
DS484Q/DS486Q
|
Installation Instructions | 4.0
Setup and Alignment
10
Bosch Security Systems, Inc. | 7/05 | 4998138530F
4.0 Setup and Alignment
4.1 Setup
4.1.1 Receiver
Setup
Figure 14: Receiver Setup Switches
INTERRUPTION
TIME (msec)
50
75
100
150 200
300
400
500
ALIGNMENT IS COMPLETED
WHEN ‘ ‘ IS OFF
SW2 - 3 : CHANNEL
M
OFF
OFF
SW2
SW3
1
OFF
ON
2
ON
OFF
3
ON
ON
ALIGNMENT
CHECK
TERMINALS
SWITCH
OFF
↔
ON
No ITEM
OFF ON
1 Group
A
B
2
3
SEE CHART
BELOW
4 AND/OR AND OR
5 BYPASS OFF ON
6 SOUND
CHECK
OFF ON
EDC LEVEL
ALARM
1
2
3
1 - INTERRUPTION TIME switch
2 - DIP Switch 4 (ON or OFF for the AND/OR
gate)
3 - DIP Switch 5
2.
Select the beam alarm condition by setting DIP
Switch 4 ON or OFF for the AND/OR gate. Refer
to
Figure 14
.
•
If DIP Switch 4 is ON, the OR condition is
selected. The upper
or
lower beam pairs must
be broken to cause an alarm.
•
If DIP Switch 4 is OFF, the AND condition is
selected. The upper
and
lower beam pairs
must be broken to cause an alarm.
3.
Choose whether or not to bypass alarms by setting
DIP Switch 5 to ON or OFF when the EDC
activates. Refer to
Section 1.3.7 Environmental
Discrimination Circuit (EDC)
on page 4 for more
information.
The EDC is always on. DIP Switch 5 (BYPASS)
controls the alarm condition relative to the EDC
relay status. Refer to
Figure 4
on page 4.
•
If DIP Switch 5 is ON, the system alarms only
if the EDC relay is not activated. If the EDC is
activated, the system does not indicate an
alarm.
•
If DIP Switch 5 is OFF, the system alarms
regardless of whether the EDC relay is
activated or not.
Connect the EDC to a trouble circuit, and
check the system any time the EDC relay
activates.
If the EDC remains activated for prolonged
periods when the beam path is clear, the
beam might be misaligned. Refer to
Section 4.2 Alignment
on page 13 to re-
align the beam.
4.
Use a Phillips head screwdriver to adjust the rotary
INTERRUPTION TIME switch according to how
sensitive you want the detector to be to movement
(catch performance). Refer to
Figure 14
for the
location of the INTERRUPTION TIME switch.
Refer to
Table 4
for interruption times and
corresponding catch performance examples.
For UL applications, the interrupt time
cannot be set above 75 ms.
For best performance when using the AND
mode, do not exceed 100 ms beam
interruption time.
Table 4:
Beam Interruption Time Examples
Interrupt Time (ms)
Catch Performance
50
Running
100 Jogging
200
Fast Walking
300
400
Normal Walking
500
Slow Moving