Operating and fault displays
45
Condens 7000 F – 6720871560 (2019/11)
14
Operating and fault displays
14.1
Control unit status indicators
Table 15 Operating codes
Operatin
g code
Sub-
code
Cause
Description
Test procedure/
Cause
Action
OA
-
Device is in optimized
switching mode.
A new request for burner
operation has occurred within
the set switching optimisation
time. Device is in standby
period. The standard switching
optimisation time is 10
minutes.
Check output setting on basic
controller.
Check the control setting at the
control unit.
Adjust boiler output to required
heat energy demand of the
building.
Adjust control setting to system
conditions.
OC
-
Beginning of burner start. -
-
-
OE
-
The device is on standby,
heat demand exists but too
much heat is being
delivered.
The current heat energy
demand from the system is
lower than that supplied by the
burner with the minimum
modulation setting.
-
-
OF
-
Insufficient flow rate
through the boiler.
Temperature difference
between supply and return
> 15 K
Temperature difference
between flow and safety
temperature sensor > 15 K
Check the flow temperature
with the basic controller,
check the return temperature
with the control unit or service
key, measure the resistance of
the boiler water temperature
sensor (high limit safety cut-
out) and compare it with the
curve.
Adjust the setting of the boiler
circulation pump.
Check the surface temperature of
the cast section, which is fitted
with the safety temperature
sensor, using a temperature
measuring instrument.
Check if cast section is blocked
with dirt.
OH
-
The device is on standby;
no heat energy demand
present.
The floor standing boiler is on
standby and there is no heat
requirement from the heating
circuit.
-
-
OL
-
Air/gas ratio control valve
opening.
-
-
-
OP
-
Waiting for fan to start up. Start-up of the fan has to be
detected before the sequence
can be continued.
-
-
OU
-
Beginning of burner start
program sequence.
-
-
-
OY
-
The current boiler
temperature is higher than
the set boiler water
temperature.
The current boiler temperature
is higher than the set boiler
water temperature.
The floor standing boiler is shut
down.
-
-
2P
564
Temperature rises too
quickly at the boiler
temperature sensor
( > 70K/min).
Heat exchanger cut-out due to
excessive rate of temperature
rise.
Little or no heat draw (e.g.
thermostatic valves and mixer
closed).
Volumetric flow rate too low.
Pump does not work.
Deposits in water carrying
parts of boiler (dirt from
heating system, calcification).
Ensure adequate heat draw-off.
Install adequately sized pumps.
Check whether the pump is being
activated. Replace the pump if
required.
Flush/clean heating water side of
boiler block with agents suitable
and approved for aluminium.
8Y
572
The control unit is locked
externally via the terminal
EV.
The control unit sets the heat
requirement to the burner
control unit to 0.
–
If external blocking is not required,
a jumper must be fitted to the EV
terminals.