8
en | Installation
Automatic detector
2019.11 | 5 | F.01U.002.682
Installation manual
Bosch Sicherheitssysteme GmbH
1
Installation
Notes
–
Carefully cut open the packaging of the detectors with C sensor.
–
Do not remove the protective film from the detector head until installation is finished.
Inserting color rings (P-Variants)
See chapter Graphics.
1.
The detector front plate
(1)
is secured with a small snap-fit hook
(2)
on the three‑way
guideway. To remove, insert the enclosed opening tool
(3)
in the slot
(4)
above the snap
−fit hook, secure it with your thumb, turn the front plate counterclockwise and lift.
2.
From the selected color, place the color rings
(5)
on the front plate
(1)
and put on the
detector. Only one position of the front plate is possible.
3.
Turn the cover clockwise to lock it into place. Ensure the sensor windows lie free.
4.
Insert the selected color ring in the trim ring
(6)
.
Mounting the detector and trim ring
See chapter Graphics.
Use of the FAA‑500‑RTL exchanger device is recommended for removing and inserting the
detectors.
1.
Snap the trim ring into place on the base
(7)
.
2.
Remove the protective film from the detector head.
On startup, a protective film left on the detector by mistake is recognized by the system.
The message O‑malfunction will occur.
3.
Press the detector one time gently upwards into the base. The push/push system holds
the detector.
Due to the guideways, the detector can only be placed in the base in the correct position.
For high mounting heights: The clearly visible two contact plates
(8)
in the base are on
the same side as the single guideway
(9)
.
Dismantling the detector and trim ring
1.
Press the detector one time gently upwards into the base. The push/push system
releases the detector.
2.
Lift the trim ring by the edge to remove it from the base.
Address setting
See chapter Graphics.
Fit a rotary switch in the required position using a pan head slotted screwdriver.
Address (A)
Operating mode
0 0 0
Loop/stub in LSN improved version mode with automatic addressing
0 0 1 - 2 5 4
Loop/stub/T-taps in LSN improved version mode with manual
addressing
CL 0 0
Loop/stub in LSN classic mode
2 5 5 - 2 9 9
Non-permitted address range (error message on fire panel)
2
Technical Specifications
Input voltage
15 to 33
V
DC
Current consumption
3.25
mA