8
en | Technical Specifications
Automatic Fire Detector
2019.11 | 5.0 | F.01U.002.684
Installation manual
Bosch Sicherheitssysteme GmbH
Maximum installation
height
16
m (heed local guidelines)
Minimum distance to
lamps
50
cm
Permissible operating
temperature
FCP‑O
500(-P): -20
°C to +65
°C
FCP‑OC
500(-P): -10
°C to +50
°C
Permissible rel. humidity <95
% (non-condensing)
Permissible air speed
20
m/s
Protection class as per
IEC
60529
FCP‑O 500(-P): IP
53
FCP‑OC 500(-P): IP
33
Weight
FCP‑O 500(-P): 170
g
FCP‑OC 500(-P): 180
g