You want to retrieve the address "Input Register 34 - HMI State" from substation 8
via the master using Slave12:
𝑂𝑓𝑓𝑠𝑒𝑡𝑆𝑙𝑎𝑣𝑒12 = (12 − 10) ∗ 8 ∗ 500 = 8000
𝑂𝑓𝑓𝑠𝑒𝑡𝑆𝑢𝑏𝑆𝑙𝑎𝑣𝑒8 = (8 − 1) ∗ 500 = 3500
𝑂𝑓𝑓𝑠𝑒𝑡𝑆𝑢𝑏𝑆𝑙𝑎𝑣𝑒12
8
= 10000 + 8000 + 3500 = 21500
𝐴𝑑𝑟𝑒𝑠𝑠𝑒𝑉𝑖𝑎𝑀𝑎𝑠𝑡𝑒𝑟 = 21500 + 34 = 21534
You can access the HMI State of slave station 8 of segment slave station 12 via the
head-end station using the address "Input Register 21534".