Powered loop interface
Specifications | en
11
Bosch Security Systems, Inc.
Installation instructions
2018.06 | 4.0 | F.01U.036.340
9 Power-limited, supervised positive to A
loop detectors (see
Wiring sensor
loops, page 6
)
10 Earth ground
11 Power‑limited, supervised switched
auxiliary power from the control
panel’s relay C to the switching relay
12 For 24
V applications, cut this wire
13 Negative connection from the auxiliary
power supply to the negative terminal
of the relay and panel common
14 Positive connection from the auxiliary
power supply to the positive terminals
of the relay
15 UL Listed regulated, power‑limited auxiliary power supply (12
VDC or 24
VDC) for fire
protection systems
6
Specifications
Electrical
12
VDC
24
VDC
Nominal operating voltage
Supplied by the control panel
or by a regulated,
power‑limited 12
VDC power
supply listed under UL864 or
UL1481
Supplied by a regulated,
power-limited 24
V power
supply listed under UL864 or
UL1481
Alarm Current (maximum)
–
One loop only
75 mA
168 mA
–
Both loops
145 mA
300 mA
Standby Current (maximum)
–
One loop only
12 mA
25 mA
–
Both loops
24 mA
50 mA
Electrical - two‑wire powered loop Class
B
Current
12
VDC
24
VDC
–
Alarm
> 11.8
mA
> 24.1
mA
–
Detector
3
mA
7
mA
–
Trouble
< 3.5
mA
< 7.5
mA
Loop wire resistance
50
Ω
50
Ω
Environmental
Environment
Indoor, dry
Operating Temperature
+32°F to +122°F (0°C to +50°C)
Relative Humidity
5% to 93% at +86°F (+30°C); non-condensing
Содержание D125B