Technical Data
5.1
Detector and Trim Ring
Detector type
FCP-OC
500/FCP-OC
500-P
FCP-O
500/FCP-O
500-P
Detection principle
Combination of scattered light
and combustion gas
measurement
Scattered light measurement
Special features
–
Contamination detection
–
Drift compensation in
optical and in gas
measuring unit
–
Contamination detection
–
Drift compensation in
optical unit
Individual display
Two‑color LED: red/green
Operating voltage
8.5 to 30
V
DC
Current consumption
–
Standby
with FCA-500-EU: 3
mA
with FCA-500-E-EU: 24
mA
–
Alarm
47
mA
–
Malfunction
with FCA-500-EU: 52
mA
with FCA-500-E-EU: 58
mA
Response sensitivity:
–
O
unit
< 0.36
dB/m (EN
54-7)
< 0.18
dB/m (EN
54-7)
–
Gas
unit
in ppm-range
-
Max. monitoring area
120
m
2
(note local guidelines)
Maximum installation
height
16
m (note local guidelines)
Minimum installation
height
Out of arm’s reach
Minimum distance to
lamps
50
cm
Permitted air speed
20
m/s
Permitted operating
temperature
-10
°C to +50
°C
-20
°C to +65
°C
Permitted relative
humidity
<95
% (non‑condensing)
Protection class as per
IEC
60529
IP
33
IP
53
Dimensions:
–
Detector without trim
ring
Ø
113
mm x
55 mm (without base)/Ø
113
x
70
mm (with base)