14 | Maintenance/inspection

8.3

Safety Thermostat

The DHW cylinder is equipped with an automatic safety device. 
This safety device isolates the DHW cylinder from the power 
supply to prevent the risk of injury if the DHW cylinder water 
temperature rises above a certain limit.

Fig. 17

Reset button

[1] Screw
[2] Reset button

8.4

After maintenance

▶ Retighten all water connections and check for tightness.
▶ Connect the DHW cylinder.

DANGER: 

Only authorised contractors are 

permitted to troubleshoot the temperature 
limiter.
The high limit safety cut-out must be reset 
manually, but only once the cause of the fault 
has been eliminated. To troubleshoot the high 
limit safety cut-out:

▶ Remove the screws in the cylinder cover, 

and remove the cover [1].

▶ Push down the reset key [2].

6720812247-05.2V

2

1

Содержание ES 035 5 Series

Страница 1: ...Installation and operating instructions DHW cylinder Tronic 4000 T Tronic 6000 T 6720818520 00 1V ES 035 050 080 100 120 150 5 6 720 818 731 2016 07 EN ...

Страница 2: ...on 7 5 2 Selecting the installation location 8 5 3 Wall mounting bracket 8 5 4 Water connection 9 5 5 Electrical connection 10 5 6 Commissioning 10 6 Operating the appliance 10 6 1 Turn the appliance on off 10 6 2 Adjust the domestic hot water temperature 11 6 3 Draining the DHW cylinder 11 7 Environmental protection Recycling 12 8 Maintenance inspection 12 8 1 User information 12 8 1 1 Cleaning 1...

Страница 3: ...lity during installation and service work Use only original spare parts If the power cable is damaged it may only be replaced by the manufacturer themanufacturer scustomer service or individuals who are comparably qualified in order to prevent danger Handover to the user When handing over the heating system instruct the user in its operation and operating conditions Explain the operation with part...

Страница 4: ...rmometers W Wall mounted installation V Vertical installation R Reversible installation B Connections to the bottom side 2 3 Description of the DHW cylinder Enamel coated steel storage cylinder according to European standards High pressure stability Outer wall jacket Sheet metal and or plastic Easy operation CFC free PU insulation Magnesium anode 2 4 Corrosion protection The internal wall of the D...

Страница 5: ... 8 7 8 7 Power cable with plug type HO5VV F 3 x 1 5 mm2 or HO5VV F 3 x 1 0 mm2 Protection class I IP Rating IP24 DHW temperature Temperature range C up to 70 C Table 4 Technical data Tronic 6000 T Technical data Units ES 035 ES 050 ES 080 ES 100 ES 120 ES 150 General Information Capacity l 34 47 76 95 115 142 Dry weight kg 15 7 19 2 22 5 25 8 29 3 35 Weight when full kg 49 7 66 2 98 5 120 8 144 3 ...

Страница 6: ...n mm vertical installation Fig 3 Dimensions in mm horizontal installation A 185 ØG1 2 27 5 C Ø470 486 100 B 6720818520 01 1V min 220 max 300 D 250 500 6720818520 02 1V Device A B C D ES035 485 300 405 ES050 585 400 505 180 ES080 810 625 730 407 ES100 960 775 880 552 ES120 1110 925 1030 702 ES150 1329 1144 1250 927 Table 6 ...

Страница 7: ...ee location If applicable observe Directive EU 2012 19 EC for disposal of electrical and electronic old appliances 5 Installation 5 1 Important information 1 6720818520 07 2V 2 8 4 5 7 3 6 A1 L A2 L B1 N B2 N T2 R1 6720818585 01 1V A1 L A2 L B1 N B2 N T2 R1 6720818585 02 1V R2 Installation electrical connection and commissioning may only be carried out by a contractor approved for such work by the...

Страница 8: ...ll the DHW cylinder outside of the protection zones and maintain a clearance of 60 cm to the bathtub Fig 7 Protection zones 5 3 Wall mounting bracket Vertical installation Fig 8 Vertical installation Horizontal installation only Tronic 6000 T Fig 9 Horizontal installation CAUTION Select a wall for mounting the cylinder that has sufficient load bearing capacity to support the full DHW cylinder Page...

Страница 9: ... ES100 552 ES120 702 ES150 927 Table 7 NOTICE Corrosion damage to the DHW cylinder s connections Provide the water connections with insulating dielectric unions This prevents current DC current from flowing between the metal hydraulic connections and the resulting corrosion NOTICE Material damage Useafilteratthewaterinletifthewaterhas suspended matter Recommendation Flush the system beforehand as ...

Страница 10: ... Switching off Isolate the storage tank from the power supply NOTICE NEVER CLOSE OFF THE PRESSURE RELIEF VALVE DRAIN Neverinstallaccessoriesbetweenthe pressure relief valve and the cold water connection on the right of the electrical DHW cylinder If the water pressure is 80 above the maximum pressure of the DHW cylinder 6 4 bar install a pressure reducing valve Fig 11 If the water pressure in the ...

Страница 11: ... a hot water tap Open pressure relief valve Fig 15 Wait until the DHW cylinder has drained fully Fig 15 Manually opening the pressure relief valve The DHW cylinder stops heating once the water reaches the required temperature and the ON indicator goes dark Fig 12 1 The DHW cylinder starts heating again once the water temperature falls below the required temperature ON indicator shines until the se...

Страница 12: ... dispose of old electrical or electronic devices you should use the return and collection systems put in place in the country concerned 8 Maintenance inspection 8 1 User information 8 1 1 Cleaning Do not use abrasive caustic or solvent containing cleansers Ifrequired cleanthe casing of the DHWcylinderwithasoft cloth 8 1 2 Checking the pressure relief valve Check whether water leaks from the pressu...

Страница 13: ...er Let all of the hot water drain for at least 3 minutes from the DHW cylinder Closethehotwatertaps andsetthetemperaturelimiterto the normal operating temperature 8 2 4 Extended nonuse longer than 3 months Isolate the DHW cylinder from the power supply Completely drain the DHW cylinder Fill the DHW cylinder until water drains from all of the hot water taps Connect the DHW cylinder to the power sup...

Страница 14: ... limit Fig 17 Reset button 1 Screw 2 Reset button 8 4 After maintenance Retighten all water connections and check for tightness Connect the DHW cylinder DANGER Only authorised contractors are permitted to troubleshoot the temperature limiter The high limit safety cut out must be reset manually but only once the cause of the fault has been eliminated To troubleshoot the high limit safety cut out Re...

Страница 15: ...set by the temperature regulator Adjust the temperature regulator X High limit safety cut out triggered Replacethetemperaturelimiterorinstall a new one X Defective heating element Exchange the heating element X Incorrect operation of the temperature limiter Replacethetemperaturelimiterorinstall a new one X X X Scale on the DHW cylinder and or the safety group Remove scale If necessary replace the ...

Страница 16: ...Bosch Thermotechnik GmbH Junkersstrasse 20 24 D 73249 Wernau www bosch thermotechnology com ...

Отзывы: