background image

 

 

 

 

FPP-RNAC-8A-4C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EN 

Operation and Installation Guide 

Remote NAC Power 
Supply 

 

Содержание FPP-RNAC-8A-4C

Страница 1: ...FPP RNAC 8A 4C EN Operation and Installation Guide Remote NAC Power Supply ...

Страница 2: ... for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL864 certain programming features or options must be limited to specific values or not used at all as indicated below Program Feature or Option Permitted in UL864 Y N Possible Settings Settings Permitted in UL864 Ground Fault Detection disable N Jumper in place enabled Jumper ...

Страница 3: ...ress 20 4 5 NAC Input Variable 20 4 6 AC Fail Time Delay 20 5 0 FPP RNAC 8A 4C Local Status Display 21 6 0 Specifications 23 Figures Figure 1 FPP RNAC 8A 4C Remote NAC Power Supply Board 5 Figure 2 FPP RNAC 8A 4C Enclosure and Board Installation 7 Figure 3 AC Power Connections 9 Figure 4 Install Ferrite Core 9 Figure 5 Battery Connections Inside FPP RNAC 8A 4C Enclosure 10 Figure 6 Battery Connect...

Страница 4: ...NC protocols Wheelock SYNC Protocol Gentex SYNC Protocol System Sensor SYNC Protocol All outputs are synchronized if the conventional inputs are activating the FPP RNAC 8A 4C For option bus synchronization information refer to the control panel documentation 1 3 Power Management The controlling section of the board has un interruptible power If AC line voltage is lost the power supply switches to ...

Страница 5: ...wever needs to be mounted into the enclosure Hardware for mounting the board in the enclosure is supplied in the hardware pack Figure 1 FPP RNAC 8A 4C Remote NAC Power Supply Board T R O U B L E T R O U B L E AC I N P U T 1 I N P U T 2 EOL REF O U T P U T 4 O U T P U T 3 O U T P U T 1 O U T P U T 2 OPTION BUS R Y G B AUX POWER BATTERY REPLACE WITH 15A BLADE TYPE FUSE BOSCH 4998149856 INPUT ACTIVE ...

Страница 6: ...When it is in the retainner tabs the board rests on the two support posts 4 To secure the bottom of the board screw the two bottom corners through the support posts and through to the enclosure 2 2 Enclosure Installation 1 Use the enclosure as a template and mark the top mounting holes on the mounting surface Ensure that enough clearance exists to open the door for maintenance 2 Pre start the moun...

Страница 7: ... P U T 3 O U T P U T 1 O U T P U T 2 OPTION BUS R Y G B AUX POWER BATTERY REPLACE WITH 15A BLADE TYPE FUSE BOSCH 4998149856 INPUT ACTIVE AC OK SYSTEM TROUBLE GROUND FAULT TROUBLE 4 TROUBLE 3 TROUBLE 2 TROUBLE 1 TROUBLE RESET FLASH PROGRAMMING PORT GROUND FAULT OPEN DISABLE CLOSE ENABLE 4 2 1 3 5 5 1 5 7 5 6 6 1 FPP RNAC 8A 4C Printed circuit board 2 Retainer hole in enclosure 3 Support post 4 Moun...

Страница 8: ...e with a resistance per foot less than Line 7 Table 2 Wire Gauge Table based on solid wire AWG B S Gauge Ohms per Foot 12 2 0 mm 0 00162 14 1 6 mm 0 00258 16 1 3 mm 0 00409 18 1 0 mm 0 00651 NFPA 72 requires the use of 18 AWG 1 0 mm or larger diameter wire in fire applications 3 1 AC Power Connections Disconnect all power AC and battery before servicing the FPP RNAC 8A 4C Wait 60 sec before handli...

