Release Notes for Firmware V2.07 | 7.0 

Fixed Items Since Firmware Version 1.08 

 

 

Bosch Security Systems | 8/06 | 36925V 

 

 

DS9431 Accidental Removal (DS9400M 
only):

 On control panels running firmware 

version 2.02 or earlier, if the wires on the 
keypad option bus are momentarily shorted for 
less than a second, the DS9431 Multiplex 
Expansion Module may stop working. If this 
occurs, the display will show “MUX NOT 
DETECTED” and the Trouble buzzer will 
sound. If the */Clear key is pressed, the DS9431 
will be uninstalled. 
Firmware version 2.03 corrects this problem. If 
the DS9431 should fail, a new message, “CALL 
FOR SERVICE,” will be displayed along with 
the following message, “MUX NOT 
WORKING.” Pressing the */Clear key will 
silence the Trouble buzzer, but will neither clear 
the trouble messages nor uninstall the DS9431. 
If “MUX NOT WORKING, CALL FOR 
SERVICE” or INST.FLT MX EXP” is 
displayed, the control panel should be powered 
down by removing AC and standby battery 
connections, and then restarted. Doing so will 
restore the DS9431 to proper operation. If the 
problem is not corrected, please contact 
Technical Support at (888) 886-6189. 

 

 

Make sure that you are at the control panel 
site with an available phone line before 
calling Technical Support. 

 

To remove the DS9431 after installing firmware 
version 2.03, please contact Technical Support at 
(888) 886-6189. 

 

DS9434 Four Point Expander Removal

: To 

prevent the accidental removal of the DS9434, a 
new message “CALL FOR SERVICE,” is 
displayed. If you wish to remove a previously 
installed DS9434, please contact Technical 
Support at (888) 886-6189. 

7.0  Fixed Items Since 

Firmware Version 1.08  

 

AC Failure during Automatic Battery Test

The DS9400 FACP automatically tests the 
standby batteries every 180 seconds for two 
seconds. The system will now continue normal 
operation if an AC power failure occurs exactly 
during this two-second battery test window. 

 

 

Boards shipped before August 31, 1999 
must be modified according to Technical 
Service Note (P/N: 42363) to ensure that 
the battery test runs properly. Affected 
boards carry a lot number of 99 or lower 
and a date code of 9935 or earlier. Boards 
shipped after August 31, 1999 with a date 
code higher than 9935 are unaffected. See 
Figure 1 on page 3 for the location of the 
lot number and date code. 

 

 

 

Figure 1: 

Firmware Version Label and Date 
Code Locations 

XXXX

2

1

3

 

1

 

Lot Number Label 

2

 

Firmware Version Label 

3

 

Date Code Stamp 

 

 

Do not exceed standby current ratings for 
the control panel. If the total current drawn 
from the smoke power and option bus 
power terminals exceeds 1 amp, the 
system may not be able to switch to battery 
power when AC fails. Current drawn from 
NACs and auxiliary power does not impact 
battery transfer operation. 

 

Содержание DS9400 Series

Страница 1: ...EN Release Notes for Firmware V2 07 Fire Alarm Control Panel DS9400 Series ...

Страница 2: ...grade Information If this firmware is installed in a control panel that has been running version 1 x software it is necessary to erase the old programming in the control panel and re select the control panel type when the control panel is first powered up Be careful to select 1 DS9400 an incorrect selection cannot be undone 3 0 Fixed Items in Firmware Version 2 05 Version 2 05 firmware for the DS9...

Страница 3: ... two on board relays is programmed using Zone 62 General Trouble For this output the relay will be energized when there are no troubles present in the system When there is a trouble the relay will de energize For this relay to function properly Zones B C and D must be programmed with a value of 00 The General Trouble output function can not be combined with any other output function When communica...

Страница 4: ...1 after installing firmware version 2 03 please contact Technical Support at 888 886 6189 DS9434 Four Point Expander Removal To prevent the accidental removal of the DS9434 a new message CALL FOR SERVICE is displayed If you wish to remove a previously installed DS9434 please contact Technical Support at 888 886 6189 7 0 Fixed Items Since Firmware Version 1 08 AC Failure during Automatic Battery Te...

Страница 5: ...ents on the line This issue was observed during recent lab testing of the control panel and has not been reported from actual installations but upgrading the firmware in installed control panels to version 2 02 will assure proper response time under all circumstances Programming Access Firmware version 2 02 corrects a configuration problem found in control panels with prior firmware that improperl...

Страница 6: ...emoval of DS9431 Multiplex Expansion Module Clears PINs If the DS9431 Multiplex Expansion Module is installed and then removed all Personal Identification Numbers PINs including the standard 16 PIN numbers will be erased when the DS9400 is re powered The PIN numbers can be re entered normally User ID Report for Drill and Walk Test As shown in Appendix C of the DS9400M Reference Guide P N 31499 or ...

Страница 7: ...one number or account number for phone number 2 while routing reports to line 1 backup line 2 If only one phone number is available for reporting set report steering for all events to phone 1 only Comm fault may also be caused if one of the phone lines has Telco battery voltage but will not complete a call Make test calls to the receiver s on both phone lines listening for the receiver ACK tone 6 ...

Страница 8: ... 2006 Bosch Security Systems 36925V Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 Customer Service 800 289 0096 Technical Support 888 886 6189 ...

Отзывы: