2 6 |
Bosch IDS BVA 2.0
Installation Instructions
02.2019
|
Bosch Thermotechnology Corp.
Data subject to change
Figure 23
COM
208V
240V
WHITE/BLACK
W2
CN35
CN33
CN4
CN5
DETAILED REFERENCE
MANUAL INSTRUCTIONS
SPEED TAPS
WHITE
GRA
Y
BLUE
MEDIUM LOW
LOW
MEDIUM
MEDIUM HIGH
HIGH
B
W1
Y2
GREEN
RED
YELLOW
R
C
Y1
PURPLE
BROWN
CN38
CN39
L1-A
L1-B
CN36
T2 OPEN
LED4
INDOOR MAIN BOARD
SW6-1,2
SW6-3
NORMAL
HEAT:
FAN DELAY START
HEAT:
ANTI-COLD AIR
FAN DELAY
POWER ON
ON
3
C
CN6
G
SCHEMATIC DIAGRAM
SEE RATING PLATE FOR VOLT&HERTZ
FIELD POWER WIRING
54321C
1 * / &
HEATER
KIT PLUG
1 * / &
GROUND
POWER IN
6
SW6
BLACK
BLACK
RED
RED
RED
NOTES:
NOTES:
1: If connected to 1-Stage thermostat jump Y1 and Y2.
1: If connected to 1-Stage thermostat jump Y1 and Y2.
2: Use copper wire (75
2: Use copper wire (75
℃
℃
min) only between disconnect switch and unit .
min) only between disconnect switch and unit .
3: Rewired in accordance with NEC and local codes.
3: Rewired in accordance with NEC and local codes.
4: If any of the original wire, as supplied, must be replaced use the same or
4: If any of the original wire, as supplied, must be replaced use the same or
equivalent type wire.
equivalent type wire.
5: Connect R to R,G to G,Y1 to Y,etc.See outdoor instruction for details.
5: Connect R to R,G to G,Y1 to Y,etc.See outdoor instruction for details.
6: If some signal lines of CN4 and CN5 are not used, wrap them up
6: If some signal lines of CN4 and CN5 are not used, wrap them up
separately with CAP.
separately with CAP.
7: See airflow tables for airflow settings.
7: See airflow tables for airflow settings.
8
: :
When need to change the transformer stage, remove the lead from “240V”
When need to change the transformer stage, remove the lead from “240V”
terminal and then connect the lead to “208V”terminal.
terminal and then connect the lead to “208V”terminal.
ON
ON
ON
ON
SW6-4
1 2
ON
CAUTION:
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
.
.
24V
WHITE
YELLOW
BLUE
PURPLE
GREEN
1 * / &
ANTI-COLD
AIR FAN
DELAY
TRANSFORMER
FAN
GREEN LED4 FLASH
WORKING
5
T2 TEMPERATURE
SENSOR FAULT
/
燧燩1燨燫1燫燥1
燩燭1
DEHUMIDIFICATION
1
/
NORMAL
BROWN
W2
W1
Dh
Y1+Y2 OR W
Y1 OR G
1
1
2
3
2
3
4
5
*
FACTORY DEFAULT
RESERVED
FAN SPEED
TAPS
*
*
*
3
ON
4
ON
4
ON
1
OFF
1
YELLOW
1 2
1 2
1 2
1 2
ON
3
Switch ON Position:
Color upper half to show
switch position is UP.
Switch OFF Position:
Color upper half to show
switch position is DOWN.
ANTI-COLD
AIR FAN
DELAY
Indoor Unit Wiring Diagram