Страница 9: ...2 9 Figure 3 AC Power Connections Figure 4 Install Ferrite Core L N G 1 2 3 4 5 6 1 AC input select switch 2 AC power terminal 3 Ground 4 Neutral 5 Line 120 VAC or 240 VAC 6 Ferrite core 1 Ferrite core Install the Line and Neutral power connections through the ferrite core as shown in Figure 4 ...

Страница 10: ...es Figure 5 Battery Connections Inside FPP RNAC 8A 4C Enclosure T R O U B L E T R O U B L E AC I N P U T 1 I N P U T 2 EOL REF O U T P U T 4 O U T P U T 3 O U T P U T 1 O U T P U T 2 OPTION BUS R Y G B AUX POWER BATTERY REPLACE WITH 15A BLADE TYPE FUSE BOSCH 4998149856 INPUT ACTIVE AC OK SYSTEM TROUBLE GROUND FAULT TROUBLE 4 TROUBLE 3 TROUBLE 2 TROUBLE 1 TROUBLE RESET FLASH PROGRAMMING PORT GROUND...

Страница 11: ... B O SC H 4998149856 I N P U T A C T I V E A C O K S Y S T E MT R O U B L E G R O U N D F A U L T T R O U B L E 4 T R O U B L E 3 T R O U B L E 2 T R O U B L E 1 T R O U B L E R E S E T F L A S H P R O G R A M MI N G P O R T G R O U N D F A U L T O P E N D I S A B L E C L O S E E N A B L E 1 3 4 5 2 7 6 1 BATB 40 Battery Case 2 Conduit 20 ft 6 1 m maximum 3 Black wire 4 Red wire 5 To field 6 Power...

Страница 12: ... Each Device Quantity x Alarm Current for Each Device FPP RNAC 8A 4C Remote NAC Power Supply 1 150 mA 150 mA 150 mA 150 mA Grand Total Standby Current Grand Total Alarm Current Table 4 Calculating the Required Battery Size Descriptions Calculations Grand Total Standby Current in amps A CS Total Hours of Standby Required usually 24 or 60 HS Total Standby Capacity multiply CS x HS TS CS x HS Grand T...

Страница 13: ... 6 1 1 1 7 2 2 2 0 to 3 0 A 0 3 0 6 0 8 1 7 2 5 3 3 3 0 to 4 0 A 0 4 0 7 1 1 2 2 3 3 4 4 4 0 to 5 0 A 0 5 0 9 1 4 2 8 4 1 5 5 5 0 to 6 0 A 0 6 1 1 1 7 3 3 5 0 6 6 6 0 to 7 0 A 0 6 1 3 1 9 3 9 5 8 7 7 7 0 to 8 0 A 0 7 1 5 2 2 4 4 6 6 8 8 For capacities greater than 18 Ah the batteries require a BATB 40 Battery Case Connections between the batteries in the Battery Case and the control panel must be ...

Страница 14: ...72 Class A or B used instead of the option bus connection Refer to the control panel s compatibility information Polarity reversal on Input 1 activates NAC Outputs 1 and 2 Input 2 activates NAC Outputs 3 and 4 DIP switch settings allow NAC Input 1 to control all four outputs refer to Section 4 0 DIP Switch and Option Bus Settings on page 17 If the control panel detects a trouble condition on eithe...

Страница 15: ...ons The auxiliary output provides a continuous unsupervised 24 V output to power external devices It is rated at 0 75 A and can be wired in series with the trouble relay to provide power to the associated appliance A short circuit on this output causes a trouble condition but does not affect the operation of the FPP RNAC 8A 4C in any way Refer to Figure 10 for wiring details Figure 10 Wiring the A...

Страница 16: ...d before installation is completed Use DIP Switch S1 positions 3 4 5 and 6 refer to Figure 12 to make the output always active When the output is configured as always active the output is unsupervised and no EOL is needed 3 7 3 EOL Reference Programming Add a resistor that matches the value of the EOL used in the notification appliance circuit This must be in the range of 1 kΩ to 20 kΩ If no resis...

