Functional Description
The short-circuit isolator isolates alarm zones in which a short circuit or an interruption due to wire
break or detector removal has occurred. This means the functionality of the remainder of the network
remains preserved.
Wiring
Pos.
Description
Connection
1
b1+
2
a-
LSN
3
b2+
4
N/A
freel terminals, e.g. for looping
5
N/A
freel terminals, e.g. for looping
through ext. auxiliary voltage and for
hi ldi
6
N/A
g
y
g
shielding
Adress
Setting
Mode/
X
XX
X
X
X
XX
X
CL 0 0
0 0 0
1...254
FPA-
5000
BZ 500 LSN
UEZ 2000 LSN
UGM 2020
255...299
_
_
_
D
D
D
D
B
Technical Specification
Address setting 0 0 0
Loop/stub in LSN improved mode with automatic addressing
(T-tap system not possible)
Address setting 1...254
Loop/stub/T-tap system in LSN improved mode with manual ad-
dressing
Address setting CL 0 0
Loop/stub in „classic“ LSN mode
Input voltage (min - max)
15 V DC - 33 V DC
Maximum current consumption
- during initialization
- following the initialization
(from LSN)
< 0,4 mA
< 0,25 mA
Safety class as per IEC 60950
III
Protection class as per IEC 60529
IP 54
Permitted operating temperature
-20 °C . . . 50 °C
Permitted storage temperature
-25 °C . . . 85 °C
Permitted relative humidity
< 96%
Housing material and color
PPO (Noryl), signal white (RAL 9003)
Material interface module housing
Material surface-mount housing
PPO (Noryl)
ABS + PC-Blend
5 6
3 4
1 2
INFO
It is not permitted to use
different adressing modes together.
Содержание F.01U.508.711
Страница 3: ...FLM I 420 S Bosch Sicherheitssysteme GmbH F 01U 003 287 A3 2008 03 3 36 1 2 ...
Страница 6: ...FLM I 420 S Bosch Sicherheitssysteme GmbH F 01U 003 287 A3 2008 03 6 36 6 7 1 2 8 ...
Страница 8: ...FLM I 420 S Bosch Sicherheitssysteme GmbH F 01U 003 287 A3 2008 03 8 36 4 3 2 1 3 2 1 ...
Страница 35: ...FLM I 420 S Bosch Sicherheitssysteme GmbH F 01U 003 287 A3 2008 03 35 36 ...