![Bosch Control Air M Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/bosch/control-air-m/control-air-m_installation-and-operation-manual_50887013.webp)
Installation & Operation Manual
Control Air M/M+ Water to Water Applications
| 13
BTC 469503103 A | 02.2019
Data subject to change
8.4 Compliance
FCC Compliance
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
NOTICE: HARMFUL INTERFERENCE HAZARD
Changes or modifications not expressly approved
by the responsible party for compliance could void
the user’s authority to operate the equipment.
CE Compliance
NOTICE: HARMFUL INTERFERENCE HAZARD
This is a Class A product. In a domestic
environment, this product may cause radio
interference in which case the user may be
required to take adequate measures.
External sensor resistance requirements
Temp (°C)
Temp (°F)
Resistance (Ohms)
-40
-40
335,651
-35
-31
242,195
-30
-22
176,683
-25
-13
130,243
-20
-4
96,974
-15
5
72,895
-10
14
55,298
-5
23
42,315
0
32
32,651
5
41
25,395
10
50
19,903
15
59
15,714
20
68
12,494
25
77
10,000
30
86
8,056
35
95
6,530
40
104
5,325
45
113
4,367
50
122
3,601
55
131
2,985
60
140
2,487
65
149
2,082
70
158
1,752
Table 6