Страница 17: ...he commands from the option bus and pattern settings are ignored for any output configured in the power supply mode Table 7 DIP Switch S1 Settings Bell Pattern and Protocol Output Options Output Mode Options Position Name SYNC 2 SYNC 1 SYNC 0 NAC 4 POWER 4 NAC 3 POWER 3 NAC 2 POWER 2 NAC 1 POWER 1 Position Number 0 1 2 3 4 5 6 Notes Steady Follower1 OFF OFF OFF OFF NAC ON PWR OFF NAC ON PWR OFF NA...

Страница 18: ...ts 1 and 2 NAC Input 2 controls NAC Outputs 3 and 4 OFF NAC Input 1 controls all four NAC Outputs ON AC Failure Delay Reporting Options No delay in AC failure reporting the unit signals an AC Failure immediately OFF OFF AC failure reporting delay 1 hour OFF ON AC failure reporting delay 3 hours ON OFF AC failure reporting delay 6 hours ON ON Option Bus Settings Disabled OFF OFF OFF OFF Address 1 O...

Страница 19: ...ut 2 Output Response OFF OFF Outputs are off OFF ON NAC outputs 1 and 2 are off NAC outputs 3 4 follow the protocol selected on the DIP switch ON OFF NAC outputs 1 and 2 follow the protocol selected on the DIP switch NAC outputs 3 and 4 are off ON ON NAC outputs 1 2 3 and 4 follow the protocol selected on the DIP switch When Switch S2 Position 0 ON and Protocol is Pulsed March Time Temporal NAC In...

Страница 20: ... Instead of having Input 1 drive NAC Output 1 and 2 and Input 2 drive NAC Output 3 and 4 Input 1 can be set to drive all four outputs Set Switch S1 to the ON position to select this option 4 6 AC Fail Time Delay A trouble condition is registered to the control panel but is not indicated with an LED if the AC falls below 85 105V for more than 5 sec A programmable time delay allows the indication of...

Страница 21: ...ming process completes successfully The green LED lights to indicate that the user can now read the value A series of blinks indicates the primary revision number followed by the secondary revision number The green LED turns off to indicate the end of the sequence The display continues until the Flash module is removed from the programming port For example revision number 2 04 has two blinks follo...

Страница 22: ...urrents measured at each NAC output together with the Auxiliary Power Port output 7 Power supply output voltage is low STEADY The SYS TRBL LED and the Trouble Relay are active when the Flash Programming module is connected 4 GROUND FAULT Yellow Ground Fault Indicates that the NAC output wiring is not connected properly to an external source or ground The Trouble Relay is deactivated 5 TRBL1 Yellow...

Страница 23: ...urrent 8 A Load Regulation 400 mV Line Regulation 200 mV Ripple Voltage 250 mV pp Standby Current Draw 150 mA use for current calculation 1 5 kΩ Ground Fault NAC Input compatible with NFPA 72 Class A or B NAC Non polarized Input Voltage 12 24 VDC VAC RMS Input to Output Response Time 10 ms Current Draw 15 mA maximum Option Bus Input Voltage 12 V nominal NAC Outputs x4 NFPA 72 Class B Style Y NAC o...

Страница 24: ...tput Contact Type Form C Contact Rating 1 5 A 30 VDC resistive load Power Output Circuit when Notification Appliance Circuit NAC is Configured as a Power Output Circuit Output Voltage 24 VDC Nominal Range for Compatibility 19 6 to 27 5 VDC Output Current 1 3 A maximum Ripple Voltage 250 mVpp Maximum current of 8 A is shared among all notification appliance circuits NAC power output circuits and au...

Страница 25: ...FPP RNAC 8A 4C Operation and Installation Guide 6 0 Specifications Bosch Security Systems Inc 8 09 F01U025431 02 25 ...

Страница 26: ... 2009 Bosch Security Systems Inc F01U025431 02 Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 800 289 0096 ...

Отзывы: