6 720 821 651 (2017/05)
CRC200
Service menu | 17
8.1
System data menu
The heating system is configured automatically or manually in
this menu. With automatic configuration, important data are
preset.
Menu item
Default
setting
Control range
Functional description
HC assignment
1
1 ... 8
Number of the assigned heating zone
Auto-Config.
NO
NO | YES
NO: Manual configuration of the system
YES: Automatic system configuration, detects connected modules and
temperature sensors and presets important data.
Pump conn.
see
desciption
Heat Source |
HC Module
Heat Source: Heating pump connected to heat source (only for heating
zone 1). Heat Source is default if no CZM100 is detected.
HC Module: Heating pump connected to CZM100. HC Module is default if
CZM100 is detected.
Heat. System
High Temp
High Temp |
Low Temp.
Assign the heating system to the heating zone to cancel the factory default.
Control type
Room supply External simple |
External opt. |
Room supply |
Room output
Select control type (details in
Chapter 2.1.1, Page 4)
Outdoor reset operation (
):
External simple: simple outdoor reset control
External opt.: optimized outdoor reset control
Room temperature-dependent operations:
Room supply: supply temperature control
Room output: power output control (not possible if CZM100 is detected).
Ext.RoomSens. NO
NO | YES
NO: The room temperature is determined by the internal temperature
sensor of the user interface.
YES: An additional room temperature sensor connected to the user
interface (future feature; currently not available).
DHW
(factory settings
depend on
installed heat
source)
No | Yes, 3-wy vlv |
Yes, pr. pump
DHW is only available if supported by the heat source (not visible at combi
boilers)
No: No hot water system installed in conjunction with boiler
Yes, 3-wy vlv: Hot water system is supplied via 3-way valve
Yes, pr. pump: Hot water system is supplied via indirect tank
LLH Sensor /
System Supply
Sensor
No
No | Yes, on mod.
LLH Sensor / System Supply Sensor is only available for heating zone 1
No: No low-loss header installed
Yes, on mod.: Low-loss header installed (even if temperature sensor is
connected at heat source).
Recirculation
NO
NO | YES
Recirculation is only available for heating zone 1
NO: The recirculation pump cannot be controlled by the heat source.
YES: If the recirculation pump is to be controlled by the heat source, the
recirculation pump must be activated here as well.
Solar module
NO
NO | YES
NO: No solar module connected.
YES: No function in US/CA; no solar module available
WWSD
70 °F (21 °C) OFF | 50...86 °F
(10...30 °C)
Heating is off in the entire system at this set outdoor temperature. This
saves energy at higher outdoor temperatures. (only for heating zone 1)
Table 5 Settings in the system data menu