Heatronic boiler control settings
59
Greenstar FS/Combi FS – 6 720 810 590 (2020/04)
Service function 3.d: Minimum output (heating and DHW)
The output for heating and DHW can be set to any level in percent
between the minimum and maximum nominal output.
The
default setting
is the minimum nominal output (heating and DHW)
and varies according to appliance.
Service function 3.E: Cycle time, keeping DHW hot (only combi
boiler KWB..-3A)
NOTICE:
System damage or boiler malfunction!
▶ Never change the setting of this service function on heating boiler
KBR..-3A appliances.
This service function is only active in comfort mode.
It specifies the time from completion of preheating or DHW demand until
the next time the plate-type heat exchanger is heated up. This prevents
the plate-type heat exchanger from overheating.
The cycle time can be set from
20
to
60
minutes.
Default setting
is
20
(20 minutes).
Service function 3.F: Constant DHW period (only conbi boiler
KWB..-3A
NOTICE:
System damage or boiler malfunction!
▶ Never change the setting of this service function on heating boiler
KBR..-3A appliances.
The constant DHW period specifies how long the space heating mode
remains disabled after DHW is drawn.
The duration for keeping DHW hot can be set from
00
to
30
(0 to 30
minutes).
Default setting
is
01
(1 minute).
Service function 4.b: Maximum heat exchanger temperature (only
combi boiler KWB..-3A)
NOTICE:
System damage or boiler malfunction!
▶ Never change the setting of this service function on heating boiler
KBR..-3A appliances.
This function can be used to reduce limestone built-up in the heat
exchanger, which increases with temperature. The maximum heat
exchanger temperature can be set in steps of 1 °F (0.5 °C).
Service function
0.E
is set to
00
(metric units):
• The maximum temperature for keeping the heat exchanger hot can be
set from
40
to
65
(40 to 65 °C).
Service function
0.E
is set to
01
(US-customary units):
• The maximum temperature for keeping the heat exchanger hot can be
set from
104
to
150
(104 to 150 °F)
Default setting
is
140
(140 °F (60 °C)).
Service function 4.d: Audible fault warning tone
The appliance can be set to sound an audible alarm to alert the operator
of a fault present. The audible warning tone can be deactivated with the
service function 4.d.
•
00:
Warning tone off
•
01:
Warning tone on
Default setting
is
01
(ON).
Service function 4.E: Appliance type
This service function displays the appliance type detected.
Possible displays are:
•
00
: Central heating only
•
01
: Combi appliance
•
02
: DHW tank temperature sensor (NTC) connected to Heatronic.
•
03
: DHW tank thermostat connected to Heatronic.
•
04
: Stratified DHW tank
•
05
: Tank with NTC return
Service function 4.F: Condensate trap filling sequence
DANGER:
Risk of flue gas poisoning!
If the condensate trap is not filled, flue gas may escape from the dry trap.
▶ Only deactivate the trap filling sequence for servicing purposes.
▶ When servicing is complete, reactivate the trap filling function.
The trap filling sequence ensures that the condensate trap is filled after
initial installation or after a longer downtime of the appliance.
The trap filling sequence is activated if:
• The appliance is switched OFF using the ON/OFF switch
• The burner has not been in use for at least 28 days
• You are switching between summer and winter mode
The next time there is a demand for heat in central heating or hot water
mode, the appliance is held at low output for 15 minutes. The trap filling
sequence remains active until the appliance has completed 15 minutes
of operation at low output. The display shows
in alternation with the
supply temperature.
The following settings are available:
•
00:
Condensate trap filling sequence is off.
•
01:
Trap filling program at the lowest output.
•
02:
Trap filling sequence at set minimum output.
Default setting
is
01
.
Service function 5.A: Reset inspection interval
This function enables resetting the indication on the display after
completing inspection/servicing of the appliance.
Default setting
is
00
.
Service function 5.b: Fan post purge time
This service function allows setting the time the fan purges after the
burner is shut off.
The post purge time can be set from
01
to
18
(10 - 180 seconds).
Default setting
is
03
(30 seconds).
Service function 5.E: Functionality of black plug in boiler junction
box
With this service function you can set the functionality of the black plug
in the boiler junction box (
Section 7.1.4).
The following settings are possible:
•
00:
Off - black connector in junction box is disabled (120VAC output
deactivated).
•
01:
DHW recirculation pump enabled - see FW200 instructions on
how to set a recirculation pump program.