background image

3

6 720 606 804

Principle of Operation:

When a hot water faucet is opened, the water flow through
the heater causes the gas valve to open. At the same time
the hydro-generator activates the electronics which sends
a spark to the pilot. The flame sensor confirms the pilot has
been lighted and allows the first two burners to come on.
The flame sensor confirms correct activation and all burners
come on. The pilot goes off. The heat exchanger coils absorb
the heat generated by the burners and transfer heat to the
water. When the hot water faucet is shut off, the gas valve
automatically closes and the burners turn off. Your hot water
faucet is an ignition key to activate the water heater, giving
you control over your hot water energy use. Every time you
turn off your hot water faucet, the energy consumption of
your hot water returns to zero.

FEATURES

- Electronic Pilot Ignition driven by hydro-generator

- High Quality Materials for Long Working Life.

- Copper heating coils for  endless supply of hot water.

- Burner output proportional to hot water flow demand for

maximum energy efficiency.

- Safety flame sensor at pilot burner.

- Automatic overheating protection shut-off sensor.

- Flue gas safety device.

- Stainless steel burners with stabilized blue flame.

- Built-in corrosion resistant draft diverter.

- Compact space saver: mounts on a wall with two hooks.

- Easily removable one-piece cover.

- Easy one person installation.

- Adjustable water flow restrictor to ensure that water flow

demand will not exceed the heating capacity of the heater.

- On/Off Switch to activate system.

- Red LED indicator flashes with low water pressure.

- Green LED indicator main burner operation.

BOSCH  is  constantly  improving  our  products,  therefore
specifications are subject to change without prior notice.

125 HX LP and 125 HX NG Specifications

Gas Input max.: 117,000 Btu/hr

min.: 28,000 Btu/hr

Water Connection 

½

” Thread  fitting NPT

H x W x D 29 3/4” x 18 1/4” x 8 3/4"

Vent 5”

Gas Connection 1/2” NPT thread

Min. Water Pressure 18 Psi at 4 GPM

Max. Water Pressure 150 Psi

Shipping Weight 43 LB

Net Weight 40 LB

1.8 GPM at 90° rise

3.7 GPM at 45° rise

Min. Water Flow 1/2 gal/min

LP GAS Supply Pressure
(before 125 HX regulator)

min. 11” W.C.
max.

14” W.C.*

Required LP GAS Pressure at inlet
tap while 125 HX is operating:

10.5” W.C.

LP GAS Burner Manifold pressure while 125 HX is
operating at maximum input:

9.0” W.C.

Natural Gas Supply Pressure

min.: 7” W.C.

(before 125 HX regulator)

max.: 14” W.C.*

Required Natural Gas Pressure at inlet
tap while 125 HX is operating:

5.7” W.C.

Natural Gas Burner Manifold Pressure while 125 HX is
operating at maximum input:

4.2” W.C.

* Inlet gas pressure before 125 HX regulator must not exceed
this  value.  Pressure  may  need  to  be  adjusted  for  high
altitudes, see page 9.

UNPACKING THE 125 HX HEATER

This heater is packed securely. The box includes one water connection fitting, a control knob with collar, a gas pressure
regulator,  a  pressure  relief  valve,  an  incandescent  particle  tray,  two  hooks  for  hanging  the  heater,  this  manual  and  a
warranty registration card. 

Do not lose this manual, as there is a charge for replacement.

 Please complete and return

the enclosed warranty registration card.

Содержание 125HX

Страница 1: ...sing property damage personal injury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable combustible or corrosive vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follo...

Страница 2: ...f the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable combustible or corrosive vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use ...

Страница 3: ... will not exceed the heating capacity of the heater On Off Switch to activate system Red LED indicator flashes with low water pressure Green LED indicator main burner operation BOSCH is constantly improving our products therefore specifications are subject to change without prior notice 125 HX LP and 125 HX NG Specifications Gas Input max 117 000 Btu hr min 28 000 Btu hr Water Connection Thread fi...

Страница 4: ...INIMUM INSTALLATION CLEARANCES FROM COMBUSTIBLE AND NON COMBUSTIBLE MATERIALS FOR ALCOVE OR CLOSET INSTALLATIONS FRONT VIEW SIDE VIEW MODEL 125HX MODEL 125 HX TOP A 12 FRONT B 4 BACK 0 SIDES 4 FLOOR C 12 VENT DIAMETER 5 ...

Страница 5: ...control which has been underwater PROPER LOCATION FOR INSTALLING YOUR HEATER Carefully select the location of your new heater For your safety and for proper heater operation you must provide an abundant supply of combustion air and a proper venting Fig 1 Water heater drain plug The heater may still operate even when improperly vented It will however be less efficient and could eventually damage th...

Страница 6: ...ng 2000 Btu hr if all air is taken from the outside by horizontal ducts 4000 Btu hr if all air is taken from the outside by direct openings or vertical ducts Or the confined space must be provided with one permanent opening or duct that is within 12 inches of the ceiling of the enclosure This opening must have a minimum free area of one square inch per 3000 Btu hr if all air is taken from the outs...

Страница 7: ...s stamped with a number 79 for LPG and 120 for Natural Gas Fig 2 Mounting the Heater WALL STUDS 1 X 4 SPACE BOARD SUPPORT BOARD 13 Fig 3 Incandescent Particle Tray Illustration The incandescent particle tray shipped loose in the carton with the water heater must be attached at the bottom of the water heater front cover at the time of installation Use the screws provided See figure 3 SCREWS INCANDE...

Страница 8: ...ter heater to a masonry chimney the following connector guidelines must be followed for safe and proper operation An approved gas vent connector must be attached to the top of the water heater and rise vertically at least 12 before entering into an approved gas vent connector elbow Any gas vent section that is greater than 45 degrees from the vertical is considered horizontal If a horizontal vent ...

Страница 9: ...the gas lines or malfunction of the supply system the gas valve and regulator must be checked for safe operation Make sure that the regulator vent is protected against blockage When your connections are made check for gas leaks at all joints not just the ones you made Apply some soapy water to all gas fittings and gas valve Soap bubbles are a sign of a leak NOTE Do not apply soap solution to the p...

Страница 10: ...l length of piping and then adding 5 ft for every elbow or T to the actual length Use the charts below to determine the pipe diameter necessary to accommodate the BTU demand of the unit If there are more gas drawing appliances on the line size according to the maximum amount of BTU demand Follow boxed numbers for piping just one 125 HX example 3 4 B I Natural Gas pipe for 30 ft will handle 152 000...

Страница 11: ...runs as short as possible When facing the heater the cold water inlet will be on the right and the hot water outlet on the left Although water piping throughout the building may be other than copper copper or galvanized piping should be used when connecting to the heaters male NPT flex connectors follow local codes if more stringent Plastics or other PEX type plumbing line materials are not suitab...

Страница 12: ...icator light is flashing this is a warning that the water pressure is not enough to ignite the main burner 6 Turn the hot water faucet on to the minimum flow rate required to activate the heater The automatic ignition system first ignites the safety pilot burner which then ignites the main burner in about 4 seconds 7 The green LED indicator is on when the main burner is on 8 The pilot flame will e...

Страница 13: ...have yellow flames while others have good flames it is likely that dust lint or spider webs have partially clogged the burner venturis To clean the burners contact a gas service person Mineral Scale Build up The 125 HX heater when operated at lower temperature settings does not accumulate mineral build up If however the heater is used at the higher temperature settings and the water has a high min...

Страница 14: ...and component parts must be totally free of dirt In hard water areas mineral deposits can eventually 3 5 years in hard water areas corrode the water valve parts to a point where they will need replacing Any sign of moisture or corrosion at the joint of the water valve and the gas valve is a sign that the water valve components need to be serviced immediately 7 Poor circuit connections at the ECO o...

Страница 15: ...is mixing with the hot water between the 125 HX and the outlet Compare water temperature at outlet of the 125 HX hold the 125 HX outlet pipe with your hand and at the tap If these two are very different check for mixing valve or plumbing crossover see NO SPARK AT THE PILOT paragraph 2 5 Parts in water valve are dirty or damaged which will prevent the gas valve from being fully opened Water valve m...

Страница 16: ... reduce such hot water temperature in the event of any temperature instability with the use of a temperature balance shower valve refer to shower valve manufactures instructions for internal adjustment setting Adjustments should be made to the hottest setting in the shower valve Additionally the temperature control of the heater can be adjusted to produce a more comfortable hot water temperature S...

Страница 17: ...ner manifold gas pressure test nipple 4 Main gas burner 5 Pilot gas tubing 6 LED failure indicator 7 on off switch 8 LED operation indicator 9 Water valve 10 Temperature adjustment selector 11 Gas inlet gas pressure test nipple 12 Hose 3 1 4 10 11 2 9 8 6 7 5 12 6 720 606 804 10 1AL ...

Страница 18: ...18 6 720 606 804 Fig 15 INTERIOR COMPONENTS DIAGRAM AND PARTS LIST ...

Страница 19: ...7 Pilot electrovalve 8 708 501 249 18 Burner electrovalve 8 708 501 250 19 O ring 8 700 205 023 20 Hydro generator 8 707 406 043 21 Cold water pipe 8 700 705 947 22 Outlet flex hose 8 700 703 139 23 Washer 8 700 103 658 24 Water valve 8 707 002 649 25 Water valve cover 8 705 500 101 26 Diaphragm 8 700 503 053 27 Water inlet filter 8 700 507 001 28 Water valve selector screw 8 708 500 289 29 Volume...

Страница 20: ...20 6 720 606 804 Fig 16 Flow chart of 125 HX ...

Страница 21: ... in normal use and service within the applicable periods specified below in accordance with the terms of this warranty The CEC replacement will be warranted for the unexpired portion of the original warranty This warranty will be valid only for water heaters in possession of the original purchaser as recorded on the warranty card The Heat Exchanger If the heat exchanger fails within twelve 12 year...

Страница 22: ...22 6 720 606 804 ...

Страница 23: ...23 6 720 606 804 ...

Страница 24: ...ield Vermont 05673 Phone 800 642 3111 Fax 802 496 6924 www controlledenergy com tech techsupport controlledenergy com 3 1 e g a p e e s E L B A T E C N A N E T N I A M R A E Y Y R E V E S R A E Y 2 Y R E V E S R A E Y 5 3 Y R E V E E V L A V R E T A W E T A C I R B U L E V L A V R E T A W D L I U B E R N E E R C S R E T L I F R E T A W T C E P S N I Y L B M E S S A T O L I P T C E P S N I Y L B M ...

Отзывы: