Conventional aspiration smoke detector
Configuration | en
17
Bosch Sicherheitssysteme GmbH
Quick installation guide
2020.04 | 2.0 | F.01U.123.590
Notice!
The alarm delay time should be set to 0 seconds for test purposes only.
Activation threshold of the airflow monitoring
The activation threshold for an airflow problem can be changed for the detection module via
the FAS-ASD-DIAG.
Activation
threshold
Activation threshold
(default)
Setting intervals
Detection module
10% - 50%
20%
1%
Select the activation threshold in line with Planning.
Delay time of the airflow malfunction
If you wish to change the delay time for transmitting the signal for an airflow malfunction, this
is possible via the FAS-ASD-DIAG.
Fault delay
Fault delay (default)
Setting intervals
Detection module
1 s – 60 min
100 s
1 s
The default delay time is set to 100 seconds. In areas with time-limited disturbance variables
(e.g. air pressure fluctuations), other delay times should be set based on the duration of the
disturbance variables.
Pre-alarm threshold
If you wish to change the pre-alarm threshold, this is possible via the FAS-ASD-DIAG.
Pre-alarm threshold (default)
Detection module
60%
Fault indication
The collective fault display (airflow and detection module malfunction) can be set to log or not
to log (default) trouble messages. Activation or deactivation is possible via the diagnostic
software.
Log trouble
Do not save trouble messages
(default)
Detection module
off - on
off
Dynamic airflow
Activation or deactivation of dynamic airflow is possible via the diagnostic software.
Dynamic airflow
Dynamic airflow (default)
Detection module
off - on
off
ROOM-IDENT
Activation or deactivation of fire source identification is possible via the diagnostic software.
ROOM-IDENT
ROOM-IDENT (default)
Detection module
off - on
off