GAS CONNECTIONS

          

NOTE:  The  125  HX  is  supplied  with  a  gas  pressure
regulator  that  must  be  installed  on  the  heater  before
attaching the gas supply line. See fig. 5. Failure to install
the  gas regulator as shown in figure 5 will be a violation
of CSA certification of the unit.  The regulator supplied
with the heater is preset for the gas shown on the rating
plate  to  the  correct  pressure.  It  is  an  appliance  level
regulator designed for (low inlet) pressure (less than 1/
2 Psig or 15” W.C.)
DO  NOT  connect  to  an  unregulated  or  high  pressure
propane line or to a high pressure commercial natural
gas line.

GAS LINE SIZING

-It is strongly recommended that the Natural Gas pipe
be Black Iron pipe the entire distance from the outside
meter to the inlet of the 125 HX regulator. 1/2” Black Iron
pipe up to 10 feet, 3/4” Black Iron pipe up to 40 feet and
1” Black Iron pipe up to 150 feet distances. Flex line tubing
is NOT recommended, but if used then oversize it.
-It  is  strongly  recommended  that  the  LP  Gas  pipe  be
semi-rigid copper or Black Iron pipe from the outside
regulator to the inlet of the 125 HX regulator. For semi-
rigid copper piping: 5/8” up to 20 feet and 3/4” up to 60
feet distances. For Black Iron piping: 1/2” up to 45 feet
and 3/4” up to 160 feet distances. Flex line tubing is NOT
recommended, but if used then oversize it.
THESE FIGURES ARE FOR 125 HX SUPPLY ONLY, ALL
OTHER APPLIANCES IN THE BUILDING WILL NEED TO
BE INCLUDED IN THE PIPE SIZING.

National Fuel Gas Code requires that a sediment trap (drip
leg) be installed on gas appliances not so equipped. The
drip  leg  must  be  accessible  and  not  subject  to  freezing
conditions. Install in accordance with the recommendations
of the serving gas supplier.

  WARNING:

  The  heater  must  be  disconnected  from

the gas supply piping system during any pressure testing of
that system at test pressures in excess of 0.5 psig.
The water heater must be isolated from the gas supply piping
system  by  closing  the  manual  shutoff  valve  during  any
pressure  testing  of  the  gas  supply  piping  system  at  test
pressures equal to or more than 0.5 psig.
The water heater, including the pressure regulator provided
with  it,  must  not  be  operated  at  gas  supply  pressures  in
excess of 0.5 psig. If overpressure has occurred, such as
through improper testing of the gas lines or malfunction of
the  supply  system,  the  gas  valve  and  regulator  must  be
checked  for  safe  operation.  Make  sure  that  the  regulator
vent is protected against blockage.
When your connections are made, check for gas leaks at
all joints (not just the ones you made). Apply some soapy
water to all gas fittings and gas valve. 

Soap bubbles are a

sign of a leak.
NOTE:

 Do not apply soap solution to the pilot or pilot orifice

area. If you have a leak, shut off the gas. After verifying that
required gaskets are in place, tighten appropriate fittings to
stop  leak.  Turn  the  gas  on  and  check  again  with  a  soapy
solution. 

Never test for gas leaks using a match or flame

.

Fig. 5 - Installation of Gas Pressure Regulator

The pressure regulator provided with the heater is adjusted
to deliver the proper gas pressure (as indicated on the rating
plate and in the manual for altitude up to 2000 feet (660
meters) above sea level. On appliances being installed above
2000 ft (660 meters) elevation, the inlet gas pressure should
be set at installation to the value shown below.

draft diverter outlet must be connected to an unobstructed
vent of the same size, or larger.

In Canada, CAN/CGA-B149 Installation Code for detailed
requirements
In  U.S.A.,  ANSI  Z223.1  -  NFPA  54,  National  Fuel  Gas
Code for detailed requirements.

The vent connection for the 125 HX is 5 inches.  However,
for installations at high altitude (over 2000 feet above sea
level)  a  six  inch  vent  is  required.  A  5"  by  6"  vent  adaptor
must be affixed to the flue collar of the 125 HX with at least
two screws. See fig. 4.

WARNING

: Failure TO INCREASE THE VENT SIZE

TO SIX INCHES AND/or assure that the manifold pressure
is set to proper value listed for applications at high altitudes
will cause unsafe venting, asphyxiation, and will void CSA
Certification.

Altitude

Natural Gas

Liquid Propane

inches W.C:

inches W.C:

0' - 2.000 ft

5.7"

10.5"

2.000 ft - 4.500 ft

4.6"

8.4"

Above 4.500 ft consult your local gas provider.

MAXIMUM INLET GAS FLOW PRESSURE SETTING

Fig. 4 - Vent Adaptor for High Altitude Installations

5” X 6” ADAPTOR

USED ON HIGH ALTITUDE

NOTE:  The  gas  pressures  specified  below  refer  to
pressures taken at the pressure tap on the gas inlet pipe
just  above  the  regulator  (See  Fig  5)

.   

These  readings

should be taken while the heater is operating at full input
—  i.e.  maximum  water  flow  with  the  temperature  dial
selector turned all the way clockwise.

GAS INLET PIPE

PRESSURE TAP

PRESSURE REGULATOR
(with directional arrow on
reverse side pointing
upward)

      

PLASTIC VENT CAP

Содержание 125HX

Страница 1: ...sing property damage personal injury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable combustible or corrosive vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follo...

Страница 2: ...f the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable combustible or corrosive vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use ...

Страница 3: ... will not exceed the heating capacity of the heater On Off Switch to activate system Red LED indicator flashes with low water pressure Green LED indicator main burner operation BOSCH is constantly improving our products therefore specifications are subject to change without prior notice 125 HX LP and 125 HX NG Specifications Gas Input max 117 000 Btu hr min 28 000 Btu hr Water Connection Thread fi...

Страница 4: ...INIMUM INSTALLATION CLEARANCES FROM COMBUSTIBLE AND NON COMBUSTIBLE MATERIALS FOR ALCOVE OR CLOSET INSTALLATIONS FRONT VIEW SIDE VIEW MODEL 125HX MODEL 125 HX TOP A 12 FRONT B 4 BACK 0 SIDES 4 FLOOR C 12 VENT DIAMETER 5 ...

Страница 5: ...control which has been underwater PROPER LOCATION FOR INSTALLING YOUR HEATER Carefully select the location of your new heater For your safety and for proper heater operation you must provide an abundant supply of combustion air and a proper venting Fig 1 Water heater drain plug The heater may still operate even when improperly vented It will however be less efficient and could eventually damage th...

Страница 6: ...ng 2000 Btu hr if all air is taken from the outside by horizontal ducts 4000 Btu hr if all air is taken from the outside by direct openings or vertical ducts Or the confined space must be provided with one permanent opening or duct that is within 12 inches of the ceiling of the enclosure This opening must have a minimum free area of one square inch per 3000 Btu hr if all air is taken from the outs...

Страница 7: ...s stamped with a number 79 for LPG and 120 for Natural Gas Fig 2 Mounting the Heater WALL STUDS 1 X 4 SPACE BOARD SUPPORT BOARD 13 Fig 3 Incandescent Particle Tray Illustration The incandescent particle tray shipped loose in the carton with the water heater must be attached at the bottom of the water heater front cover at the time of installation Use the screws provided See figure 3 SCREWS INCANDE...

Страница 8: ...ter heater to a masonry chimney the following connector guidelines must be followed for safe and proper operation An approved gas vent connector must be attached to the top of the water heater and rise vertically at least 12 before entering into an approved gas vent connector elbow Any gas vent section that is greater than 45 degrees from the vertical is considered horizontal If a horizontal vent ...

Страница 9: ...the gas lines or malfunction of the supply system the gas valve and regulator must be checked for safe operation Make sure that the regulator vent is protected against blockage When your connections are made check for gas leaks at all joints not just the ones you made Apply some soapy water to all gas fittings and gas valve Soap bubbles are a sign of a leak NOTE Do not apply soap solution to the p...

Страница 10: ...l length of piping and then adding 5 ft for every elbow or T to the actual length Use the charts below to determine the pipe diameter necessary to accommodate the BTU demand of the unit If there are more gas drawing appliances on the line size according to the maximum amount of BTU demand Follow boxed numbers for piping just one 125 HX example 3 4 B I Natural Gas pipe for 30 ft will handle 152 000...

Страница 11: ...runs as short as possible When facing the heater the cold water inlet will be on the right and the hot water outlet on the left Although water piping throughout the building may be other than copper copper or galvanized piping should be used when connecting to the heaters male NPT flex connectors follow local codes if more stringent Plastics or other PEX type plumbing line materials are not suitab...

Страница 12: ...icator light is flashing this is a warning that the water pressure is not enough to ignite the main burner 6 Turn the hot water faucet on to the minimum flow rate required to activate the heater The automatic ignition system first ignites the safety pilot burner which then ignites the main burner in about 4 seconds 7 The green LED indicator is on when the main burner is on 8 The pilot flame will e...

Страница 13: ...have yellow flames while others have good flames it is likely that dust lint or spider webs have partially clogged the burner venturis To clean the burners contact a gas service person Mineral Scale Build up The 125 HX heater when operated at lower temperature settings does not accumulate mineral build up If however the heater is used at the higher temperature settings and the water has a high min...

Страница 14: ...and component parts must be totally free of dirt In hard water areas mineral deposits can eventually 3 5 years in hard water areas corrode the water valve parts to a point where they will need replacing Any sign of moisture or corrosion at the joint of the water valve and the gas valve is a sign that the water valve components need to be serviced immediately 7 Poor circuit connections at the ECO o...

Страница 15: ...is mixing with the hot water between the 125 HX and the outlet Compare water temperature at outlet of the 125 HX hold the 125 HX outlet pipe with your hand and at the tap If these two are very different check for mixing valve or plumbing crossover see NO SPARK AT THE PILOT paragraph 2 5 Parts in water valve are dirty or damaged which will prevent the gas valve from being fully opened Water valve m...

Страница 16: ... reduce such hot water temperature in the event of any temperature instability with the use of a temperature balance shower valve refer to shower valve manufactures instructions for internal adjustment setting Adjustments should be made to the hottest setting in the shower valve Additionally the temperature control of the heater can be adjusted to produce a more comfortable hot water temperature S...

Страница 17: ...ner manifold gas pressure test nipple 4 Main gas burner 5 Pilot gas tubing 6 LED failure indicator 7 on off switch 8 LED operation indicator 9 Water valve 10 Temperature adjustment selector 11 Gas inlet gas pressure test nipple 12 Hose 3 1 4 10 11 2 9 8 6 7 5 12 6 720 606 804 10 1AL ...

Страница 18: ...18 6 720 606 804 Fig 15 INTERIOR COMPONENTS DIAGRAM AND PARTS LIST ...

Страница 19: ...7 Pilot electrovalve 8 708 501 249 18 Burner electrovalve 8 708 501 250 19 O ring 8 700 205 023 20 Hydro generator 8 707 406 043 21 Cold water pipe 8 700 705 947 22 Outlet flex hose 8 700 703 139 23 Washer 8 700 103 658 24 Water valve 8 707 002 649 25 Water valve cover 8 705 500 101 26 Diaphragm 8 700 503 053 27 Water inlet filter 8 700 507 001 28 Water valve selector screw 8 708 500 289 29 Volume...

Страница 20: ...20 6 720 606 804 Fig 16 Flow chart of 125 HX ...

Страница 21: ... in normal use and service within the applicable periods specified below in accordance with the terms of this warranty The CEC replacement will be warranted for the unexpired portion of the original warranty This warranty will be valid only for water heaters in possession of the original purchaser as recorded on the warranty card The Heat Exchanger If the heat exchanger fails within twelve 12 year...

Страница 22: ...22 6 720 606 804 ...

Страница 23: ...23 6 720 606 804 ...

Страница 24: ...ield Vermont 05673 Phone 800 642 3111 Fax 802 496 6924 www controlledenergy com tech techsupport controlledenergy com 3 1 e g a p e e s E L B A T E C N A N E T N I A M R A E Y Y R E V E S R A E Y 2 Y R E V E S R A E Y 5 3 Y R E V E E V L A V R E T A W E T A C I R B U L E V L A V R E T A W D L I U B E R N E E R C S R E T L I F R E T A W T C E P S N I Y L B M E S S A T O L I P T C E P S N I Y L B M ...

Отзывы: