FAS-420-TM | FAS-420-TM-R | FAS-420-TM-RVB
en
31
Bosch Sicherheitssysteme GmbH
F.01U.088.879 | 3.0 | 2009.07
Technical Specifications
LSN power supply
15 V DC-33 V DC
Auxiliary power supply
15 V DC-30 V DC
LSN current consumption
3.25 mA
Current consumption from auxiliary power
supply
Fan voltage
9 V
10.5 V
12 V
-
Starting current
150 mA
-
In standby
105 mA
125 mA
145 mA
-
With alarm, device variants FAS-420-TM and
FAS-420-TM-R
110 mA
130 mA
150 mA
-
With alarm, device variant FAS-420-TM-RVB
140 mA
160 mA
180 mA
Max. wire gauge
2.5 mm²
Housing material
Plastic (ABS)
Housing color
Papyrus white (RAL 9018)
Protection category according to EN 60529
-
Without air return
IP 20
-
With pipe section 100 mm/pipe bend
IP 42
-
With air return
IP 54
Permissible temperature range
-
FAS-420-TM Series Aspirating Smoke
Detectors
-20 °C to +60 °C
-
PVC pipe system
-10 °C to +60 °C
-
ABS pipe system
-40 °C to +80 °C
Permissible relative humidity (non-condensing)
Max. 95%
Sound power level (at 9 V fan voltage)
40 dB(A)
Response sensitivity (light obscuration)
0.5 to 2.0%/m
Life cycle of fan (at 12 V and 24 °C)
60,000 hrs