COMPRESSOR REPLACEMENT
QV/WQ SERIES
5
8733829556 (2021/07) Subject to change without prior notice
15)
New compressor installation
a.
Place new compressor in the unit with
encapsulation panels #1 and #2
already attached. NOTE: Maintain a
clearance of 1/8" between
encapsulation and pipes.
b.
Re-install compressor bolts.
16)
Encapsulation re-installation
a.
If removed (at step 11), re-install
encapsulation panels #4 and #5 and
insert screws attaching panels to the
divider.
b.
Screw front encapsulations panels #1
to divider.
c.
Route compressor power plug through
encapsulation panel #3 electrical wires
opening.
Figure 11. Opening for electrical wires
d.
Re-install front encapsulation panel #3.
e.
Re-install suction and discharge pads.
See figure 12
Figure 12. Suction and discharge pads
17)
Install filter drier between TXV and water
coil. See Figure 13.
18)
Re-braze reversing valve assembly pipes.
It is imperative that the refrigerant
system remain clean and dry during
the above operations. A new bi-flow
liquid line dryer must be installed
19)
Re-install and re-wire Electrical Box. Refer
to main unit wiring instructions.
20)
Evacuate the unit and recharge according to
unit nameplate.
If you have any questions regarding the
information provided in this document,
please contact the Bosch Technical Support
Department by phone at 1-800-283-3787,
or via email at