D9210B
Installation
D9210B Operation and Installation Guide
© 2002 Bosch Security Systems
Page 17
32206G
3.2.5
Door Lock, Terminals 2, 3 and 4
State
Description
Common Input (3)
For 12/24 VDC strikes, provide the input power
here from the power supply.
Lock N/C (2)
For door strikes that require an interruption of
power to open, connect the positive side of the
door strike to this terminal.
Lock N/O (4)
For door strikes that require power to open,
connect the positive side of the door strike to
this terminal.
Description
. A removable relay (model D136)
provides a dry contact single pull double throw
output. Some strikes require a closed circuit to
unlock the door while others require an open
circuit to unlock the door. The relay will
support 12 VDC @ 2A or 24 VDC @ 2.5 A or
12/24 VAC @ 40 A (See Table 6).
Table 6: Door Lock Strikes
Relay Installation. The D136 Relay is installed into the relay socket of
the D9210B. Follow these steps for installing the relay:
1.
Locate the relay socket on the D9210B board (shown in
Figure 3).
2.
Place the relay into the socket. The plug-in relay has two
legs on the bottom and three legs on the top. When
inserting the relay, ensure that it is oriented as shown in
Figure 3.
1
PWR +
7
SDIB
6
SDIA
5
COM
8
T +
10
ZN +
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
11
ON
D9210B
MAN
U FA
CT
UR
E R
N A
ME
MA
NU
FA
CTUR
ER
NAM
E
D9210B
TOP
L
E
F
T
Figure 3: Relay Installation
3.2.6
Request to Enter [RTE], Terminals 11 and 12
Description.
When Terminal 11 is momentarily shorted to Terminal 12, the strike is activated and the door point is
shunted.
Shunt Only:
An option is provided that only shunts the point when this input is momentarily shorted. To activate the
shunt, but not the strike, program
RTE Shunt Only?
as [YES].
3.2.7
Request to Exit [REX], Terminals 13 and 12
Description.
When Terminal 13 is momentarily shorted to Terminal 12, the strike is activated and the door point is
shunted.
Shunt Only:
An option is provided that only shunts the point when this input is momentarily shorted. To activate the
shunt, but not the strike, program [REX]
Shunt Only?
as [YES].
REX must not be used for emergency exit applications. NFPA 101 requires that a UL listed panic device be
used to provide direct power from the standby power source. (
see Figure 2: Wiring Diagram for Typical
D9210B Installation
, p.15 for wiring an emergency exit device). Check with your local Authority Having
Jurisdiction (AHJ) prior to installing your system.
3.2.8
Enclosure Tamper Switch, Terminals 8 and 9
Description.
A short to this loop will generate a
Missing Trouble Point ###
for the point number assigned to
the D9210B. With this tamper point faulted, the D9210B will still function.
Connect a N/O tamper switch to Terminals 8 and 9. Upon opening the enclosure, the tamper switch will short the inputs
and generate the
Missing Trouble Point ###
message.
SDI FAILURE ###
and
MISSING PT ###
are reported to the central station when the SDI bus has
failed or the D9210B is missing.
Содержание D9210B
Страница 1: ...Access Control Interface Module D9210B Operation and Installation Guide ...
Страница 2: ...D9210B D9210B Operation and Installation Guide 32206G Page 2 2002 Bosch Security Systems ...
Страница 22: ...D9210B Installation D9210B Operation and Installation Guide 32206G Page 22 2002 Bosch Security Systems Notes ...
Страница 24: ...D9210B Operation D9210B Operation and Installation Guide 32206G Page 24 2002 Bosch Security Systems Notes ...