D8125 Operation and Installation Guide

D8125

Page 24

© 2004 Bosch Security Systems, Inc.

74-04247-000-N

Installation

0 1 2 3 4 5 6

Peel off and place Point
Label on POPIT cover

Peel off and place
POPIT Switch
Settings Label
to cover this chip

POPIT Cover

POPIT 6-position Terminal Block

POPIT Switches

Point Label

POPIT Switch Settings Label

D9127 POPIT shown
(6 Position Terminal Block and Switches
location similar on D8126 & D8127)

Figure 8: POPIT Label Placement for 9000 Series Control Panels

To place the POPIT Labels in using the D7212B1 or D9112B1, use the labels with the part number 79-04252-000 and either
the sheet marked Vertical Grid for POPEX #1  for points 9 to 71 or the sheet marked Vertical Grid for POPEX #2 for Points 73
to 135. Refer to Figure 9.

Vertical Grid for POPEX #1

(Use this Vertical Grid for D9112 Points 9 to 71)

D8112

MASTER ZONE 1

1 2 - 4 5 6

ZN 109

PX1

1 - 3 4 5 6

ZN 201

PX1

1 2 3 4 5 -

ZN 102

PX1

1 2 - 4 5 -

ZN 110

PX1

1 - 3 4 5 -

ZN 202

PX1

1 2 3 4 - 6

ZN 103

PX1

1 2 - 4 - 6

ZN 111

PX1

1 2 3 4 5 6

ZN 101

PX1

D8112

MASTER ZONE 1

POPIT Cover

POPIT 6 position Terminal Block

POPIT Switches

Point Label

POPIT Switch Settings Label

D9127 POPIT shown
(Terminal Block and Switches
location similar on D8126 & D8127)

PT 09

Peel off and place Point
Label on POPIT cover

Peel off and place
POPIT Switch
Settings Label
over this chip

Figure 9: POPIT Label Placement for D9112B1/D7212B1 Control Panels

Each label has two parts. Place the smaller part, with just the point number on it, on the POPIT terminal block as shown in
Figure 8 and Figure 9. Place the larger part with the switch settings on the POPIT cover. Set the switches and cover the POPIT.

Do not program two POPITs for the same point number. After you program all the points, perform a walk test. The
Security System Owner’s Manual (P/N: 74-06633-000) and the Security System User’s Guide (P/N: 71-06141-000) contain
instructions for performing a walk test. If a point does not test, check the programming for a duplicated address.

Содержание D8125

Страница 1: ...Zone Expansion Module D8125 Operation and Installation Guide ...

Страница 2: ...D8125 Operation and Installation Guide D8125 Page 2 2004 Bosch Security Systems Inc 74 04247 000 N ...

Страница 3: ... 1 Programming 14 2 6 1 2 Listing 14 2 6 2 Operation 14 2 7 D9124 Point Expansion 15 2 7 1 POPEX POPIT Configurations 15 3 0 Installation 17 3 1 D9412G D7412G D7212G D9412 D9112 D7412 D7212 17 3 1 1 Mounting to the Panel 17 3 1 2 Wiring to the Panel 17 3 1 2 1 Disconnecting the Battery and Transformer 17 3 1 2 2 Wiring Procedure 17 3 1 3 Wiring POPITs to the Data Expansion Loop 18 3 1 3 1 Combine ...

Страница 4: ...gnments 28 3 3 5 POPIT Labels 28 3 3 5 1 POPEX POPIT Configurations 29 3 3 6 POPIT Displays 33 3 3 6 1 Alarm Condition Displays 33 3 3 6 2 Fault Condition Displays 33 3 3 6 3 Trouble Condition Displays 33 3 3 7 Central Station Reports 34 3 3 7 1 Pulse and BFSK Reporting 34 3 3 7 2 Modem II Reporting 34 3 3 8 Local Status Test 35 3 3 8 1 Operation 35 3 3 8 2 Missing and Extra POPIT Modules 35 4 0 T...

Страница 5: ...er Setting 15 Figure 2 POPEX Installation 17 Figure 3 Connecting the D8125 POPEX to the 9000 Series Panel 19 Figure 4 Program Record Sheet 20 Figure 5 D8125 Connections 21 Figure 6 Typical Expansion Loop POPIT Configuration 22 Figure 7 D9112B1 Program Record Sheet 23 Figure 8 POPIT Label Placement for 9000 Series Control Panels 24 Figure 9 POPIT Label Placement for D9112B1 D7212B1 Control Panels 2...

Страница 6: ...D8125 Operation and Installation Guide D8125 Page 6 2004 Bosch Security Systems Inc 74 04247 000 N Notes Contents ...

Страница 7: ...D8125 POPEX Operation and Installation Guide Organization 1 2 Other Literature Referenced See the following for a more complete and detailed description of the D8125 POPEX Zone Expansion They have been included in the table below with their part number for easy ordering Contact Bosch Security Systems if you need to order additional literature Name of Literature Bosch Security Systems Part Number D...

Страница 8: ...lity of physical damage to the operator equipment and or proper execution of the program CAUTION Cautions the operator that physical damage to the equipment or improper execution of the program may occur IMPORTANT ImportantNotesshouldbeheededforsuccessfuloperationandprogramming Helpfultipsand orshortcutsmaybe included here Programming Note 0101 0101 0101 This covers notes and clarifications specif...

Страница 9: ...lications The control panel enclosure and POPIT modules required for specific UL or NFPA ZONEX system applications are listed below The D8108A Attack Resistant Enclosure meets or surpasses the requirements for all of these applications A D8109 Fire Enclosure can be used for fire applications Any mercantile combination fire and burglar system must use the D8126T D8127T D9127 POPIT Module Refer to U...

Страница 10: ...an open or shorted state the command center neither annunciates nor displays a trouble condition No Extra Point event is generated the system is presently in a Service Walk Test and the point input goes from an electrically normal state to an open or shorted state the command center neither annunciates nor displays a trouble condition However an Extra Point event is logged and printed to an on sit...

Страница 11: ...n may also be transmitted to a central station or printed to an on site printer if programmed to do so See the D7212G Program Entry Guide P N 4998138538 for programming options Extra Point events are generated when a POPIT is connected to the data expansion bus but does not have a Point Index assigned to it Shown below are instances when an EXTRA POINT event will or will not be generated If a POPI...

Страница 12: ...fe and Vault and Grade A Household systems and Proprietaryas a Control Unit for Household Fire Warning The D7212G is not listed for commercial fire applications See the D7212G Approved Applications Compliance Guide P N 4998138560 to determine the required equipment and enclosures for the application 2 4 Non G 9000 Series Point Expansion On the D9412 D9112 you can use POPIT Point Of Protection Inpu...

Страница 13: ...l number of points the D9112B1 can monitor to 134 The D7212B1 can monitor up to 40 off board points for a total of 48 points Each off board point requires a POPIT module POPITs connect to supervised two wire data expansion loops run from POPIT to POPIT throughout the premises Data expansion loops connect to a D8125 POPEX module POPEX modules connect to the point buss on the panel Terminals 23 and ...

Страница 14: ...are two different versions of the D8126 D8127 POPIT Modules the D8126T D8127T plastic enclosure which contains a tamper switch and the D8126U D8127U which comes in an untampered enclosure Both enclosures are made of UL Listed fire retardant material 2 6 1 1 Programming POPEX POPIT application programs are developed using the Remote Account Manager or the Bosch Security Systems D5200 Bar Code Progr...

Страница 15: ...y the proper setting of motherboard jumpers Make sure the jumpers above Terminals 18 to 24 on the motherboard are in the D8125 position Figure 1 2 7 1 POPEX POPIT Configurations With the D8125 POPEX Module you can use D8125 POPEX 1 data loops 1 to 4 Terminals 11 to 18 on the motherboard install a maximum of 119 POPITs Points 9 to 127 use Points 7 and 8 for power supply and initiation circuit super...

Страница 16: ...D8125 Operation and Installation Guide D8125 Page 16 2004 Bosch Security Systems Inc 74 04247 000 N Overview Notes ...

Страница 17: ...amagestheD8125 MakesureyouwiretheD8125AUXandGNDterminalstothepanel 3 1 2 2 Wiring Procedure For Points 9 to 127 9 to 75 on D7412 D7212 1 Connect the GND terminal of the D8125 to Terminal 23 on the D9412 D9112 Connect the GND terminal of theD8125toTerminal9ontheD7412 D7212 2 Connect the OUT terminal of the D8125 POPEX module to ZONEX IN 1 Terminal 27 3 Connect the IN terminal of the D8125 POPEX mod...

Страница 18: ... POPIT assigns it a point number regardless of its physical location Three inch clearance for tampered POPITs Mount tampered POPIT Modules at least 3 0 in 76 mm apart to prevent the tamper magnets from interfering with each other 3 1 4 Wiring Data Expansion Loops to POPEX Modules There are two positive and two negative data expansion loop terminals on each POPEX module Follow the procedure below t...

Страница 19: ...D8125 D8125 Operation and Installation Guide Page 19 2004 Bosch Security Systems Inc 74 04247 000 N Installation Figure 3 Connecting the D8125 POPEX to the 9000 Series Panel ...

Страница 20: ...on to the OFF position see Figure 4 The second column contains the translation of the point number into the ZONEX format See Point User Flag in the Panel Wide Parameters module of the D9412G D7412G Program Entry Guide P N 47775 for an explanation of this feature The third column contains the point number as it is displayed at command centers The fourth column contains the point index See the Point...

Страница 21: ...for the D7212B1 1 Connect the GND terminal of the D8125 POPEX module toTerminal 23 on the D9112B1 use Terminal 9 on the D7212B1 2 Connect the OUT terminal of the D8125 to ZONEX IN 1 Terminal27ontheD9112B1 D7212B1 3 Connect the IN terminal of the D8125 to ZONEX OUT 1 Terminal28ontheD9112B1 D7212B1 4 Connect theAUX terminal of the D8125 to Terminal 24 on the D9112B1 use Terminal 3 on the D7212B1 For...

Страница 22: ...r tampered POPITs Mount tampered POPIT modules at least 3 0 in 76 mm apart to prevent the tamper magnets from interfering with each other DATA LOOP POPIT DATA LOOP POPIT DATA LOOP POPIT DATA LOOP POPIT DATA LOOP POPIT DATA LOOP POPIT DATA LOOP POPIT DATA LOOP POPIT GND OUT IN AUX UP TO 63 POPITS NEGATIVE POSITIVE GND OUT IN AUX UP TO 63 POPITS NEGATIVE POSITIVE ZONE EXPANSION LOOP ZONE EXPANSION L...

Страница 23: ...numbered 0 to 6 left to right Set switches whose number appears in the setting to the ON position Set switches with a dash in the switch position in the setting to the OFF position See Figure 7 The second column contains the translation of the point number into the D8112 ZONEX format See Point User Flag in the Panel Wide Parameters module of the D9412G D7412G Program Entry Guide P N 47775 for an e...

Страница 24: ...201 PX1 1 2 3 4 5 ZN 102 PX1 1 2 4 5 ZN 110 PX1 1 3 4 5 ZN 202 PX1 1 2 3 4 6 ZN 103 PX1 1 2 4 6 ZN 111 PX1 1 2 3 4 5 6 ZN 101 PX1 D8112 MASTER ZONE 1 POPIT Cover POPIT 6 position Terminal Block POPIT Switches Point Label POPIT Switch Settings Label D9127 POPIT shown Terminal Block and Switches location similar on D8126 D8127 PT 09 Peel off and place Point Label on POPIT cover Peel off and place PO...

Страница 25: ...igure 11 4 Connect D8112G1 G2 Terminal 3 to the POPEXAUX terminal 5 Connect D8112G1 G2 Terminal 31 to the POPEX INterminal 6 Installing only onePOPEX Horizontal Mode Connect the POPEX OUT terminal to the D8112G1 G2 Terminal 28 then go to step 8 Vertical Mode Connect the POPEX OUT terminal to the D8112G1 G2 Terminal 27 or 28 then go to step 8 If an Independent Zone Control IZC D279 or D268 D269 is ...

Страница 26: ... telephone system Welding shop High voltage electrical equipment or transformers Public service police fire department etc using radio communications When wires must be run close to electrical lines fluorescent fixtures or telephone cabling POPIT Modules do not need to be wired in any particular order on the zone expansion loop A switch setting on each POPIT see POPIT Module Assignments identifies...

Страница 27: ...D8125 D8125 Operation and Installation Guide Page 27 2004 Bosch Security Systems Inc 74 04247 000 N Installation Figure 11 D8112G1 G2 POPEX and POPIT Module Installation ...

Страница 28: ...ltage drop Bosch SecuritySystemsrecommendstheuseoftwisted pairwireinallPOPEX POPITinstallations Ifanoisyorunstable environment is suspected or if a long sensor loop wire run is used the cable must be shielded against AC induction Refer to the AC induction hint in Wiring POPITs to the Expansion Loop in this section for more information 3 3 4 POPIT Module Assignments Six switches provided on each PO...

Страница 29: ...differences between the modes are listed below In the horizontal mode with one POPEX Module All eight zones of the D8112G1 G2 can be used in the ZONEX system Up to eight POPITs can be assigned to D8112G1 G2 Master Zones 1 7 A maximum of seven POPITs can be assigned to D8112G1 G2 Master Zone 8 A maximum of 63 POPITs can be installed In the horizontal mode with two POPEX Modules Up to 16 POPITs can ...

Страница 30: ... 4 and 8 A maximum of 126 POPITs can be installed Table 7 and Table 8 display all POPIT assignment switch settings for both the horizontal and vertical modes e g 1 2 3 4 Numbers 1 through 6 indicate switches 1 6 on the POPIT Module The dash indicates a switch is in the OFF or open position These switches assign each point of protection to a master zone refer to Section 3 2 6 POPIT Module Point Ass...

Страница 31: ... 1 3 6 ZN 307 1 6 ZN 407 2 3 6 ZN 507 2 6 ZN 607 3 6 ZN 707 6 ZN 807 POPEX 1 D8112G1 G2 TERMINAL 28 1 2 3 ZN 108 1 2 ZN 208 1 3 ZN 308 1 ZN 408 2 3 ZN 508 2 ZN 608 3 ZN 708 NOT USED 1 2 3 4 5 6 ZN 109 1 2 4 5 6 ZN 209 1 3 4 5 6 ZN 309 1 4 5 6 ZN 409 2 3 4 5 6 ZN 509 2 4 5 6 ZN 609 3 4 5 6 ZN 709 4 5 6 ZN 809 1 2 3 4 5 ZN 110 1 2 4 5 ZN 210 1 3 4 5 ZN 310 1 4 5 ZN 410 2 3 4 5 ZN 510 2 4 5 ZN 610 3 ...

Страница 32: ...ZN 306 3 5 ZN 406 1 2 3 5 ZN 506 1 3 5 ZN 606 2 3 5 ZN 706 3 5 ZN 806 1 2 3 6 ZN 107 1 3 6 ZN 207 2 3 6 ZN 307 3 6 ZN 407 1 2 3 6 ZN 507 1 3 6 ZN 607 2 3 6 ZN 707 3 6 ZN 807 1 2 3 ZN 108 1 3 ZN 208 2 3 ZN 308 3 ZN 408 1 2 3 ZN 508 1 3 ZN 608 2 3 ZN 708 3 ZN 808 1 2 4 5 6 ZN 109 1 4 5 6 ZN 209 2 4 5 6 ZN 309 4 5 6 ZN 409 1 2 4 5 6 ZN 509 1 4 5 6 ZN 609 2 4 5 6 ZN 709 4 5 6 ZN 809 1 2 4 5 ZN 110 1 4...

