Programming
Programming occurs via a PC or laptop connected to the fire panel
–
With FSP‑5000‑RPS (Remote Programming System) for panels with LSN improved version
line technology
–
With WinPara version 4.85 for panels with conventional LSN line technology.
420 series detectors are programmed by entering the area of operation. The selection of the
area of operation determines the optimum characteristic field for fire and disturbance variable
evaluation.
When optical sensor sensitivity in the FAP‑OTC 420 and FAP‑DOTC420 is low, the detector
only triggers if both smoke and an increase in CO concentration or temperature is detected.
The operating mode can be changed for the FAP‑OTC 420 and FAP‑OT 420 detector models,
as well as the FAP‑DOTC420 and FAP‑DOT420 models, i.e. individual sensors can be switched
off:
–
Switch to optical (O sensor sensitivity = low, T sensor = switched off)
–
Switch to thermal differential (T sensor sensitivity = A2R, O sensor = switched off)
–
Switch to thermal maximum (T sensor sensitivity = A2S, O sensor = switched off).
In the case of the purely optical FAP‑O 420 and FAP‑DO420 detectors, the sensitivity of the
optical sensor can be set to three levels. Depending on the operating location, the optical
sensor in the detector is thus adjusted to the environmental conditions.
i
Notice!
For fire detection, the purely optical detector also evaluates the time behavior of the fire char-
acteristics, which differs significantly from the time behavior of disturbance variables and that
occurring during a detector test
As a result, there are also different trigger times when testing with a test aerosol outside of
Walk test operation (10 s to max 60 s), depending on the selected sensitivity adjustment.
The FAH-T 420 Heat Detector is programmed by taking into account the ambient temperature,
the installation height and the sensitivity class selection.
Programming of the optical, thermal, and chemical sensors and the linking of all sensors via
algorithms significantly increases the detection ability and security against false alarms.
FAP‑DOTC420 / FAP-OTC 420
i
Notice!
The default setting of the FAP-DOTC 420 and FAP-OTC 420 detector types in RPS and Win-
Para is "Office (smoker) / Waiting Room / Restaurant /Meeting Room". For a description of
this setting, see the below table.
Selectable installation locations in
the programming software (WinPara
and FSP‑5000‑RPS)
Detector Type
Sensitivity
Thermom
ax (T
max
)
Optical
(O)
Chemical
(C)
Office (after hours)
O, T
max
, T
diff
, C
High (A2)
High
High
Office (smoker)/waiting room/
restaurant/meeting room
= default setting
O, T
max
, T
diff
, C
High (A2) Low*
Low
Office (day mode)
O, T
max
, T
diff
, C
Low (B)
Medium
High
4
4.1
Automatic Fire Detectors LSN
improved
Programming | en
11
Bosch Sicherheitssysteme GmbH
Operation Guide
12/2012 | 8.1 | F.01U.003.448