12
en | Compatible detectors and modules
Powered loop interface
2018.06 | 4.0 | F.01U.036.340
Installation instructions
Bosch Security Systems, Inc.
Control panel to module distance
Maximum Wire Resistance
2
Ω
Maximum distance per wire size
Maximum distance
Wire size
60 ft. (15
m)
22 AWG (0.34
mm
2
)
160 ft. (40
m)
18 AWG (0.75
mm
2
)
Mechanical
Dimensions (H x W x D)
5
in. x 3
in. x 0.8
in. (12.7
cm x 7.6
cm x 2.0
cm)
7
Compatible detectors and modules
7.1
Compatible 2‑wire detectors
Underwriters Laboratories (UL) has found the following 2‑wire detectors to be compatible
with the D125B:
Manufacturer
CTN
Series
Base
Reversing* Maximum number of
detectors per loop
12
V
24
V
Bosch
D263
D263
N/A
8
8
D263TH
8
8
D263THC
8
8
D263THS
●
8
8
D285
D285
D287,
D288,
D340
10
10
D285TH
10
10
F220-P
F220
F220-B6
8
8
F220-PTH
8
8
F220-PTHC
8
8
F220-135
8
8
F220-135F
8
8
F220-190F
8
8
System Sensor
2W-B
i3
N/A
8
8
2WTA-B
8
8
2WT-B
8
8
5151
100
B110LP
10
10
* D132A does
not
operate at 24
V; use
only
on 12
V powered loops.
Содержание D125B