4.5 Electric Heat Kit MCA/MOP Data
Heat Kit Model
Air Handler
Model
(kW)Electric
Heat
MIN. Circuit Ampacity
MAX.Fuse or Breaker (HACR) Ampacity
Fan speed
240 VAC
208 VAC
240 VAC
208 VAC
1
2
3
4
5
EHK-05B
24
5
29.4
25.9
30
30
●
●
●
●
●
EHK-08B
7.5
42.4
37.2
45
40
X
X
●
●
●
EHK-10B
10
55.4
48.5
60
50
X
X
●
●
●
EHK-05B
36
5
29.9
26.4
30
30
●
●
●
●
●
EHK-08B
7.5
42.9
37.7
45
40
X
●
●
●
●
EHK-10B
10
55.9
49
60
50
X
X
●
●
●
EHK-15B
15
55.9/26.1
49/22.6
60/30
50/25
X
X
●
●
●
EHK-05B
48
5
31.8
28.3
35
30
●
●
●
●
●
EHK-08B
7.5
44.8
39.6
45
40
●
●
●
●
●
EHK-10B
10
57.8
50.9
60
60
X
●
●
●
●
EHK-15B
15
57.8/26.1
50.9/22.6
60/30
60/25
X
X
●
●
●
EHK-20B
20
57.8/52.1
50.9/45.2
60/60
60/50
X
X
X
●
●
EHK-05B
60
5
31.8
28.3
35
30
X
X
●
●
●
EHK-08B
7.5
44.8
39.6
45
40
X
X
●
●
●
EHK-10B
10
57.8
50.9
60
60
X
X
●
●
●
EHK-15B
15
57.8/26.1
50.9/22.6
60/30
60/25
X
X
●
●
●
EHK-20B
20
57.8/52.1
50.9/45.2
60/60
60/50
X
X
X
●
●
Table 5
Suitable heat kits for AHU multi position installation
—
Heat kit suitable for AHU 4-way position installation.
—
Ampacities for MCA and Fuse/breaker including the blower motor
—
Heat pump systems require a specifi ed airfl ow. Each ton of cooling requires
between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally.
Heater Kit Accessories
Model
Description
24
36
48
60
EHK05B
5 kW Heat Kit, Double Pole Breaker
●
●
●
●
EHK08B
7.5 kW Heat Kit, Double Pole Breaker
●
●
●
●
EHK10B
10 kW Heat Kit, Double Pole Breaker
●
●
●
●
EHK15B
15 kW Heat Kit, Double Pole Breaker
X
●
●
●
EHK20B
20 kW Heat Kit, Double Pole Breaker
X
X
●
●
Table 6
[ ● means available, X means not available ]