If the refrigerant leaks during installation, ventilate the area im-

mediately.

Toxic gas may be produced if the refrigerant comes into the place 

contacting with fire.

The temperature of refrigerant circuit will be high, please keep 

the communication cable away from the copper tube.
After completing the installation work, check that the refrigerant 

does not leak.

Toxic gas may be produced if the refrigerant leaks into the room and 

comes into contact with a source of fire, such as a fan heater, stove or 

cooker.

CAUTION

Ground the air conditioner.

Do not connect the ground wire to gas or water pipes, light-

ning rod or a telephone ground wire. Incomplete grounding 

may result in electric shocks.

Ensure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in 

electric shocks.

Connect the outdoor unit first and then the indoor unit 

cables.

You are not allow to connect the air conditioner with the 

power source until wiring and pipework for the air condi-

tioner is complete.

While following the instructions in this installation 

manual, install drain piping in order to ensure proper 

drainage and insulate piping in order to prevent con-

densation.

Incorrect drain piping may result in water leakage and 

property damage.

Install the indoor and outdoor units, power supply 

wiring and connecting wires at least 1 metre away from 

televisions or radios in order to prevent image interfer-

ence or noise.

Depending on the radio waves, a distance of 1 metre may 

not be sufficient enough to eliminate the noise.

The appliance is not intended for use by young children 

or infirm persons without supervision.
Do not install the air conditioner in the following loca-

tions:

 

There is petrolatum existing.

 

 Salty atmosphere (near the coast). If this can't be 

avoided, choose a anticorrosive model.

 

 There is caustic gas (the sulfide, for example) existing 

in the air (near a hot spring).

 

The Volt vibrates violently (in the factories).

 

In buses or cabinets.

 

In kitchen where it is full of oil gas.

 

There is strong electromagnetic wave existing.

 

There are inflammable materials or gas.

 

There is acid or alkaline liquid evaporating.

 

Other special conditions.

 

 The appliance shall not be installed in the laundry room.

2. 

INSTALLATION INFORMATION

 

 To install properly, please read this "installation manual" at 

first.

 

The air conditioner must be installed by only competent persons.

 

 When installing the indoor unit or its pipe work and cabling, 

please follow this manual.

 

 If the air conditioner is installed on a metal part of the 

building, it must be electrically insulated according to the 

relevant standards to electrical appliances.

 

 When all the installation work is finished, please turn on the 

power only after a thorough check.

 

 Regret for no further announcement if there is any change of 

this manual caused by product improvement.

INSTALLATION ORDER

 

Select the location;

 

Install the indoor unit;

 

Install the outdoor unit;

 

Install the connecting pipe ;

 

Connect the drain pipe;

 

Wiring;

 

Test operation.

3. 

ATTACHED FITTINGS

Please check whether the following fittings are supplied.
You may find there are extra parts supplied.

Name of Accessories Qty

Outline

Usage

Installation manual

1

(This 

manual)

Hook

2

Hang-

ing arm

model 

36~140

2

model 160

4

Network matching cable

1

The indoor unit which 

at the terminal of com-

munication system 

should connect a 

impedance between 

port P and port Q.

Drainage pipe

1

Drainage

Thermal insulation pipe 

(160model)

1

Keep the drainage 

pipe temperature

Bolt assembly

4

Copper

1

Use for pipe connec-

tion of engineering 

installation

Snapring

1

Use for fastening the 

drainage pipe

|

 INSTALLATION INFORMATION 

6720874436 (2017/04)

Ceiling-Floor Type Indoor Unit

Содержание CF112-1D

Страница 1: ...CF90 1D CF56 1D CF112 1D CF71 1D CF140 1D Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Climate 5000 VRF Ceiling Floor Type Indoor Unit CF Series DC Fan Motor ...

Страница 2: ...2 NOTES 6720874436 2017 04 Ceiling Floor Type Indoor Unit ...

Страница 3: ...jury The appliance shall not be installed in the laundry room Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The enclosure of the appliance shall be marked by word or by symbols with the direction of the fluid flow For electrical work follow the local national wiring standard regulation and this installa...

Страница 4: ...lty atmosphere near the coast If this can t be avoided choose a anticorrosive model There is caustic gas the sulfide for example existing in the air near a hot spring The Volt vibrates violently in the factories In buses or cabinets In kitchen where it is full of oil gas There is strong electromagnetic wave existing There are inflammable materials or gas There is acid or alkaline liquid evaporatin...

