2.1
Important notices on usage
The module communicates via an EMS plus interface with other
EMS-plus-enabled BUS nodes.
•
The module must only be connected to programming units
with the EMS plus (Energy Management System) BUS
interface.
•
The functional scope depends on the programming unit
installed. Detailed information about programming units
can be found in the technical guides and on the
manufacturer's website.
•
The installation space must be suitable for the IP rating
stated in the module specification.
2.2
Standard delivery
[1]
Module
[2]
Jumper for connection to MC1 if there is no temperature
limiter in the assigned heating circuit (without mixing
valve)
[3]
Bag with strain relief
[4]
Installation set flow temperature sensor
[5]
Installation instructions
2.3
Specification
Design and operation of this product conform to
European Directives and the supplementary
national requirements. Its conformity is
demonstrated by the CE marking .
WARNING:
Risk of scalding!
▶ If DHW temperatures above 60 °C are set
or thermal disinfection is switched on, a
mixing valve must be installed at the DHW
outlet or at the DHW draw off points.
NOTICE:
Floor damage!
▶ Underfloor heating systems must only be
operated with an additional temperature
limiter.
Specification
Dimensions
(W × H × D) 151 × 184 × 61 mm (further
dimensions
Maximum conductor
cross-section
•
230 V terminal
•
Extra-low voltage
terminal
•
2.5 mm
2
•
1.5 mm
2
Rated voltages
•
BUS
•
Module power supply
•
Programming unit
•
Pump and mixing
valve
•
15 V DC (reverse-polarity-
protected)
•
230 V AC, 50 Hz
•
15 V DC (reverse-polarity-
protected)
•
230 V AC, 50 Hz
Fuse rating
230 V, 5 AT
BUS interface
EMS plus
Power consumption on
– standby
< 1 W
Maximum output
•
Per connection
(PC1)
•
Per connection
(VC1)
•
400 W (high-efficiency
pumps permissible;
max. 40 A/
s)
•
100 W
Temperature sensor
measuring range
•
lower fault limit
•
display range
•
upper fault limit
•
< – 10 °C
•
0 ... 100 °C
•
> 125 °C
permissible ambient
temperature
0 ... 60 °C
Protection class
•
For installation in
heat appliance
•
For wall mounted
installation
•
Determined by the IP rating of
the heat appliance
•
IP 44
IP rating
I
ID no.
Data plate (
Table 2
Содержание EMS plus MM100
Страница 95: ...6 720 807 448 2013 06 MM100 95 Fig 15 1 2 3 4 5 6 7 8 9 10 0 6 720 645 409 25 1O ...
Страница 102: ...6 720 807 448 2013 06 MM100 102 ...
Страница 103: ...6 720 807 448 2013 06 MM100 103 ...
Страница 104: ...Bosch Thermotechnik GmbH Sophienstrasse 30 32 D 35576 Wetzlar www bosch thermotechnology com ...