14
en | Operating
Remote Command Center
F.01U.078.098 | 3.0 | 2011.11
Installation and Operation Guide
Bosch Security Systems, Inc.
9.2
Lamp Test
A lamp test is accomplished by pressing and holding the acknowledge [ACK] key for more
than 3 seconds. All LEDs on the FMR-1000-RA are turned on and the LCD display is filled with
black blocks when the lamp test starts. As soon as the acknowledge [ACK] key is released, the
revision number, Option Bus address, and key lock status appear on LCD display for
3 seconds. Then the LEDs and the LCD display return to normal working mode (controlled by
the panel).
9.3
Keypad Operations
With the key lock in the locked position, the user can use the scroll keys only for navigating
the LCD display and operate the acknowledge [ACK] key. Upon an invalid key press, the
display shows “KEY LOCKED” for 3 seconds. Refer to
Table 7.1
on
Page 11
for key lock bypass
option.
With either the key lock in unlocked position or the DIP switch setting for the key lock
bypassed, the user may operate any of the device’s keys.
View Status
With no alarms or troubles in the system, the display message is "SYSTEM NORMAL" or
"SYSTEM NORMAL DAY" along with the current date and time.
During initialization by start-up or re-configuration, the screen indicates "System Initializing”.
The panel shows the “System Resetting” screen upon reset, until the system returns to the
normal supervising condition.
If PAS or Pre-signal is turned on, the screen indicates “SYSTEM NORMAL DAY”.
Any off-normal conditions are shown in groups classified as fire alarm, gas alarm, supervisory
and trouble.
Use the arrow keys to view events or conditions in the same group. Up and down keys move
the user to the previous or next event. The left and right keys switch to other groups.
Acknowledge
During an alarm, pressing the acknowledge [ACK] key turns off the piezo that is sounding on
an annunciator. All the ongoing events or conditions are marked as “Acknowledged”. The
24-hour trouble reminder timer starts. Any trouble event not cleared within 24 hours is sent
again and the piezo begins to beep again.
If a fire input point configured as "PAS enabled" (with global PAS enabled) is activated,
pressing the acknowledge [ACK] key within 15 seconds after a PAS activation starts the
investigation timer. This allows the user to investigate the fire alarm or take other appropriate
actions until the timer expires.
An acknowledgement operation can also be initiated by the activation of an input point
configured as an acknowledge type.
Silence
Pressing the silence key performs all functions of the acknowledge operation.
When the silence operation is initiated, the panel goes into a “Silenced” status and the
“Silenced" LED lights. The piezos on all keypads and annunciators turn off. All outputs are
silenced if configured as “Silenceable”. NACs play the “Silenced” pulse for the programmed
NOTICE!
For system display information, refer to
FPA-1000 Installation and Operation Guide
(P/N F.01U.173.607).