Installation Instructions
7.
Vent Pipe Installation
• Make sure vent pipe is gas tight and will not
leak. Use heat resistant silicon sealant wher-
ever necessary.
• Do not place any dangerous objects at the end
of the exhaust vent.
• Steam (smoke) or water drops may come out
from the end of the exhaust pipe. Select the
location for the end of the vent so that steam is
not visible, and the vent is not wet with drip-
ping water.
• If snow is expected to accumulate, take care
that the end of the pipe is not covered with
snow or hit by falling lumps of snow.
• Use a maximum of 1m of straight vertical pipe
before the first elbow.
• Minimum flue length
1 elbow (90 degree) + Flue Terminal.
• Consult the vent pipe manufacturer's install-
ation instructions for chimney connections.
• Do not common vent or connect more than
one appliance to this venting system.
Vent Piping
• Use only Bosch vent materials.
• Follow the vent pipe manufacturer's installation
instructions.
• Make the vertical section of the exhaust vent
as short as possible.
• Maintain the same vent pipe diameter all the
way to the end.
Pipe diameter
100mm
No. of Elbows
Max. Straight Vent Length
3
5m
2
9m
1
13m
Horizontal Vent Termination
• Terminate at least 350mm above
ground.
• Terminate at least 2.3m above
a public walkway, 2m from the
combustion air intake of any
appliance, and 1m from any
other building opening, gas
utility meter, service regulator
etc.
• Terminate at least 1m above
any forced air inlet, 1.5m
below, 500mm horizontally
from and 300mm above any
door, window, or gravity air
inlet into any building as per
AS5601.
• Slope the horizontal vent
50mm upwards for every 1m.
• Use a condensation drain if
necessary.
Elbow
Hanger
Straps
Wall
Thimble
Termination
1m
Max.
Slope
Upwards
(Indoor Installation Only)