Troubleshooting
59
Climate 5000i – 6721824787 (2021/09)
Table 10
5.2
Faults without indication
Table 11
Fault code
Possible Cause
EC 07
Fan speed of outdoor unit outside the normal range
EC 51
Faulty parameter in the EEPROM of the outdoor unit
EC 52
Temperature sensor error at T3 (condenser coil)
EC 53
Temperature sensor error at T4 (outside temperature)
EC 54
Temperature sensor error at TP (compressor discharge pipe)
EC 56
Temperature sensor error at T2B (outlet of evaporator coil; only multi-split air conditioner)
EH 0A
EH 00
Faulty parameter in the EEPROM of the indoor unit
EH 0b
Communication error between main PCB of indoor unit and display
EH 02
Fault when detecting the zero-crossing signal
EH 03
Fan speed of indoor unit outside the normal range
EH 60
Temperature sensor error at T1 (room temperature)
EH 61
Temperature sensor error at T2 (centre of evaporator coil)
EL 0C
1)
1) Leak detection not active, if in a system with multi-split air conditioner.
Insufficient or escaping refrigerant or temperature sensor error at T2
EL 01
Communication error between IDU and ODU
PC 00
Fault at IPM module or IGBT overcurrent protection
PC 01
Over- or undervoltage protection
PC 02
Temperature protection at compressor or overheating protection at IPM module or pressure relief device
PC 03
Low pressure protection
PC 04
Inverter compressor module error
PC 08
Protection against current overload
PC 40
Communication fault between main PCB of outdoor unit and main PCB of compressor drive
−−
Conflicting operating mode of indoor units; operating mode of indoor units and outdoor unit must correspond.
Error
Possible Cause
Remedy
The output of the indoor unit is too low.
Heat exchanger of outdoor or indoor unit soiled. ▶ Clean heat exchanger of outdoor or indoor
unit.
Lack of refrigerant
▶ Check tightness of pipes, reseal if required.
▶ Refill refrigerant.
Outdoor unit or indoor unit is not working.
No power
▶ Check power connection.
▶ Power on the indoor unit.
RCD or built-in fuse
1)
has tripped.
1) A fuse for overcurrent protection is located on the PCB. The specifications of the fuse are printed on the PCB and can also be found in the technical data on page 61. Only use
a blast-proof ceramic fuse.
▶ Check power connection.
▶ Check RCD or fuse.
Outdoor unit or indoor unit starts and stops
continuously.
Insufficient refrigerant in the system.
▶ Check tightness of pipes, reseal if required.
▶ Refill refrigerant.
Too much refrigerant in the system.
▶ Remove refrigerant with refrigerant recovery
unit.
Moisture or impurities in the refrigerant circuit.
▶ Evacuate refrigerant circuit.
▶ Fill with new refrigerant.
Voltage fluctuations too high.
▶ Install voltage regulator.
Defective compressor.
▶ Replace compressor.