Страница 33: ...3 Trouble Condition Displays When a loop trouble occurs the following displays can appear on the D1252A rows of stars separate displays pertaining to individual points of protection Installation SERVICE WINDOWS Programmed display 8112 MAIN Standard display indicating a troubled zone ZN301S2 KITCHEN Programmed display 8112 PTEXT Standard POPIT status code for POPIT 301 Row of stars NOT READY TO ARM...

Страница 34: ...ssing condition the following report will be printed out on the D6500 Receiver tape ACCT 1234 RESTORAL ZN D ACCT 1234 RESTORAL ZN 101 When multiple points on the same master zone go into any trouble condition all of the points on the master zone must be returned to normal before individual restoral reports are sent to the D6500 receiver A RESTORAL ZONE D will however be sent when the backbone itse...

Страница 35: ...d from the D8112G1 G2 memory by arming the system and allowing the exit time to expire or disable restarttheD8112G1 G2 If a programmed point of protection does not respond to the polling interrogation a missing POPIT condition is displayed see Section 3 3 6 POPIT Displays An extra POPIT display indicates that the ZONEX program does not recognize a POPIT Module transmission Press any key on the D12...

Страница 36: ... etc the missing POPIT indicates a trouble condition MISSING POPIT 2 5 Z1POINTS 6 2 12 Z8POINTS 00 PROGRAMMED 2 6 Z2POINTS 6 2 7 Z3POINTS 6 2 8 Z4POINTS 6 2 9 Z5POINTS 6 2 10 Z6POINTS 00 2 11 Z7POINTS 00 MASTER ZONE 1 6 MASTER ZONE 2 6 MASTER ZONE 3 6 MASTER ZONE 4 6 MASTER ZONE 5 5 INSTALLED Figure 14 Missing POPIT Figure 15 illustrates a system with six POPITs assigned in programming to each of ...

Страница 37: ... 6 2 7 Z3POINTS 6 2 8 Z4POINTS 6 2 9 Z5POINTS 6 2 10 Z6POINTS 00 2 11 Z7POINTS 00 MASTER ZONE 1 6 MASTER ZONE 2 6 MASTER ZONE 3 6 MASTER ZONE 4 6 MASTER ZONE 5 5 MISSING POPIT MASTER ZONE 7 1 EXTRA POPIT INSTALLED Figure 16 POPIT Switch Setting Error Figure 17 also displays a system containing one POPIT with erroneous switch settings Both missing and extra POPIT conditions will be displayed on the...

Страница 38: ... similar Figure 17 will display the extra POPIT condition because all POPIT switch settings assigned to master zone 5 are unique In Figure 19 the extra POPIT condition is not displayed due to the duplication of switch settings If a POPIT is assigned to the wrong master zone and it has the same switch settings as a POPIT in that master zone the missing POPIT condition will be indicated but the extr...

Страница 39: ... The ServiceWalk Test will not test points in areas that are currently armed CAUTION Fire and other 24 hour points do not transmit reports during ServiceWalkTest The steps below outline a simple Service Walk Test procedure Figure 20 shows all the ServiceWalk Test options 1 Choose a command center with panel wide scope to conduct the test Be certain the display shows the idle disarmed text 2 Enter ...

Страница 40: ...n ZONEX 2 Sensor loop switch 1 to 8 is turned off on OctoPOPIT If the sensor loop switch on an OctoPOPIT is turned off for a programmed point the point reports as missing Point appears as missing at command centers and in reports to the receiver POPIT is not programmed correctly Verify that the switches on the POPIT are set for the missing POPIT number Switches set incorrectly can cause both missi...

