32 | Service menu
7.1.3 Menu Heating circuit 1 ... 8
Settings for the single heating circuits can be made in this
menu. For the selected heating circuit, for instance, it can be
set here which heating system is installed. In addition it can be
set whether a remote control is available and which control
type is used. There is also the possibility to optimise the
heating curves of the heating circuits.
Signal ext. heat req.
On/Off
An additional on/off temperature controller is connected to the heat source
(e.g. in a building control system).
0-10V
An additional 0-10 V temperature controller is connected to the heat source
(e.g. in a building control system).
Set value ext. heat req.
Flow temperature
The 0-10 V signal that is present at the connection for an external heat
requirement signal is interpreted as a requested flow temperature or heat
output.
Output
AirCorrFact min fan power -9 ...
0
... 9
Air correction at minimum fan output rate
AirCorrFact max fan pow.
-9 ...
0
... 9
Air correction at maximum fan output rate
3 WV centre pos.
Yes
3-way valve in centre position
No
Emerg. altern. op.
Yes
If the DHW cylinder takes a long time to charge, alternating operation
between DHW heating and CH is started to ensure that heating is supplied
despite the fact that DHW priority is set.
No
Turbine signal delay time
0.5
... 4 s
Turbine signal delay in seconds
Menu item
Adjustment range
Description
Table 14 Settings in the boiler data menu
NOTICE:
Risk of damaging the screed!
▶ If an underfloor heating system is used,
the max. flow temperature recommended
by the manufacturer of the system should
be observed.
Menu item
Adjustment range
Description
Heating circuit
installed
No
Heating circuit is not installed. If no heating circuit is installed, the heat
source is only used for DHW heating.
At the boiler
Electrical assemblies and components of the selected heating circuit are
directly connected to the heat source (only available with heating circuit 1).
At the module
Electrical assemblies and components of the selected heating circuit are
connected to a MM 100/MM 200 module.
Ctrl type h. circ. 1
Outdoor-temp.-
compensated
Further information on the control type
Æ
Control types, page 34
Outside temp. with low end
Room-temp.-compensated
Room temperature output
Constant
User interface
CR400
C 400/C 800 controls the selected heating circuit without remote control.
CW400
CW800
CR100
CR 100 is installed as remote control for the selected heating circuit
CR10
CR 10 is installed as remote control for the selected heating circuit
Table 15 Check settings in the menu Heating circuit 1 ... 8