RDCI Series – All DC Inverter Outdoor Units
6 720 862 437 (
2016/10
)
OUTDOOR UNIT INSTALLATION | 7
■
Curve diagram of static pressure, air flow volume.
Table.4-5
Unit: mm
Table.4-6
Unit: mm
A
A≥300
A
A≥300
B
B≥250
B
B≥250
C
C≤3000
C
C≤3000
D
750≤D≤760
θ
θ
≤15°
θ
θ
≤15°
NOTE
■
Before installing the air deflector, please ensure the fan grill has
been taken off.
■
Once air deflector has been installed, the air volume, cooling/
heating capacity will decrease. The maximum angle allowed for the
shutter is 15 degrees.
■
Only one bend set is allowed.
■
Install anti vibration pads in between the unit and air deflector.
Fig. 4-22
12 ST3.9 self-threading screws
Remove the fan grills
10
01
12-Ø3.2
39
3
56
7
1250
411
411
213
411
411
213
Fig. 4-23
9500
10000
10500
11000
11500
12000
12500
0
5
10
15
20
25
Fig. 4-24
8/10HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
10500
11000
11500
12000
12500
13000
13500
0
5
10
15
20
25
Fig. 4-25
12HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
12500
13000
13500
14000
14500
15000
15500
0
5
10
15
20
25
Fig. 4-26
14/16HP
Air pressure curve diagram
(Remove the fan grills)
Air volume (m
3
/h)
Static pressure (Pa)
B
09
21
C
1210
A
Fig. 4-27
Example B
Support
Radius
Air outlet louver dimension (optional)
725
Ø3.2
39
3
56
7
1250
411
411
213
411
411
213
Fig. 4-28
Fig. 4-29
12 ST3.9 self-threading screws
Remove the fan grills
Содержание CLIMATE 5000 VRF RDCI Series
Страница 31: ...RDCI Series All DC Inverter Outdoor Units 6 720 862 437 2016 10 31 ...
Страница 33: ......
Страница 34: ...6 720 862 437 2016 10 RDCI Series All DC Inverter Outdoor Units 34 ...
Страница 35: ...RDCI Series All DC Inverter Outdoor Units 6 720 862 437 2016 10 35 ...
Страница 36: ......