background image

COMPRESSOR REPLACEMENT 

QV/WQ SERIES 

 

 

8733829556 (2021/07)                                       Subject to change without prior notice 

COMPRESSOR REPLACEMENT INSTRUCTIONS  

(Illustrations showing Vertical unit 

configuration. Parts and layout may vary based 

on unit configuration) 

 

Introduction 

This document shows step-by-step instructions 

that will assist in the removal and replacement 

of the compressor for QV and WQ Series. 

 

Warnings 

 

 

Warnings in this document are 

identified by a warning triangle 

printed against a gray background. 

Keywords at the start of the 

warning indicate the type and 

seriousness of the ensuing risk if 

measures to prevent the risk are 

not taken.

 

The following keywords are defined and can be 

used in this document: 

• 

DANGER 

indicates a situation that, if not 

avoided, will result in death or serious injury. 

• 

WARNING

 indicates a situation that, if not 

avoided, could result in death or serious injury. 

• 

CAUTION

 indicates a situation that, if not 

avoided, could result in minor to moderate 

injury. 

 NOTICE

 is used to address practices not 

related to personal injury. 

 

Important Information 

 

This symbol indicates important 

information where there is no risk to 

property or people. 

 

SAFETY WARNINGS

 

 

DANGER: PERSONAL INJURY HAZARD  

Before performing service turn off 

electrical power to unit and 

observe the proper process of 

locking-out power at the 

main/disconnect box and follow all 

safety precautions outlined in unit’s 

IOM before performing any repairs 

to unit. 

 

 

WARNING: PERSONAL INJURY HAZARD 
 

Installation and servicing of this 

equipment can be hazardous due 

to system pressure and electrical 

components. Only trained and 

qualified personnel should install, 

repair, or service the equipment. 

 

 

WARNING: PERSONAL INJURY HAZARD 

When working on equipment, 

always observe precautions 

described in the literature, tags, 

and labels attached to the unit. 

Follow all safety codes. Wear safety 

glasses and work gloves. Use a 

quenching cloth for brazing, and 

place a fire extinguisher close to 

the work area. 

 

 

WARNING: PERSONAL INJURY HAZARD 

R410A is flammable when exposed 

to open flame. Recover all 

refrigerant prior to brazing.

 

 

 

NOTICE: 

All refrigerant discharged 

from this unit must be recovered 

WITHOUT EXCEPTION.

 

Technicians must follow industry 

accepted guidelines and all local, 

state, and federal statutes for the 

recovery and disposal of 

refrigerants. If a compressor is 

removed from this unit, refrigerant 

circuit oil will remain in the 

compressor. To avoid leakage of 

compressor oil, refrigerant lines of 

the compressor must be sealed after 

it is removed. 

 

 

 

 

 

 

 

 

 

Содержание Greensource i QV Series

Страница 1: ...FETY WARNINGS DANGER PERSONAL INJURY HAZARD Before performing service turn off electrical power to unit and observe the proper process of locking out power at the main disconnect box and follow all safety precautions outlined in unit s IOM before performing any repairs to unit WARNING PERSONAL INJURY HAZARD Installation and servicing of this equipment can be hazardous due to system pressure and el...

Страница 2: ...nd apply Lock Out Tag Out a Remove line voltage connections and ensure there is no power supply to the lines 2 Remove front access panel Figure 3 Access panel removal 3 Recover all refrigerant from heat pump utilizing standard refrigerant recovery techniques 4 Removing Electrical Box a Remove screws holding Electrical Box to unit base bottom left and to unit corner post top and bottom side of the ...

Страница 3: ...ation to the divider Qty 4 Figure 5 Divider encapsulation screw locations Vertical unit configuration only 6 Cut pipes shown on figure 6 to remove reversing valve assembly Figure 6 Suggested locations to cut pipes 7 Remove Reversing valve assembly 8 Remove and save to re install later insulation pads around suction and discharge pipes 9 Remove screws holding encapsulation panel 3 See figure 7 Figu...

Страница 4: ...OTE Remove side encapsulation panels 4 and 5 for easier clearance to compressor Figure 9 Compressor bolt locations 12 Unplug power harness from old compressor and un braze Suction and discharge from old compressor 13 Braze suction and discharge to the new compressor and re install compressor power plug As soon as pipes are brazed cover to prevent compressor contamination 14 Re assemble encapsulati...

Страница 5: ...s opening Figure 11 Opening for electrical wires d Re install front encapsulation panel 3 e Re install suction and discharge pads See figure 12 Figure 12 Suction and discharge pads 17 Install filter drier between TXV and water coil See Figure 13 18 Re braze reversing valve assembly pipes It is imperative that the refrigerant system remain clean and dry during the above operations A new bi flow liq...

Страница 6: ...COMPRESSOR REPLACEMENT QV WQ SERIES 6 8733829556 2021 07 Subject to change without prior notice Figure 13 Piping Schematic Filter drier and overall components location ...