 the HPC switch is open upon a Y call the 

UPM  will  not  energize  the  CC  output  and 
therefore the compressor will remain off, the 
fault LED will flash one (1) time for the HPC 
and the alarm contact will remain off. 
 
If the compressor is running in normal mode 
on  a  Y  call  and  the  high  pressure  switch 
opens,  the  UPM  will  shut  down  the 
compressor  output  and  will  keep  it  off  until 
the  switch  closes  and  the  anti  short  cycle 
has expired. The controller will keep track of 
the  number  of  times  the  switch  opens,  if 
within one (1) hour period the switch opens 
the number of times set  via the DIP switch 
the controller will shut the compressor down 
and perform a hard lockout condition under 
this  condition  the  alarm  contact  will  be 
energized. 
 
The  UPM  allows  the  user  to  configure  the 
counts that the HPC will be allowed to open 
within one hour before the UPM performs a 
hard  lockout  on  the  compressor.  The  user 
can  select  either  two  or  four  times  by 
changing  switch  four  (4)  on  the  DIP  switch 
SW1 (shown on table 3) on the UPM board. 

 

Low pressure protection 
 

If the LPC switch is open upon a Y call the 
UPM  will  not  energize  the  CC  output  and 
therefore the compressor will remain off, the 
fault LED will flash two (2) times for the LPC 
and the alarm contact will remain off. 
 
If the compressor is running in normal mode 
on  a  Y  call  and  the  low  pressure  switch 
opens,  the  UPM  will  keep  the  compressor 
running  for  two  (2)  minutes  if  the  condition 
remains  after  this  period  of  time  the 
compressor will shut down and the UPM will 
start a soft lockout. The UPM will flash two 
(2) times for the LPC. And the alarm contact 
will remain off.  
If  the  switch  closes,  the  UPM  will  start  the 
compressor  after  the  anti  short  cycle  has 
expired  UPM  will  energize  the  compressor 
output. 
 
 
 

 

 

 

 

High pressure protection 

 
If

IMPORTANT: 
To exit the hard lockout the controller must 
be reset from the Y or R terminal by 
removing the power from the selected 
terminal. The user can choose which will be 
the reset point via the DIP switch SW1.

 

Содержание FHP UPM I

Страница 1: ...I O ZONE 560 583 UPM I INSTALLATION AND OPERATION MANUAL 1 ...

Страница 2: ...o verify correct part number TABLE OF CONTENTS Specifications 3 Unit Protection Module UPM 4 Power Random Start Up 5 Anti short cycle delay 5 Y Call 5 High and Low pressure protection 5 Ground 7 DIP Switch Settings 7 Selectable Alarm Mode 7 Freeze protection 8 Brownout protection 8 Condensation overflow 8 UPM Sequence of Operation SOO Flow Chart 9 2 ...

Страница 3: ... purposes dry contact Normally Open NO Inputs Four 4 inputs Dedicated inputs for High Pressure Switch HPC Low Pressure Switch LPC Freeze Sensor FREEZE 10 K 77F Thermistor Condensate Overflow Sensor CON 230 K 15 Compressor Call Y Signal Status Indication Visual LED status of power and alarms status indication Protection Surge and transient protection circuitry Weight 0 14 lbs 0 07 Kg Overall Dimens...

Страница 4: ...ches and sensors this device provides time delays and protects the unit against freezing of the water and refrigerant heat exchangers as well as condensate overflow when the appropriate sensors are installed Figure 1 UPM Single Stage Alarm output is Normally Open NO dry contact If 24 VAC output is needed R must be wired to the ALR COM terminal 24VAC will be available on the ALR OUT terminal when t...

Страница 5: ...en completely powered down for mor m typically the unit will star between the time range of 0 and 00 seconds his only if the controller is set to normal operation test switch set to NO In order for the random sequence to initiate the unit power mus Anti short This cycling if the Y call is set and removed Y Call The UPM will energize the compressor s utput CC in an event of a Y c o th s energize Hi...

Страница 6: ... The user can select either two or four times by changing switch four 4 on the DIP switch SW1 shown on table 3 on the UPM board Low pressure protection If the LPC switch is open upon a Y call the UPM will not energize the CC output and therefore the compressor will remain off the fault LED will flash two 2 times for the LPC and the alarm contact will remain off If the compressor is running in norm...

Страница 7: ...de Normal or Test operation The settings shown below are factory default for most heat pump applications however the Unit wiring diagram is the ultimate guide for factory D The following table is availab board as well and it depicts the switch position and its associated functionality Selectable Alarm Mode The UPM controller can be configured to have either a co If constant CONT is selected the UP...

Страница 8: ...will enter e co not monitor the power pply du first 500 illisecon f mpress p to av e a the UPM detects a brownout condition ive 5 times as error code indication ondensation overflow tors e drain pan for high condensate water impedance drops below 230KΩ 5 ONLY when condensate sensor the correspondent code via its status LED 4 flashes To exit the hard lockout water has to return to its normal level ...

Страница 9: ...UPM Sequence of Operation SOO Flow Chart 9 ...

Страница 10: ...10 10 th 601 N W 65 Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www fhp mfg com 6 720 220 321 REV 6 11 ...

Отзывы: