AMAX panel 4000 / AMAX panel 4000 EN

ICP-AMAX4-P1 / ICP-AMAX4-P2-EN / ICP-AMAX4-P3-EN

 

 

en

Quick Start Guide

 

Содержание AMAX panel 4000

Страница 1: ...AMAX panel 4000 AMAX panel 4000 EN ICP AMAX4 P1 ICP AMAX4 P2 EN ICP AMAX4 P3 EN en Quick Start Guide ...

Страница 2: ......

Страница 3: ...Keypad Menu Programming 10 4 1 2 LED Icon LCD Keypad Address Programming 10 4 2 Reset to Factory Default Settings 11 4 3 LCD Menu Programming 12 4 4 Address Programming 20 4 4 1 Communication and Report Setting 20 4 4 2 Zone Programming 26 4 4 3 Output Programming 38 4 4 4 Access Codes 43 4 4 5 System Programming 49 5 Troubleshooting 63 6 Technical Data 66 AMAX panel 4000 AMAX panel 4000 EN Table ...

Страница 4: ...components and describe how to simply program and operate the system with IUI AMAX4 TEXT keypad IUI AMAX3 LED16 keypad IUI AMAX3 LED8 keypad ICPKP8 LED keypad or ICP KP8L Icon LCD keypad As the system includes a large number of programmable functions and options we suggest reading the complete installation manual For detailed operation method please refer to the User Guide 1 4 en Short information...

Страница 5: ...System overview Information Customer Location Account Installer Date 2 AMAX panel 4000 AMAX panel 4000 EN System overview en 5 Bosch Sicherheitssysteme GmbH Quick Start Guide 2013 07 03 F 01U 267 113 ...

Страница 6: ...correctly For operation safety the ground terminals must be connected 3 3 2 Slow flash Normal state On Trouble state Off Trouble state _ _ _ _ _ _ _ _ 12V 12V 12V COM _ 12V 7Ah AUX2 12V _ COM supervised PO 5 Z1 2 2 3 3 Keypads IUI AMAX4 TEXT IUI AMAX3 LED16 IUI AMAX3 LED8 Keypads IUI AMAX LED8 IUI AMAX LCD8 I O Moduls DX2010 Adr 103 108 DX3010 Adr 150 151 DX4010 Adr 253 Communicators DX4020G Adr 1...

Страница 7: ...erson four times a year System Power Up After the system is powered up set date and time Otherwise the system prompts as fault After the system is powered up or reset it resets to previous arming disarming status To reduce false alarms caused by system power up or by power supply restoration after both mains supply and AUX power supply fail the system is designed to not perform zone test within on...

Страница 8: ... 5 4 Change Individual Code Code 5 5 Change Dom estic Phone No 1 Code 5 6 _ _ _ _ _ _ LED KP Change Dom estic Phone No 2 Code 5 6 _ _ _ _ _ _ LED KP Change Dom estic Phone No 3 Code 5 6 _ _ _ _ _ _ LED KP Change Dom estic Phone No 4 Code 5 6 _ _ _ _ _ _ LED KP Change Dom estic Phone No 1 4 Code 5 6 _ _ _ _ _ _ _ Text KP Call Back Code 5 7 Change Language Code 5 8 _ _ 01 EN 02 DE 03 ES 04 FR 05 IT ...

Страница 9: ...rrent for all components with a 18Ah Battery 1500mA standby 12h recharge Battery 80 in 72h PCB l00mA IUI AMAX Keypads 31mA DX2010 35mA DX3010 10mA B426 100mA DX4020G 65mA RF3227E 30mA RFRC OPT 30mA To realize EN conform Arming procedure an indication of arm disarm status must be accessible from outside the monitored area this indication can be time limited To realize EN conform Access to the Monit...

Страница 10: ...e menu prompt Select menu and enter data for specific programming items according to the display on the keypad to complete programming step by step The data value ranges in the menu programming and address programming are the same For specific options and value ranges see contents in LCD Keypad Menu Programming page 10 4 After completing input press to get back to the previous menu Complete all pr...

Страница 11: ...e programming data exceeds the display range of the keypad indicator there will be no display on the keypad Programming Data Indicators Data Zone Indicators Value 1 2 3 4 5 6 7 8 Mains 0 1 X 2 X 3 X 4 X 5 X 6 X 7 X 8 X 9 X X 10 X 11 X X 12 X X 13 X X 14 X X 15 X X Reset to Factory Default Settings The factory Default can be reset with the Resetting to Factory Default pads on the main board of the ...

Страница 12: ...ce If the DEFAULT pads are short circuited for over 10 seconds after power up the control panel will discard resetting to factory Default LCD Menu Programming For menu programming with LCD keypad see Section 4 1 1 LCD Keypad Menu Programming on page 10 Use and to move main menus submenus and secondary submenus up or down Use and to move main menus submenus and secondary submenus left or right 4 3 ...

Страница 13: ...B PANIC AL RF SUPERVISION OUTPUT SETTINGS RF PARA SETTING FORCE ARM FAULT TA FW VERSION OUTPUT SETTING SYS TAMPER INDIC DATE TIME FACTORY DEFAULT LANGUAGE VERSION KP 2 BUTTON ALARM KP TONE LOCKOUT FUNCTION SETTING FAULT CONFIG KEYPAD AREA AREA TIMING COMMON AREA CROSS TIMER ZONE SETTING TEST REPORT DURAT DUAL IP REMOTE ACCESS DOMESTIC CALLBACK INSTALLER CODE CODE PERMISSIONS KP AREA SETTING CODE L...

Страница 14: ...AL IP REMOTE ACCESS RPC IP PORT DHCP IP ADDRESS PORT No DHCP UPDATE TIME h CALLBACK SETTING DOMEST CALLBACK No DOMESTIC CALLBACK RING COUNT RING TIMES COM REPORT SETTING RECEIVER SETTING INPUT RECEIVER No PHONE IP PORT No SUBSCRIBER ID No REPORT SETTING FORMAT NETWORK ANTIREPLAY ACK WAIT TIME sec NETW POLLING min Figure 4 2 Com Report 14 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 ...

Страница 15: ... TIMER CROSS ZN TIMER sec ZONE FUNCTION ZONE IN AREA PULSE COUNT DURAT ADD DELETE ZONE INPUT ZONE No ZONE MODULE SEL ZONE STATUS REPORT UNVERF REP CROS ZN ZONE DOMESTIC ZONE PULSE COUNT ZONE LOCKOUT ZONE TAMPER ZONE TYPE FORCE ARM BYPASS SILENT AL CHIME ZONE SETTING ZONE FUNCTION ZONE FUNCTION No Figure 4 4 Zone Setting AMAX panel 4000 AMAX panel 4000 EN Configuration en 15 Bosch Sicherheitssystem...

Страница 16: ...KEYPAD AREA INPUT KEYPAD No ENTRY DELAY sec COMMON AREA COMMON AREA KP TONE LOCKOUT KEYPAD ALARM TONE KEYPAD LOCK COUNT Figure 4 5 KP Area Setting 16 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 F 01U 267 113 Quick Start Guide Bosch Sicherheitssysteme GmbH ...

Страница 17: ...AULT TA EVENT RECORD COUNT EVENT RECORD COUNT INSTALLER ACCESS INSTALLER ACCESS FORCE ARM FAULT TA SIREN SUPERVISED QUICK ARM ONLY QUICK ARM ONLY DISABLE FAULT REPO BATT CHK INTERVAL PHO LN SUPERVISED FAULT CONFIG KEYPAD FAULT SOUND AC FAULT REP TIME FUNCTION SETTING DATE TIME CHANGE DATE TIME SYSTEM SETTING Figure 4 6 System Setting AMAX panel 4000 AMAX panel 4000 EN Configuration en 17 Bosch Sic...

Страница 18: ...EP ENABLE OUTPUT AREA ZONE OUTPUT MODE OUTPUT TIME sec OUTPUT SETTINGS ENTER OUTPUT No OUTPUT EVENT TYPE OUTPUT SETTING Figure 4 7 Output Setting 18 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 F 01U 267 113 Quick Start Guide Bosch Sicherheitssysteme GmbH ...

Страница 19: ...RF JAM DETECT LEV RF PARA SETTING RF RECEIVER RF RECEIVER ENABLE RF SETTING CLEAR CONFIRM CLEAR CANCEL CLR ALL RF DEVICES RF REPEATER DIAGN REPEATER No 1 8 SIGNAL STRENGTH DEVICE STATE SIGNAL STRENGTH DEVICE STATE Figure 4 8 RF Setting COPY DATA TO KEY ADDRESS KEY PROGR ADDRESS PROGRAM ADDR VALUE COPY DATA TO PANEL Figure 4 9 Address Key Program AMAX panel 4000 AMAX panel 4000 EN Configuration en ...

Страница 20: ...055 0056 05 Network Polling Time for Receive 001 999 minutes 0057 0059 001 Telephone Number IP Address and Port for Receiver 3 0060 0076 15 Subscriber ID Number 0077 0082 000000 Transmission Format for Receiver 0 Not used 1 Contact ID 2 SIA 3 Conettix IP 0083 1 Anti replay for Receiver 0 Disabled 1 Enabled 0084 1 EN 1 Acknowledge Wait Time for Receiver 05 99 seconds 0085 086 05 Network Polling Tim...

Страница 21: ... when the port is fewer than 5 digits Example Receiver IP address 128 73 168 7 port 7700 should be made as 128 073 168 007 07700 Dual IP Settings Option Address Default 0 1 IP module 1 2 IP modules 0120 1 Notice Dual IP Settings are valid only when used in the Connetix IP format This programming option is valid for B426 and ITS DX4020 G modules ITS DX4020 G cannot be set as No 2 IP module Module A...

Страница 22: ...30 24 VDS A EN 1 24 Report Time Hour 00 23 0 23 hours Others Do not use real time report 0131 0132 99 Report Time Minute 00 59 0 59 minutes Others Do not use real time report 0133 0134 99 Report Expiry Time Address 0135 0137 Address Default 000 No time limit 001 255 1 255 minutes 0135 0137 000 VDS A EN 000 Installer Access Until Next Arming Address 0138 Address Default 0 disabled 1 enabled 0138 0 ...

Страница 23: ...ng 15 Call the control panel and allow the phone to ring no more than four times and then hang up If you call again within 45 sec the control panel answers the call on the first ring 0144 14 Remote Programming Address 0145 Address Default 0 disabled 1 enabled 0145 1 VDS A 0 Callback Telephone Number Address 0146 0161 Address Default See Telephone Programming Parameters page 26 0146 0161 15 Remote ...

Страница 24: ...Zone Tamper Bypass when DEOL Zone is Bypassed Address 0184 Address Default 0 Disable 1 Enable 0184 1 0 Incert This function is only accessible in address programming Call Back Setting Address 0196 Address Default 0 Disable 1 Enable 0196 0 Silence Warning Device On Disarm Address 0197 Address Default 0 Disable 1 Enable 0197 1 Zone Pulse Count Duration Address 0198 0200 Address Default 0 Disable 1 9...

Страница 25: ...s 0208 0209 Address Default 99 Disabled 00 98 minutes 0208 0209 60 VDS A EN 00 60 Domestic Call Telephone Number Address 1618 1682 Address Default Domestic Call Telephone Number 1 1618 1633 15 Domestic Call Telephone Number 2 1634 1649 15 Domestic Call Telephone Number 3 1650 1665 15 Domestic Call Telephone Number 4 1666 1681 15 See Telephone Programming Parameters page 26 If the default 15 is set...

Страница 26: ...nction 00 Address Default Zone Type 0210 0211 0 0 Force Arm Zone Bypass 0212 3 VDS A EN 0 2 Silent Alarm Chime Mode 0213 0 VDS A EN 0 2 Zone Pulse Count 0214 0 VDS A EN 0 Zone Lockout 0215 3 Zone Tamper DEOL 0216 1 Zone Status Report 0217 6 VDS A EN 1 5 6 7 Unverified Alarm Report Cross Zone 0218 0 VDS A EN 0 Domestic No 0219 0 Zone Function 01 Address Default Zone Type 0220 0221 0 1 Force Arm Zon...

Страница 27: ... Arm Zone Bypass 0242 3 VDS A EN 0 2 Silent Alarm Chime Mode 0243 0 VDS A EN 0 2 Zone Pulse Count 0244 0 VDS A EN 0 Zone Lockout 0245 3 Zone Tamper DEOL 0246 1 Zone Status Report 0247 6 VDS A EN 1 5 6 7 Unverified Alarm Report Cross Zone 0248 0 VDS A EN 0 Domestic No 0249 0 Zone Function 04 Address Default Zone Type 0250 0251 0 4 Force Arm Zone Bypass 0252 3 VDS A EN 0 2 Silent Alarm Chime Mode 02...

Страница 28: ...Tamper DEOL 0276 1 Zone Status Report 0277 6 VDS A EN 1 5 6 7 Unverified Alarm Report Cross Zone 0278 0 VDS A EN 0 Domestic No 0279 0 Zone Function 07 Address Default Zone Type 0280 0281 0 7 Force Arm Zone Bypass 0282 3 VDS A EN 0 2 Silent Alarm Chime Mode 0283 0 VDS A EN 0 2 Zone Pulse Count 0284 0 VDS A EN 0 Zone Lockout 0285 3 Zone Tamper DEOL 0286 1 Zone Status Report 0287 6 VDS A EN 1 5 6 7 U...

Страница 29: ...0 Zone Function 10 Address Default Zone Type 0310 0311 1 0 Force Arm Zone Bypass 0312 3 VDS A EN 0 2 Silent Alarm Chime Mode 0313 0 VDS A EN 0 2 Zone Pulse Count 0314 0 VDS A EN 0 Zone Lockout 0315 3 Zone Tamper DEOL 0316 1 Zone Status Report 0317 6 VDS A EN 1 5 6 7 Unverified Alarm Report Cross Zone 0318 0 VDS A EN 0 Domestic No 0319 0 Zone Function 11 Address Default Zone Type 0320 0321 1 1 Forc...

Страница 30: ...343 0 VDS A EN 0 2 Zone Pulse Count 0344 0 VDS A EN 0 Zone Lockout 0345 3 Zone Tamper DEOL 0346 1 Zone Status Report 0347 6 VDS A EN 1 5 6 7 Unverified Alarm Report Cross Zone 0348 0 VDS A EN 0 Domestic No 0349 0 Zone Function 14 Address Default Zone Type 0350 0351 1 4 Force Arm Zone Bypass 0352 3 VDS A EN 0 2 Silent Alarm Chime Mode 0353 0 VDS A EN 0 2 Zone Pulse Count 0354 0 VDS A EN 0 Zone Lock...

Страница 31: ...Zone Function Option Zone Function Option Description Zone Type 00 Zone Not Used 01 Instant 02 Interior Instant 03 Delay 04 Interior Delay 05 Follower 06 Interior Follower 07 24 Hour 08 Key Switch Toggle 09 Key Switch on off 10 24 Hour Panic 11 24 Hour Fire 12 24 Hour Fire With Verification 13 Tamper 14 Bolt Contact 15 External Fault 16 Delay Exit 17 Interior Delay Exit 18 Technical Alarm 19 Reset...

Страница 32: ... Required 1 Receiver 1 2 Receiver 2 3 Receiver 3 4 Receiver 4 5 Receiver 1 2 3 and 4 6 Receiver 1 2 3 and 4 for backup 7 Receiver 1 2 for backup and Receiver 3 4 for backup Unverified Alarm Report Cross Zone 0 Disabled 1 Unverified Alarm Report 2 Cross Zone 3 All Domestic Call Follow Alarm report Option s Logic Range 0 7 0 No Reports Allowed 1 Report to Destination 1 2 Report to Destination 2 3 Re...

Страница 33: ...o Destination 1 2 3 4 6 Report to Destination 1 2 3 4 backup 7 Report to Destination 1 2 Backup and 3 4 backup AMAX panel 4000 AMAX panel 4000 EN Configuration en 33 Bosch Sicherheitssysteme GmbH Quick Start Guide 2013 07 03 F 01U 267 113 ...

Страница 34: ...ition 2 9 9 Follow Partition 2 10 10 Follow Partition 2 11 11 Follow Partition 2 12 12 Follow Partition 2 13 13 Follow Partition 2 14 14 Follow Partition 2 15 15 Follow Partition 2 16 Notice In case of common Area the Area 1 will be the common Area When there is only 1 Area in the system the address 0370 can only be programmed as 1 34 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 ...

Страница 35: ...ed 1 16 Area 1 16 Value Range 0 15 See Section Zone Functions page 26 0 On board zone 1 Keypad zone 2 DX2010 zone 3 RF Device 15 not used Notice Zones may be indicated on keypads with a number that are different from zone number used for programming and hardware input Example In a one area system keypad zone number 17 should be indicated as Zone number 16 e g visible on 16 zone LED keypad After di...

Страница 36: ... 0739 00 836 1 900 15 32 0740 0741 00 837 1 901 15 Value Range 00 zone not used 1 16 Area 1 16 Value Range 0 15 See Section Zone Functions page 26 0 On Board zone 1 Keypad Zone 2 DX2010 Zone 3 RF Device 15 not used Zones 17 to 32 are dedicated to Keypad 1 to 32 Zone 17 Keypad 1 Zone 32 Keypad 32 Zones 17 to 24 are dedicated to DX2010 address 103 ports 1 to 8 also see Table DX2010 modules Zones 25 ...

Страница 37: ... 0850 1 0913 15 46 0768 0769 00 0851 1 0915 15 47 0770 0771 00 0852 1 0916 15 48 0772 0773 00 0853 1 0917 15 49 0774 0775 00 0854 1 0918 15 50 0776 0777 00 0855 1 0919 15 51 0778 0779 00 0856 1 0920 15 52 0780 0781 00 0857 1 0921 15 53 0782 0783 00 0858 1 0922 15 54 0784 0785 00 0859 1 0923 15 55 0786 0787 00 0860 1 0924 15 56 0788 0789 00 0861 1 0925 15 57 0790 0791 00 0862 1 0926 15 58 0792 0793...

Страница 38: ...X2010 module 6 zones 57 64 108 See also Zone Programming page 26 Output Programming On board Output Programming Option Address Default Keypad Alarm Tone 0 Disabled 1 Enabled 0503 1 Siren Running Time 00 99 0 99 minutes 0508 0509 00 See The Value Ranges of Output Programming Options page 39 Output 1 Output Event Type 0510 0511 05 VDS A EN 5 Output Area Zone 0512 0513 00 Output Mode 0514 0 VDS A EN ...

Страница 39: ...s well as the relationship between output event type and Output in area see The Value Ranges of Output Programming Options page 39 The Value Ranges of Output Programming Options Output Event Type Description Output Area Zone Output Event 0 Not Used No 1 System Disarmed 0 All Areas 1 16 Areas 1 16 2 System Armed 3 System Alarm 0 Any Area 1 16 Areas 1 16 4 System Alarm audile and silent 5 External A...

Страница 40: ...hnical Alarm 28 Bypassed Zone 29 Ready to Arm 0 All Areas 1 16 Areas 1 16 30 Walktest Output Mode 0 Continuous output 1 Pulse 2 Inverted Output Time 000 999 0 999 seconds 1 Output Timer is fix 1 sec DX3010 Output Programming This section is optional programming Module Address DX3010 module 1 Output 5 12 150 DX3010 module 2 Output 13 20 151 Table 4 2 DX3010 Address Settings DX3010 1 Output Programm...

Страница 41: ... Default Output Event Type 0566 0567 00 Output Area Zone 0568 0569 00 Output Mode 0570 0 Output Time 0571 0573 000 Output 9 Address Default Output Event Type 0574 0575 00 Output Area Zone 0576 0577 00 Output Mode 0578 0 Output Time 0579 0581 000 Output 10 Address Default Output Event Type 0582 0583 00 Output Area Zone 0584 0585 00 Output Mode 0586 0 Output Time 0587 0589 000 Output 11 Address Defa...

Страница 42: ...s Default Output Event Type 0614 0615 00 Output Area Zone 0616 0617 00 Output Mode 0618 0 Output Time 0619 0621 000 Output 15 Address Default Output Event Type 0622 0623 00 Output Area Zone 0624 0625 00 Output Mode 0626 0 Output Time 0627 0629 000 Output 16 Address Default Output Event Type 0630 0631 00 Output Area Zone 0632 0633 00 Output Mode 0634 0 Output Time 0635 0637 000 Output 17 Address De...

Страница 43: ...Zone 0664 0665 00 Output Mode 0666 0 Output Time 0667 0669 000 See also Output Programming page 39 Access Codes Code Length Option Address Default Code Length 4 6 4 6 digits 1003 4 The access code includes installer Code and User codes If the code is set as 15 then code is not used The code length is the same for all Access Codes Installer Code Option Address Default Installer Code 1004 1 1005 2 1...

Страница 44: ...36 04 1037 1038 1039 1040 1045 05 1046 1047 1048 1049 1054 06 1055 1056 1057 1058 1063 07 1064 1065 1066 1067 1072 08 1073 1074 1075 1076 1081 09 1082 1083 1084 1085 1090 10 1091 1092 1093 1094 1099 11 1100 1101 1102 1103 1108 12 1109 1110 1111 1112 1117 13 1118 1119 1120 1121 1126 14 1127 1128 1129 1130 1135 15 1136 1137 1138 1139 1144 16 1145 1146 1147 1148 1153 17 1154 1155 1156 1157 1162 18 11...

Страница 45: ...1355 1360 40 1361 1362 1363 1364 1369 41 1370 1371 1372 1373 1378 42 1379 1380 1381 1382 1387 43 1388 1389 1390 1391 1396 44 1397 1398 1399 1400 1405 45 1406 1407 1408 1409 1414 46 1415 1416 1417 1418 1423 47 1424 1425 1426 1427 1432 48 1433 1434 1435 1436 1441 49 1442 1443 1444 1445 1450 50 1451 1452 1453 1454 1459 51 1460 1461 1462 1463 1468 52 1469 1470 1471 1472 1477 53 1478 1479 1480 1481 148...

Страница 46: ...62 1559 1560 1561 1562 1567 63 1568 1569 1570 1571 1576 64 1577 1578 1579 1580 1585 If the code is set as 15 then code is not used For Code Description refer to User Code Commands page 8 46 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 F 01U 267 113 Quick Start Guide Bosch Sicherheitssysteme GmbH ...

Страница 47: ...X X 10 X X 11 X X X 12 X X 13 X X X 14 X X X 15 X X X X 16 X 17 X 18 X X 19 X 20 X X 21 X X 22 X X X 23 X 24 X X 25 X X 26 X X X 27 X X 28 X X X 29 X X X 30 X X X X 31 X AMAX panel 4000 AMAX panel 4000 EN Configuration en 47 Bosch Sicherheitssysteme GmbH Quick Start Guide 2013 07 03 F 01U 267 113 ...

Страница 48: ...49 X 50 X X 51 X X 52 X X X 53 X 54 X X 55 X X 56 X X X 57 X X 58 X X X 59 X X X 60 X X X X 61 X X X X X X X X 62 X X X X X X X X 63 X X X X X X X X 64 X X X X X X X X X X X X 65 X X X X X X X X 48 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 F 01U 267 113 Quick Start Guide Bosch Sicherheitssysteme GmbH ...

Страница 49: ...Exit Delay Area Address Default 1 0403 0405 045 2 0409 0411 045 3 0415 0417 045 4 0421 0423 045 5 0427 0429 045 6 0433 0435 045 7 0439 0441 045 8 0445 0447 045 9 0451 0453 045 10 0457 0459 045 11 0463 0465 045 12 0469 0471 045 13 0475 0477 045 14 0481 0483 045 15 0487 0489 045 16 0493 0495 045 000 999 seconds 4 4 5 AMAX panel 4000 AMAX panel 4000 EN Configuration en 49 Bosch Sicherheitssysteme Gmb...

Страница 50: ...30 7 0442 0444 030 8 0448 0450 030 9 0454 0456 030 10 0460 0462 030 11 0466 0468 030 12 0472 0474 030 13 0478 0480 030 14 0484 0486 030 15 0490 0492 030 16 0496 0498 030 000 999 seconds EN 045 seconds 50 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 F 01U 267 113 Quick Start Guide Bosch Sicherheitssysteme GmbH ...

Страница 51: ... Keypad Area Settings 00 Master Keypad 00 16 Area 99 not used Notice The system supports up to 16 master keypads When the master keypad is not switched to the corresponding Area no Arming disarming bypass and alarm reset operations can be performed on the master keypad Only by switching the master keypad to the corresponding Area operations can be performed to the Area AMAX panel 4000 AMAX panel 4...

Страница 52: ...1 VDS A EN 1 Printer Functionality Address 0940 Address Default 0 disabled 1 Enable 0940 0 RF Receiver Address 0941 Address Default 0 disabled 1 Enable 0941 0 RF supervision Address 0942 Address Default 0 disable 1 1h 2 2h 3 4h 4 12 h 5 24h 6 2 5h 0942 4 RF Jam Detect Level Address 0943 Address Default 0 15 0 most sensitive 0943 12 RF Device Low Level Battery Resound Address 0944 Address Default 0...

Страница 53: ...lt 0 disable 1 Enable 0945 1 RF Keyfob Panic Option Address 0946 Address Default 0 No alarm 1 Silent alarm 2 Non silent alarm 0946 0 AMAX panel 4000 AMAX panel 4000 EN Configuration en 53 Bosch Sicherheitssysteme GmbH Quick Start Guide 2013 07 03 F 01U 267 113 ...

Страница 54: ...1990 1998 15 52 2210 2218 15 9 1780 1788 15 31 2000 2008 15 53 2220 2228 15 10 1790 1798 15 32 2010 2018 15 54 2230 2238 15 11 1800 1808 15 33 2020 2028 15 55 2240 2248 15 12 1810 1818 15 34 2030 2038 15 56 2250 2258 15 13 1820 1828 15 35 2040 2048 15 57 2260 2268 15 14 1830 1838 15 36 2050 2058 15 58 2270 2278 15 15 1840 1848 15 37 2060 2068 15 59 2280 2288 15 16 1850 1858 15 38 2070 2078 15 60 2...

Страница 55: ...38 15 21 1900 1908 15 43 2120 2128 15 22 1910 1918 15 44 2130 2138 15 Each RFID Device has nine digits Each digit range is 0 to 9 The default value is 15 not in use AMAX panel 4000 AMAX panel 4000 EN Configuration en 55 Bosch Sicherheitssysteme GmbH Quick Start Guide 2013 07 03 F 01U 267 113 ...

Страница 56: ...t 1 2340 2348 15 2 2350 2358 15 3 2360 2368 15 4 2370 2378 15 5 2380 2388 15 6 2390 2398 15 7 2400 2408 15 8 2410 2418 15 56 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 F 01U 267 113 Quick Start Guide Bosch Sicherheitssysteme GmbH ...

Страница 57: ...2878 15 2560 2568 47 2880 2888 16 2570 2578 48 2890 2898 17 2580 2588 49 2900 2908 18 2590 2598 50 2910 2918 19 2600 2608 51 2920 2928 20 2610 2618 52 2930 2938 21 2620 2628 53 2940 2948 22 2630 2638 54 2950 2958 23 2640 2648 55 2960 2968 24 2650 2658 56 2970 2978 25 2660 2668 57 2980 2988 26 2670 2678 58 2990 2998 27 2680 2688 59 3000 3008 28 2690 2698 60 3010 3018 29 2700 2708 61 3020 3028 30 27...

Страница 58: ...2 3530 3538 81 3220 3228 113 3540 3548 82 3230 3238 114 3550 3558 83 3240 3248 115 3560 3568 84 3250 3258 116 3570 3578 85 3260 3268 117 3580 3588 86 3270 3278 118 3590 3598 87 3280 3288 119 3600 3608 88 3290 3298 120 3610 3619 89 3300 3308 121 3620 3628 90 3310 3318 122 3630 3638 91 3320 3328 123 3640 3648 92 3330 3338 124 3650 3658 93 3340 3348 125 3660 3668 94 3350 3358 126 3670 3678 95 3360 33...

Страница 59: ...2 addresses Example A 4 1 A Address 3736 4 Address 3737 1 One character needs 2 values to enter into 2 addresses Determine these values using the matrix of table below Every character in this table has a row index and also a column index Row Index is the first column index is the second value for each character Example o 6 15 k 6 11 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 3 0 1 2 3 4 5 6 7 8 9 4 A...

Страница 60: ...3 0 4 3844 3879 0 5 3880 3915 0 6 3916 3951 0 7 3952 3987 0 8 3988 4023 0 9 4024 4059 0 10 4060 4095 0 11 4096 4131 0 12 4132 4167 0 13 4168 4203 0 14 4204 4239 0 15 4240 4275 0 16 4276 4311 0 17 4312 4347 0 18 4348 4383 0 19 4384 4419 0 20 4420 4455 0 21 4456 4491 0 22 4492 4527 0 23 4528 4563 0 24 4564 4599 0 25 4600 4635 0 60 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 F 01U ...

Страница 61: ...39 5104 5139 0 40 5140 5175 0 41 5176 5211 0 42 5212 5247 0 43 5248 5283 0 44 5284 5319 0 45 5320 5355 0 46 5356 5391 0 47 5392 5427 0 48 5428 5463 0 49 5464 5499 0 50 5500 5535 0 51 5536 5571 0 52 5572 5607 0 53 5608 5643 0 54 5644 5679 0 55 5680 5715 0 56 5716 5751 0 57 5752 5787 0 58 5788 5823 0 AMAX panel 4000 AMAX panel 4000 EN Configuration en 61 Bosch Sicherheitssysteme GmbH Quick Start Gui...

Страница 62: ... 64 6004 6039 0 Table 4 7 Assign Zone Names Zone Name may have up to 18 characters Each character of the zone name uses 2 addresses Example A 4 1 A Address 3736 4 Address 3737 1 62 en Configuration AMAX panel 4000 AMAX panel 4000 EN 2013 07 03 F 01U 267 113 Quick Start Guide Bosch Sicherheitssysteme GmbH ...

Страница 63: ... and time fault displayed in programming although date and time are not set Backup battery is not connected or the voltage of the battery connected is lower than 12V Alarm siren is not connected The telephone number is incorrectly set Telephone network is not connected The tamper switch is not connected External module should be used for programming but it not connected actually Set date and time ...

Страница 64: ...programming mode after power up The system is in alarm state The system is in arming state Reset the alarm Disarm the system and keep it in the disarming status The red LED on the main board goes off Abnormal AC power and backup battery The main board fails Check AC power and backup battery Replace the main board The system does not dial when the alarm presents Relevant receiver parameters are not...

Страница 65: ...one silent alarm The control panel cannot send any reports programmed to send reports to receiver The transmission format of the receiver is programmed to 0 not used Program the transmission format of the receiver to 1 or 3 A LINK cannot be connected with ITS DX4020 G The parameters of ITS DX4020 G are not properly set Recommend to set the parameter ACK TIMEOUT of ITS DX4020 G to the maximum 600 a...

Страница 66: ...ot reduce point capacity Outputs PO Programmable Onboard PO 1 supervised output max 500mA PO 2 supervised output max 500mA PO 3 12V max 750mA PO 4 12V max 750mA Onboard Watchdog PO 5 max 100mA Number of Zones 64 Users 64 Key Fob Users DSRF 24 Radion 128 Events 254 history events stamped with time and date 254 EN history events stamped with time and date 254 dialer history events stamped with time ...

Страница 67: ... Batt 80 in 24h 480mA Aux 1 12V GND Output Nominal Output Voltage under AC line input 13 8 VDC 3 5 Output Voltage Range under AC line input 13 11 VDC to 14 2 VDC 900mA maximum Vpp max 675mV Aux 1 12V GND Output Nominal Output Voltage under AC line input 13 8 VDC 3 5 Output Voltage Range under AC line input 13 11 VDC to 14 2 VDC 900mA maximum Vpp max 675mV Option Bus 1 Nominal Output Voltage under ...

Страница 68: ... max 14 devices max 8 KPs EN type EN B IK 06 IP 30 Certification EN 50131 3 Grade 3 Environmental Class II IUI AMAX3 LED16 16 Zone LED Keypad Relative Humidity 10 95 Operating Temperature 10 C 55 C Input Voltage range 10 8VDC 13 8VDC Current Consumption standby 31mA maximum 60mA Cable requirements four wire AWG18 or AWG22 maximum length 200m Panel to last KP maximum BUS 1 length 700m max 14 device...

Страница 69: ...l to last KP maximum BUS 1 length 700m max 14 devices 8 KPs maximum BUS 2 length 700m max 14 devices 8 KPs EN type EN B IK 06 IP 30 Certification EN 50131 3 Grade 3 Environmental Class II AMAX panel 4000 AMAX panel 4000 EN Technical Data en 69 Bosch Sicherheitssysteme GmbH Quick Start Guide 2013 07 03 F 01U 267 113 ...

Страница 70: ......

Страница 71: ......

Страница 72: ...Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany www boschsecurity com Bosch Sicherheitssysteme GmbH 2013 ...