Installation
Climate 5000 L • Climate 5000i U/L – 6721841493 (2022/05)
56
3
Installation
3.1
Before installation
CAUTION
Risk of injury from sharp edges!
▶ Wear protective gloves during installation.
CAUTION
Danger of burns!
During operation the pipes become hot.
▶ Make sure, that the pipes cooled down before touching them.
▶ Check the scope of delivery for damage.
▶ Check whether a hissing sound due to negative pressure can be
detected when opening the pipes of the indoor unit.
3.2
Requirements for installation site
▶ Observe minimum clearances (
Chapter 2.4 on page 55).
▶ Observe minimum room area.
Table 6 Minimum room area
Notices regarding the indoor unit
▶ Do not install the indoor unit in a room in which open ignition sources
(for example: open flames, an operating wall mounted gas boiler or
an operating electric heating system) are in operation.
▶ The installation location must not be higher than 2000 m above sea
level.
▶ Keep the air inlet and air outlet clear of any obstacles to allow the air
to circulate freely. Otherwise poor performance and higher noise
levels may occur.
▶ Keep TV, radio and similar appliances at least 1 m away from the
indoor unit.
▶ Do not install the indoor unit in rooms with a high humidity (e.g.
bathrooms or utility rooms).
▶ Indoor units with a cooling capacity of 2.0 to 5.3 kW are designed for
a single room.
▶ The ceiling construction and suspension system (on site) must be
able to support the weight of the appliance.
Notices regarding the outdoor unit
▶ The outdoor unit must not be exposed to machine oil vapour, hot
spring vapour, sulphur gas, etc.
▶ Do not install the outdoor unit directly next to water or where it is
exposed to sea air.
▶ The outdoor unit must always be kept free of snow.
▶ There must be no disruption caused by extract air or operating noise.
▶ Air should be able to circulate freely around the outdoor unit, but the
appliance must not be exposed to strong wind.
▶ Condensate that forms during operation must be able to drain off
easily. Lay a drain hose if required. In cold regions, installation of the
drain pipe is not advisable as freezing could result.
▶ Place the outdoor unit on a stable base.
Notes on the wired room controller
▶ The ambient temperature at the installation location should be in the
following range: −5...43 °C.
▶ The relative humidity at the installation location should be in the
following range: 40. 90 %.
3.3
Unit installation
NOTICE
Incorrect assembly can cause material damage.
If the appliance is mounted incorrectly, it may drop off the ceiling
▶ Only mount the appliance on a solid flat ceiling. The ceiling must be
able to carry the weight of the appliance.
▶ Only use screws and wall plugs that are suitable for the ceiling type
and appliance weight.
3.3.1
Installing the indoor unit
We recommend preparing the pipes before hanging the indoor unit so
that only the pipes need to be connected.
▶ Open the box at the top and lift the indoor unit out and up.
▶ Determine the installation location, taking the minimum clearances
and orientation of the pipes into consideration (
Fig. 5 to 4).
Make sure that the appliance fits between the structural ceiling and
suspended ceiling.
▶ The clearance between the built-in ducted indoor unit and drop
suspended ceiling must be at least 24 mm.
▶ Define and mark the position of the suspension bolts on the ceiling.
DANGER
Risk of injury!
The ceiling attachment must be suitable for carrying the weight of the
indoor unit. We recommend using threaded rods in order to be able to
adjust the height precisely.
DANGER
Risk of injury!
At least two persons are required to hang the appliance and fasten it
securely.
▶ Do not install the appliance on your own.
▶ Hang the appliance on the suspension bolts with the washers and nuts.
▶ Position the indoor unit at the correct height and align horizontally by
turning the nuts on the threaded rods.
NOTICE
If the appliance is not level condensate may leak out.
▶ Use a spirit level to align the appliance horizontally.
▶ Secure the appliance at the correct installation position with lock nuts.
▶ Establish pipe connections as described in chapter 3.5.1.
Appliance type
Installation height
[m]
Minimum room area
[m
2
]
CL5000iU D 35 E
≥ 2.3
≥ 4
CL5000iU D 53 E
≥ 2.3
≥ 4
CL5000iU D 70 E
≥ 2.3
≥ 6
CL5000iL D 88 E
≥ 2.3
≥ 7
CL5000iL D 105 E
≥ 2.3
≥ 10
CL5000iL D 125 E
≥ 2.3
≥ 12
CL5000iL D 140 E
≥ 2.3
≥ 12
CL5000iL D 160 E
≥ 2.3
≥ 13
Содержание CL5000iL CF 53 E
Страница 30: ......
Страница 31: ...Bosch Thermotechnik GmbH Junkersstrasse 20 24 D 73249 Wernau www bosch thermotechnology com ...