Страница 5: ...ences Do not install the remote controller in a place exposed to direct sunlight or close to a heating source such as a stove Ensurethatthebatteriesarefittedthecorrectwayround NOTE This manual is subject to changes due to technological improvement without further notices 4 INDOOR UNIT INSTALLATION 4 1 The units may be mounted vertically provided that the correct clearances for positioning are main...

Страница 6: ...ing arm 20 25mm Mounting bolt max 40mm 8 13mm INDOOR UNIT Screw nut 20 25 mm 8 13 mm Mounting bolt max 40 mm INDOOR UNIT Washer Hanging screw bolt Hanging arm Hang the unit on the hanging arm by sliding backward Securely tighten the mounting bolts on both sides Refer to Fig 4 9 1 Connect the hook with self tapping screw onto the wall Refer to Fig 4 4 Fig 4 4 Washer Tapping screw 6mm Hook Hook Tapp...

Страница 7: ...ture of refrigerant circuit will be high please keep the interconnection cable away from the copper tube 5 1 The Procedure of Connecting Pipes 5 1 1 Measure the necessary length of the connecting pipe and use the following process 1 Connect the indoor unit at first then the outdoor unit a Use a pipe bender to form the radius of the pipework CAUTION 1 Cover the surfaces of the flare pipe and the jo...

Страница 8: ...t of the connecting pipe to the indoor unit with the soundproof insulating sheath fittings and tape it well to prevent leakage 6 CONNECT THE DRAIN PIPE 6 1 Install the drainpipe of the indoor unit The outlet has PTI screw bread Please use sealing materials and pipe sheath fitting when connecting PVC pipes CAUTION The drain pipe of the indoor unit must be heat insulated or it will produce condensat...

Страница 9: ...ication of power Table 7 1 TYPE W 3600 14000W Phase 1 PHASE Power Frequency volt 220 240V 50Hz 208 230V 60Hz Circuit breaker fuse a 5 3 Indoor unit power cable mm2 1 0 Indoor outdoor connecting cable mm2 Cable size mm2 1 0 Electric signal 0 75 CAUTION A disconnection device having an air gap contact separa tion in all active conductors should be incorporated in the fixed wiring according to the Na...

Страница 10: ...itted to alter the cooling output which be set before shipping from factory except licensed maintain personnel 2 3600 W 3 4500 W 4 5600 W 5 7100 W 6 8000 W 7 9000 W 8 11200 W 9 14000 W CAUTION The system together can have 64 units 0 63 everyone has only system address code If two addresses are the same in one system a abnormal operation will occur Please switch off the power before setting otherwi...

Страница 11: ...ching mode default setting 1234 SW1 ON 01 means DC fan static pressure is 1 reserved 1234 SW1 ON 1 means DC fan Is chosen 0 means AC fan Is chosen 1234 SW1 ON 10 means DC fan static pressure is 2 reserved 1234 SW1 ON 00 means DC fan static pressure is 0 reserved 1234 SW1 ON 11 means DC fan static pressure is 3 reserved SW2 definition 1234 SW2 ON 00 means the temperature is 15 degrees when shutting...

Страница 12: ...eating mode SW6 definition 1 2 3 SW6 ON 1 means old display panel 0 means new display panel 1 2 3 SW6 ON 1 means auto wind under auto mode 0 means auto wind under non auto mode 1 2 3 SW6 ON reserved SW7 definition 1 2 SW7 ON Standard configure 1 2 SW7 ON Last one in the network J1 J2 definition J1 J1 no Jumpers means power off memory function J1 J1 Jumpers means no power off memory function J2 res...

Страница 13: ... conditioner under the mode of COOLING with the remote controller and check the following points If there is any malfunction please resolve it according to the chapter Troubleshooting in the Owner s Manual 1 The indoor unit a Whether the switch on the remote controller works well b Whether the buttons on the remote controller works well c Whether the air flow Louvre moves normally d Whether the ro...

Страница 14: ...14 NOTES 6720874436 2017 04 Ceiling Floor Type Indoor Unit ...

Страница 15: ...Ceiling Floor Type Indoor Unit 6720874436 2017 04 NOTES 15 ...

Страница 16: ...Robert Bosch Pty Ltd 15th Road Randjespark 1685 Midrand SOUTH AFRICA ...

Отзывы: