![Bosch FCP-O 500 Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/bosch/fcp-o-500/fcp-o-500_operation-manual_50189021.webp)
Conventional Automatic Detectors
Maintenance and Service | en
21
Bosch Sicherheitssysteme GmbH
Operation Guide
2019.11 | 5.0 | F.01U.003.962
4
Maintenance and Service
For maintenance and inspection work on security systems, the regulations laid down in
DIN
VDE
0833 strictly apply in Germany; these refer to the maintenance intervals specified by
the manufacturer.
Notice!
The 500 Series Detectors do not require to be removed from their bases for routine
maintenance.
If occasionally a detector requires replacement due to a design change or damage to the
device then this should be carried out by a qualified engineer.
This should only be undertaken when the system is offline and the user has made alternative
arrangements for emergency evacuation.
–
Maintenance and inspection work should be carried out regularly and by trained technical
personnel.
–
Bosch Sicherheitssysteme GmbH recommends a functional and visual inspection at least
once a year.
Test steps
Detector type
O
OC
Check of the LED display
X
X
Visual check of the mounting
X
X
Visual inspection for damage and contamination of the detector
surface
X
X
Check monitoring area for limitations of function and interference
caused by lamps
X
X
Test of the optical sensors (refer to
X
-
Combined test with detector test device and CO testing gas (refer to
Inspection Procedure for FCP‑OC
)
-
X
Notice!
Multisensor detectors with C
sensors must be exchanged every 4 - 6 years.
FCP-OC
500
Due to the life expectancy of the gas sensor, the FCP‑OC
500 detector switches off the
C
sensors after approx. 4
‑
6 years of operation. The detector will continue to function as an
O
detector.
The detector should then be exchanged immediately in order to be able to keep using the
higher reliability of detection of the OC detector.
Notice!
The cleaning intervals depend on the environmental conditions.
Содержание FCP-O 500
Страница 1: ...Conventional Automatic Detectors FCP O 500 FCP OC 500 FCP O 500 P FCP OC 500 P en Operation Guide ...
Страница 2: ......
Страница 33: ......