10
|
Failures / Errors
A6
and operating LED is flashing
.
Combustion chamber NTC failure (behind burner) : when NTC not detected or open circuit
Control Step
Action
1.
Check if combustion chamber NTC dam-
aged or not and the position.
B
Switch off the appliance.
B
Pull the NTC cables out.
B
Measure NTC resistance.
Are the values correct ? (see NTC val-
ues)
yes:
B
Check the cable connection.
A6 failure still exist ? -->2.
no:
B
Change the NTC.
B
Connect the cable.
B
Switch on the appliance.
A6 failure still exist ? -->2.
2.
Check if cable damaged or not.
B
Switch off the appliance.
B
In case of NTC is cahnged :
- Pull the NTC cables out.
- Measure NTC resistance.
- Reconnect the NTC cable.
B
Pull out the 20 poled connector on
control unit.
B
Measure the NTC resistance directly
on 20 poled connector. Are the meas-
ured values on NTC and cocnector dif-
ferent ?
yes:
B
Change the cable harness.
B
Switch on the appliance.
A6 failure still exist ? -->3.
no:
-->3.
3.
Electronic card is defect.
B
Switch off the appliance.
B
Cut mains supply.
B
Change the electronic card.
B
Connect to main supply.
B
Switch on the appliance.