central heating pump.
•
Pump control mode 01
: For heating systems without control. When
there is a demand for heat, the central heating pump and the burner
start up.
•
Pump control mode 02
: Do not use.
•
Pump control mode 03
: The central heating pump runs continuously
(exceptions: See heating control operating instructions).
•
Pump control mode 04
: Intelligent control of central heating pump
in heating systems with outdoor reset control. The heating zone
pump is only switched on when needed.
Default setting
is
00
.
Service function 1. F: Pump mode (only heating boiler ZBR...-3A)
NOTICE
System damage or boiler malfunction!
▶ Never change the setting of this service function on combi boiler
ZWB...-3A appliances.
Based on this setting, the pump connected to the Heatronic or 3-way
valve are controlled according to the configuration of the heating system.
The following settings are possible:
•
Pump mode 00
: The appliance is used only as central heating boiler.
•
Pump mode 01
: A 3-way valve for DHW tank loading is connected in
boiler circuit before low loss header.
•
Pump mode 02
: Do not use this setting!
•
Pump mode 03
: A DHW tank pump is connected on the system side
after the low loss header.
In DHW mode, DHW tank loading pump runs.
In space heating mode, DHW tank loading pump does not run.
Default setting
is
03
.
Service function 2.A: Heating circuit pump lockout time (only
heating boiler ZBR...-3A)
NOTICE
System damage or boiler malfunction!
▶ Never change the setting of this service function on combi boiler
ZWB...-3A appliances.
This setting is only active if Service function 1. F: Pump mode is set to 01
(3-way valve).
During the runtime of an external 3-way valve actuator, the space heating
pump is blocked. Select the run time of the 3-way valve actuator
between
01
-
24
(10 - 240) seconds according to the manufacturer's
documentation.
Default setting
is
24
(240 seconds).
Service function 2.b: Maximum supply temperature
The values of this service function displayed depend on the setting of the
service function
0.E
:
Service function
0.E
is set to
00
(metric units):
• The maximum supply temperature can be adjusted between
35
and
86
(35 - 86 °C).
Service function
0.E
is set to
01
(US customary units):
• The maximum supply temperature can be adjusted between
96
and
187
(96 - 187 °F).
Default setting
is
187
(187 °F (86 °C)).
Service function 2.C: Purging function
When the appliance is switched ON for the first time, it performs a once-
only purging sequence. This involves the heating zone pump switching
on and off at intervals (for approx. 4 minutes).
The display shows
in alternation with the supply temperature.
This service function allows activating the purging function manually,
e.g. after servicing.
The following settings are possible:
•
00
: Purging function off
•
01
: Purging function is switched on and after completion
automatically reset to
00
•
02
: Purging function is permanently on and is not reset to
00
Default setting
is
00
for heating boilers ZBR...-3A appliances,
otherwise
01
.
Service function 2.d: Thermal disinfection (legionella protection)
WARNING
Danger of scalding!
Hot water can scald.
▶ Carry out thermal disinfection only outside the normal hours of use.
▶ Install a tempering valve if running at water temperatures above
104 °F (40 °C).
When this service function is enabled, the DHW is
permanently
heated
to approx. 158 °F (70 °C) if the DHW temperature dial has been turned
clockwise to
max
.