Sensitivity Setting
Must Not Alarm
Must Alarm
2
0% (no filter)
40% filter
0 or 3
0% (no filter)
60% filter
4
20% (filter)
60% filter
5
20% (filter)
80% filter
1 or 6
40% (filter)
80% filter
7
40% (filter)
80% filter
Table 8.1: Sensitivity and Response
Specifications
Electrical
Alarm Current (Receiver)
D296: 70 mA maximum at 24 VDC
D297: 75 mA at 12 VDC
Standby Current
D296 Receiver: 45 mA at 24 VDC
D296 Transmitter: 20 mA at 24 VDC
D297 Receiver: 50 mA at 12 VDC
D297 Transmitter: 20 mA at 12 VDC
Operating Voltage
D296: 18.0 VDC to 32.0 VDC
D297: 10.2 VDC to 15.0 VDC
Alarm contacts
Normally Open (N/O) contacts rated 1 A, 60 VDC maximum
for DC resistive loads; do not use with capacitive or inductive
loads
Auxiliary alarm contacts
Normally Open (N/O) contacts rated 1 A, 60 VDC maximum
for DC resistive loads; do not use with capacitive or inductive
loads
Trouble contacts
Normally Closed (N/C) contacts rated 1 A, 60 VDC maximum
for DC resistive loads; do not use with capacitive or inductive
loads
Environmental
Environment
Indoor, dry
Relative humidity
0% to 95%, non‑condensing
Temperature
(storage and operating)
-22°F to +130°F (-30°C to +54°C)
For UL Listed installations, the range is +32°F to +130°F (0°C
to +54°C)
9
26
en | Notices
Long-range Beam Smoke Detectors
2014.01 | 06 | F.01U.068.899
Installation Instructions
Bosch Security Systems, Inc.