16
en | Specifications
Analog Detectors and Bases
F.01U.173.498 | 1.3 | 2012.02
Installation and Operation Guide
Bosch Security Systems, Inc.
General
Table 8.1
Technical Specifications
Sensors
Table 8.2
Technical Specifications Sensors
Isolator Bases
Table 8.3
Technical Specifications Isolator Bases
Operating voltage (SLC loop)
24 V DC to 41 V DC
Maximum current consumption at 77 °F (25 °C) and
39 V bus voltage
–
Standby
–
Alarm
–
When polled
170 μA
5 mA
22 mA ± 20%
Maximum allowable line resistance
50 Ω
Installation temperature
+32 °F to +100 °F (0 °C to +38 °C)
If the sensitivity temperature is programmed within a range of
+175 °F to +249 °F (+79.4 °C to +120.6 °C), the maximum
installation temperature is +150 °F (+66 °C).
Storage temperature
–
Without CO sensor
–
With CO sensor
-13 °F to +176 °F (-25 °C to +80 °C)
+14 °F to +122 °F (-10 °C to +50 °C)
Humidity
< 95% (non-condensing)
Protection category
IP 42
Mounting locations and heights in general
Refer to NFPA-72
Maximum spacing between detectors
–
Smoke detector
–
Heat detector
30 ft. (9.1 m)
50 ft. (15.2 m)
Minimum mounting distance to magnets
(e.g. loudspeaker)
11.8 in. (30 cm)
Maximum wiring length to C point
9.8 ft. (3 m)
Dimensions (diameter x height)
–
Detector
–
Detector with 4-inch base
–
Detector with 6-inch base
4.4 in. x 2.0 in. (11.2 cm x 5.1 cm)
5.0 in. x 2.5 in. (12.7 cm x 6.4 cm)
7.0 in. x 2.5 in. (17.8 cm x 6.4 cm)
Housing material
Cycoloy/ABS
Maximum airflow
4000 ft/min (20m/s)
Sensitivity
–
Smoke sensor
–
Heat sensor (FAP-440 detectors)
–
Heat sensor (FAH-440 heat detectors)
1.25%/ft to 3.5%/ft
+135 °F (+57 °C) + RoR
+135 °F to +194 °F (+57 °C to +90 °C), progra RoR
Maximum current consumption at 77 °F (25 °C) and
39 V bus voltage
–
Standby
–
Alarm
70 μA
10 mA
Internal resistance
< 50 mΩ
Power up time
< 30 ms
Shut down
< 50 ms