Страница 41: ...248 Check to be certain all POPIT and OctoPOPIT address switches are set correctly POPITs cannot be used for Points 128 or 248 these are reserved for panel functions OctoPOPITs cannot be used for Points 121through 128 or 241through 248 Short on Aux Power Terminal 3 or ZONEX power Terminal 24 Terminals 3 and 24 share a common circuit breaker Check wiring and devices connected to these terminals for...

Страница 42: ...s programmed YES 3 Verify that the revision level of the 8112 AUX product handler is B1 or higher If you are not sure what revision level of the D8112 AUX product handler was loaded into the panel Verify that your D5100 programmer contains the D8112 AUX B1 or higher product handler Disconnect terminals 30 and 31 from the D8112 Copy the D8112 AUX file out of the D8112 Re Load the same 8112 AUX file...

Страница 43: ...ground on the drain wire 4 2 4 Extra POPIT Modules If the D1252A Command Center displays an extra POPIT status code e g ZN101X during a Command 44 1 Check the programming of horizontal or vertical mode in the D8112 handler program item 2 2 Hrzntl Yes No 2 Verify that the appropriate vertical or horizontal switch setting chart was used see Table 7 and Table 8 pages 27 and 28 respectively and that t...

Страница 44: ...ed condition and the system responds to the POPITs 3 If unable to resolve the problem contact Bosch Security Systems Technical Support 7 Keep all Zone Expansion Loops away from all AC current sources fluorescent lights high voltage transformers motors etc or sources of RF interference AC induction or RF interference may occur when a ZONEX system is installed in or near the following Radio station ...

Страница 45: ...ng 25 Module Assignments POPIT 28 POPEX POPIT Modules Horizontal Mode 31 Vertical Mode 32 POPEX Module Installation 25 POPEX Module Installation Central Station Reports 34 Local Status Test 35 Local Status Test Missing and Extra POPIT Modules 35 Local Status Test Operation 35 POPEX POPIT Configurations 29 POPIT Displays Alarm Condition 33 Fault Condition 33 POPEX Module Installation 33 Trouble Con...

Страница 46: ...D8112G1 G2 33 Documentation Conventions Introduction 8 Tips Notes Cautions and Warnings Introduction 8 Types Styles Used in this Manual Introduction 8 E Extra Points Problems with Points 9000 Series to D8125 POPEX Troubleshooting 42 Extra POPIT Modules D8112G1 G2 Troubleshooting 43 F Fault Condition POPIT Displays D8112G1 G2 33 FCC Notice 8 H Horizontal Mode D8112G1 G2 POPEX POPIT Modules 31 I Ins...

Страница 47: ...ts Off board 11 POPEX 11 POPEX POPIT Modules Horizontal Mode D8112G1 G2 31 Vertical Mode D8112G1 G2 32 POPEX Module 9000 Series POPIT Module Point Assignments20 POPIT Sensor Loops 18 D7212B1 POPIT Sensor Loops 23 D8125 D7212B1 Zonex Expansion Description 13 D9112B1 Zonex Expansion Description 13 to D7212B1 20 to D8112G1 G2 25 to D9112B1 20 D9112B1 POPIT Sensor Loops 23 Installation D8112G1 G2 25 P...

Страница 48: ...1 D8125 to D8112G1 G2 25 D8125 to D9112B1 21 Trouble Reports Modem II Reporting 34 Trouble Condition POPIT Displays D8112G1 G2 33 Troubleshooting 39 Basic 9000 Series to D8125 POPEX 39 D8112G1 G2 42 Additional Tips 43 D1252A POPIT Activity 42 Extra POPIT Modules 43 Introduction 42 Missing POPIT Modules 42 Types Styles Used in this Manual Introduction Documentation Conventions 8 V Vertical Mode D81...

Отзывы: